22. Document revision history.........32 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document.
The IED offers many integrated protection optional RTD module for direct temperature functions for the protection of motors. The measurement. thermal overload protection, cumulative motor start up supervision, running stall GUID-3F1C43CF-24FB-4A5B-B6B2-F02D2FA02A73 V1 EN Figure 1. Protection function overview of REM610...
4. Application GUID-78DADA63-492F-4C31-A42C-A6DA12AD4069 V1 EN Figure 2. REM610 can be used for the protection of both circuit-breaker controlled and contactor controlled motor drives. In the contactor controlled motor drive application, the protection also covers the feeder cable and the cable box. The CB controlled application features a transformer and motor drive application.
Page 7
Issued: 30.10.2009 GUID-1CB5AC06-0AC1-455B-9944-98281490FC32 V1 EN Figure 3. REM610 provides a full range of protection functions for the large low-voltage motors and from small to medium sized high-voltage motors. REM610 is also used for the protection of small asynchronous power generators, for which the IED offers short- circuit and time overcurrent protection, thermal overload protection, phase unbalance and stall protection, and stator earth-fault protection.
IED calculates the thermal overload and the negative-phase-sequence current of the protected motor or generator. 8. Trip-circuit REM610 also measures a number of characteristic currents of the protected object supervision during startup and duty operation. Further, by means of an optional measurement card,...
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 connection module converts the IED's 11. Communication electrical signals to optical signals for the communication bus and, vice versa, the communication bus' optical signals to The protection IEDs are connected to the fibre- electrical signals for the IED.
Page 10
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 2. Optional communication modules and protocols Protocol Bus connection modules and gateways ● ● ● ● ● ● 60780-5-103 GUID-047CEFC9-339A-4C81-A6FD-2EB4ABEFA164 V1 EN ● ● ● Modbus (RTU and ASCII) ●...
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 12. Technical data Table 3. Dimensions Description Value Width frame 177 mm case 164 mm Height frame 177 mm (4U) case 160 mm Depth case 149.3 mm Weight 3.5 kg spare unit 1.8 kg...
Page 12
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 5. Energizing inputs Description Value Rated frequency 50/60 Hz ±5 Hz Rated current, I Thermal withstand capability: • Continuously 20 A • For 1 s 100 A 500 A •...
Page 13
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 8. Signal output SO1 Description Value Rated voltage 250 V AC/DC Continuous carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit 1 A/0.25 A/0.15 A...
Page 14
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 10. Power outputs PO1, PO2 and PO3 Description Value Rated voltage 250 V AC/DC Continuous carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s...
Page 15
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 11. RTD/analogue inputs Description Value Supported RTD sensors 100 Ω platinum TCR 0.00385 (DIN 43760) 250 Ω platinum TCR 0.00385 1000 Ω platinum TCR 0.00385 100 Ω nickel TCR 0.00618 (DIN 43760) 120 Ω...
Page 16
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 14. Environmental conditions Description Value Recommended service temperature range -10...+55ºC (continuous) Humidity <95% RH Limit temperature range (short-term) -40...+70ºC Transport and storage temperature range -40...+85ºC according to IEC 60068-2-48 Atmospheric pressure 86...106 kPa...
Page 17
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 16. Electromagnetic compatibility tests Description Type test value Reference EMC immunity test level meets the requirements listed below 1 MHz burst disturbance test, IEC 60255-22-1, IEC class III 61000-4-18 •...
Page 18
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 16. Electromagnetic compatibility tests, continued Description Type test value Reference REM610CxxHxxx Class A • Common mode 300 V rms • Differential mode 150 V rms REM610CxxLxxx and Class B REM610CxxxxMx •...
Page 19
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 18. Mechanical tests Description Reference Requirement Vibration tests (sinusoidal) According to IEC 60255-21-1 Class I Shock and bump test According to IEC 60255-21-2 Class I Protection functions Table 19. Three-phase thermal overload protection (θ>)
Page 20
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 20. Three-phase definite time overcurrent protection (I >) Value Feature Set start value, I > At definite-time characteristic 1.00...10.0 x I Start time, typical 55 ms Time/current characteristic • Definite-time operate time, t >...
Page 21
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 22. Three-phase instantaneous or definite time short circuit protection (I>>) Feature Value Set start value, I>> • At definite-time characteristic 0.50...20.0 x I Start time, typical 50 ms Time/current characteristic •...
Page 22
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 24. Instantaneous or definite-time earth-fault protection (I >) Feature Value Set start value, I > • At definite-time characteristic 1.0...100% I Start time, typical 50 ms Time/current characteristic • Definite time operate time, t >...
Page 23
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 26. Phase reversal protection (REV) Feature Value Trip value NPS ≥75% of the maximum phase current Time/current characteristic • Definite time operate time 220 ms ±50 ms Resetting time, typical 100...200 ms...
Page 24
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 Table 29. Circuit-breaker failure protection (CBFP) Feature Value Set operate time 0.10...60.0 s Phase-to phase voltage threshold for external triggering of the CBFP: • Pick-up/drop-off 0.13/0.11 x I...
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 For the routine testing purposes, the IED 13. Mounting methods cases can be equipped with test switches, type RTXP 18, which can be mounted side by side with the IED cases.
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 number and quantity. The order number 15. Selection and identifies the protection IED type and ordering data hardware and is labelled on the marking strip under the lower handle of the IED.
Page 27
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 GUID-260E75FD-7DC7-4A23-8D07-31458B45AF14 V1 EN Figure 8. Ordering key for spare units...
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 16. Accessories Table 30. Cables Item Order number Front communication cable 1MRS050698 Table 31. Mounting accessories Item Order number Semi-flush mounting kit 1MSR050696 Inclined semi-flush mounting kit 1MSR050831 19” rack mounting kit with cutout for one IED 1MSR050694 19”...
Table 35. Configuration and setting tools Tool Version Protection and Control IED Manager PCM600 2.1 or later REM610 Connectivity Package 2.1 or later CAP 501 Relay Setting Tool CAP 50 2.4.0-1 or later CAP 505 Relay Setting Tool CAP 505 v. 2.4.0-1 or later 2.4.0-1 or later...
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 18. Terminal diagram GUID-7B9F6799-0EB1-4379-91BC-265F7565D352 V2 EN Figure 9. Terminal diagram of REM610...
19. Certificates range. You can find the latest relevant information KEMA has issued a Type test Certificate of on REM610 on the product page. Complete type test for the 610 series The download area on the right-hand side of products.
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 21. Functions, codes and symbols Table 37. Functions included in REM610 Functionality IEC 60617 IEC-ANSI Protection θ> Three-phase thermal overload for motors Motor startup based on thermal stress calculation 48/14 Three-phase definite-time overcurrent, low-set >...
Motor Protection 1MRS756304 C REM610 Product version: C Issued: 30.10.2009 22. Document revision history Document revision/date Product version History A/16.05.2007 First release B/27.08.2008 Content updated to correspond to the product version C/30.10.2009 Content updated to correspond to the product version...
Page 36
Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...