Page 1
Gas Burner Controls LME... Gas burner controls for the supervision of 1- or 2-stage gas burners of small to medium capacity (typically up to 350 kW), in intermittent operation. The LME… and this Data Sheet are intended for use by OEMs which integrate the burner controls in their products.
Page 2
Warning notes To avoid injury to persons, damage to property or the environment, the following warning notes should be observed! Do not to open, interfere with or modify the unit! • All activities (mounting, installation and service work, etc.) must be performed by qualified staff •...
Page 3
Installation notes • Always run the ignition cables separate from the unit and other cables while ob- serving the greatest possible distance • Do not mix up live and neutral conductors • Install switches, fuses, earthing, etc., in compliance with local regulations •...
Page 4
Commissioning notes • When commissioning the plant for the first time or when doing maintenance work, make the following safety checks: Safety check to be carried out Anticipated response Burner startup with previously inter- LME11…: rupted line to the flame detector Max.
Page 5
Mechanical design • LME... Units of plug-in design like their predecessor types LGB... and LMG... (refer to «Dimensions») • The housing is made of impact-proof, heat-resistant and flame-retarding plastic. It is of plug-in design and engages audibly in the base •...
Page 6
Type summary (other types of burner controls on request) The type references given below apply to the LME… burner control without plug-in base and without flame detector. For ordering information on plug-in bases and other accessories, refer to «Ordering». Type Main Flame detector approx.
Page 7
Type summary (other types of burner controls on request) [cont´d] t1´ Type Main Flame detector min. min. max. approx. approx. approx. approx. min. min. min. reference voltage replacing of Burner controls for atmospheric burners LME44.056A2 LGB41.255A27 Ionization probe AC 230 V (ION) or flame LME44.057A1 LGB41.258A17...
Page 8
Ordering Gas burner control, without plug-in base refer to «Type summary» Connection accessories for small burner controls refer to Data Sheet N7201 Plug-in base AGK11... Cable holders AGK65..., AGK66, AGK67... Cable strain relief elements for AGK67... Connection accessories for small burner controls refer to Data Sheet N7203 Plug-in base AGK13...
Page 9
Technical data General unit data Mains voltage AC 120 V +10 % / -15 % AC 230 V +10 % / -15 % Mains frequency 50...60 Hz ±6 % Power consumption 12 VA External primary fuse (Si) max. 10 A (slow) Mounting position optional Input current at terminal 12...
Page 10
Technical data (cont´d) Flame supervision At mains voltage with ionization probe UN = AC 230 V ¹) Detector voltage between ionization probe and ground AC 115...240 V (AC voltmeter Ri ≥ 10 MΩ) Switching threshold (limit values): Switching on (flame on) (DC ammeter Ri ≤ 5 kΩ) ≥...
Page 11
Technical data (cont´d) Flame supervision Mains voltage AC 230 V +10 % / -15 % 50...60 Hz ±6 % with AGQ3… and UV Mains frequency detector QRA... Perm. cable length from QRA... to AGQ3… max. 20 m (lay separate cable) Perm.
Page 12
Technical data (cont´d) Flame supervision Detector current required Perm. detector current Possible detector current with QRC... (with flame) (without flame) with flame (typically) QRC... Min. 70 µA Max. 5.5 µA Max. 100 µA (only LME23…) The values given in the table above only apply under the following conditions: - Mains voltage AC 230 V - Ambient temperature 23 °C Green LED for opera-...
Page 13
Functions • Preconditions for Burner control must be reset • burner startup All contacts in the line are closed, request for heat • No undervoltage • Air pressure switch «LP» must be in its no-load position or CPI or wire link 2 •...
Page 14
Operation, indication, diagnostics Operation Lockout reset button «EK...» is the key operating element for resetting the burner control and for activating / deactivating the diagnostics func- tions. The multicolor signal lamp (LED) in the lockout reset button is the key Yellow indicating element for visual diagnostics and interface diagnostics.
Page 15
Operation, indication, diagnostics (cont´d) Diagnostics of the cau- After lockout, the red fault signal lamp will remain steady on. In that condition, visual se of fault diagnostics of the cause of fault according to the error code table can be activated by pressing the lockout reset button for more than 3 seconds.
Page 16
Connection diagram and control sequence LME11… µC control RESET K2/1 K2/2 R / W 7101a24e/0606 B´ SB / R W / GP 16/23 Building Technologies CC1N7101en HVAC Products 29.06.2006...
Page 17
Connection diagram and control sequence LME21… µC control RESET K2/1 K2/2 R / W 7101a22e/0606 B´ SB / R W / GP (LR) BV2 7101d05/0206 Application examples only LME11… / LME21… / LME22… The suitable wiring schemes are merely examples which must be verified in the individual case depending on application! Burner without fan and without «LP»...
Page 18
Application examples The suitable wiring schemes are merely examples which must be verified in the individual case depending on application! Control of actuators of 2-stage or 2-stage modulating 7101a09/0705 burners. Controlled prepurging «t1» with low-fire air volume. Same low-fire actuator position during startup and operation.
Page 19
Connection diagram and control sequence LME22… / LME23… µC control RESET K2/1 K2/2 R / W Nur LME23... br bl 7101a02e/0606 B´ SB / R W / GP (LR) BV2 7101d02/0606 19/23 Building Technologies CC1N7101en HVAC Products 29.06.2006...
Page 20
Application examples The suitable wiring schemes are merely examples which must be verified in the individual case depending on application! Control of actuators of 2-stage or 2-stage modulating burn- 7101a13/0804 ers. Controlled prepurging «t1» with nominal load air volume. For information about actuators «SA»: SQN3...: Refer to Data Sheet N7808 SB/R/W SQN7...: Refer to Data Sheet N7804...
Page 21
Connection diagram and control sequence LME44… µA control RESET K2/1 K2/2 R / W 7101a20e/0606 B´ SB / R W / GP 7101d06/0206 t1´ 21/23 Building Technologies CC1N7101en HVAC Products 29.06.2006...
Page 22
Legend AGK25... PTC resistor Error message (alarm) Burner Communication Interface BV... Fuel valve Closed Position Indicator Dbr... Wire link EK... Remote lockout reset button (internal) Remote lockout reset button Ionization probe Flame signal Flame signal amplifier Gas pressure switch Main switch Auxiliary contactor, relay Ionization probe K1...5...