ABB Relion REM615 Product Manual

ABB Relion REM615 Product Manual

Relion 615 series motor protection and control
Hide thumbs Also See for Relion REM615:

Advertisement

®
Relion
615 series
Motor Protection and Control
REM615
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion REM615

  • Page 1 ® Relion 615 series Motor Protection and Control REM615 Product Guide...
  • Page 2: Table Of Contents

    15. Current circuit supervision........16 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document.
  • Page 3: Description

    REM615 is a member of ® ABB’s Relion product family and part of its REM615 is available in three alternative 615 protection and control product series. standard configurations. The standard signal...
  • Page 4 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 2. Supported functions Functionality 1)2) Protection Three-phase non-directional overcurrent protection, low ● ● ● stage, instance 1 Three-phase non-directional overcurrent protection, ● ● ● instantaneous stage, instance 1 ●...
  • Page 5 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 2. Supported functions, continued Functionality Control ● ● ● Circuit-breaker control ● ● ● Disconnector position indication, instance 1 ● ● ● Disconnector position indication, instance 2 ●...
  • Page 6: Protections Functions

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 6) Uo selectable by parameter, Uo measured as default. 7) Multi-purpose protection is used for, for example, RTD/mA based protection. The RTD/mA module offered as an option for 3.
  • Page 7 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 GUID-B0430A61-AAA8-424B-AB30-5D5D6A0375FE V1 EN Figure 1. Protection function overview of standard configuration A...
  • Page 8 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 GUID-3CDDC6F1-6747-4CC8-9D6F-72C3895A496B V1 EN Figure 2. Protection function overview of standard configuration B...
  • Page 9: Application

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 GUID-12D3399C-F58F-441D-A795-A71F71910B19 V2 EN Figure 3. Protection function overview of standard configuration C connection can also be used for earth-fault 4. Application protection. In that case possible unwanted operations of the earth-fault protection at motor start-up due to CT saturation can be REM615 constitutes main protection for prevented using the IED's internal...
  • Page 10 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Furthermore, the RTD/mA inputs can be used Temperature values can also, vice versa, be for measuring the ambient cooling air received from other IEDs over the station temperature. The analog temperature values bus, thus increasing the extent of relevant can, if required, be sent to other IEDs using information.
  • Page 11 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 GUID-52860380-D410-4969-A44E-7C7311221D0F V2 EN Figure 4. Motor protection and control of contactor and circuit-breaker controlled motors using REM615s with the standard configurations A and B. To prevent possible power system instability due to busbar voltage collapse, the simultaneous starting of several motors is inhibited.
  • Page 12: Supported Abb Solutions

    COM600 features a web-browser based HMI providing a customizable graphical display ABB’s 615 series protection and control IEDs for visualizing single line mimic diagrams for together with the COM600 Station switchgear bay solutions. The SLD feature is...
  • Page 13 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 3. Supported ABB solutions Product Version Station Automation COM600 3.4 or later MicroSCADA Pro 9.2 SP2 or later System 800xA 5.0 Service Pack 2 System 800xA COM600...
  • Page 14: Control

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 6. Control 8. Disturbance recorder The IED offers control of one circuit breaker The IED is provided with a disturbance with dedicated push-buttons for circuit recorder featuring up to 12 analog and 64 breaker opening and closing.
  • Page 15: Recorded Data

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 accessed, either locally or remotely, using the 12. Trip-circuit web-browser based user interface. supervision The trip-circuit supervision continuously 10. Recorded data monitors the availability and operability of the trip circuit. It provides open-circuit The IED has the capacity to store the records monitoring both when the circuit breaker is of 32 latest fault events.
  • Page 16: Current Circuit Supervision

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 voltage inputs and one residual voltage input. 15. Current circuit The phase-current inputs and the residual supervision current inputs are rated 1/5 A, that is, the inputs allow connection of either 1 A or 5 A secondary current transformers.
  • Page 17: Communication

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 4. Input/output overview Standard Analog inputs Binary inputs/outputs configurat mA inputs inputs 4 (12) 6 (10) 8 (14) 10 (13) 1) With optional RTD/mA module. 2) With optional binary I/O module. 3) The optional I/O module and the optional RTD/mA modules are mutually exclusive.
  • Page 18 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 spanning tree protocol (RSTP) support to be The IEC 60870-5-103 implementation created. The managed switch controls the supports two parallel serial bus connections consistency of the loop, routes the data and to two different masters.
  • Page 19 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Client A Client B Network Network Managed Ethernet switch Managed Ethernet switch with RSTP support with RSTP support REU615 REM615 RED615 REF615 RET615 GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V1 EN Figure 6. Self-healing Ethernet ring solution Table 5.
  • Page 20: Technical Data

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 19. Technical data Table 6. Dimensions Description Value Width frame 177 mm case 164 mm Height frame 177 mm (4U) case 160 mm Depth 201 mm (153 + 48 mm) Weight complete IED 4.1 kg...
  • Page 21 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 8. Energizing inputs Description Value Rated frequency 50/60 Hz Current inputs Rated current, I 0.2/1 A 1/5 A Thermal withstand capability: • Continuously 20 A • For 1 s 100 A 500 A Dynamic current...
  • Page 22 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 10. RTD/mA measurement (XRGGIO130) Description Value RTD inputs Supported RTD 100 Ω platinum TCR 0.00385 (DIN 43760) sensors 250 Ω platinum TCR 0.00385 100 Ω nickel TCR 0.00618 (DIN 43760) 120 Ω...
  • Page 23 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 12. Double-pole power output relays with TCS function Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit 5 A/3 A/1 A...
  • Page 24 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 15. Station communication link, fibre-optic Connector Wave Max. Permitted path Fibre type length distance attenuation MM 62.5/125 μm 1300 nm 2 km <8 dB glass fibre core SM 9/125 μm 1300 nm 2-20 km...
  • Page 25 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 19. Environmental conditions Description Value Operating temperature range -25...+55ºC (continuous) Short-time service temperature range 1)2) -40...+85ºC (<16h) Relative humidity <93%, non-condensing Atmospheric pressure 86...106 kPa Altitude Up to 2000 m Transport and storage temperature range -40...+85ºC 1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC...
  • Page 26 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 21. Electromagnetic compatibility tests Description Type test value Reference 1 MHz/100 kHz burst IEC 61000-4-18 disturbance test: IEC 60255-22-1, class III IEEE C37.90.1-2002 • Common mode 2.5 kV •...
  • Page 27 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 21. Electromagnetic compatibility tests, continued Description Type test value Reference Voltage dips and short 30%/10 ms IEC 61000-4-11 interruptions 60%/100 ms 60%/1000 ms >95%/5000 ms Power frequency immunity Binary inputs only IEC 61000-4-16 test:...
  • Page 28 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 22. Insulation tests Description Type test value Reference Dielectric tests IEC 60255-5 and IEC 60255-27 • Test voltage 2 kV, 50 Hz, 1 min 500 V, 50 Hz, 1 min, communication Impulse voltage test IEC 60255-5 and IEC 60255-27...
  • Page 29 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 25. EMC compliance Description Reference EMC directive 2004/108/EC Standard EN 50263 (2000) EN 60255-26 (2007) Table 26. RoHS compliance Description Complies with RoHS directive 2002/95/EC...
  • Page 30 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Protection functions Table 27. Three-phase non-directional overcurrent protection (PHxPTOC) Characteristic Value Operation accuracy Depending on the frequency of the current measured: f ±2 Hz PHLPTOC ±1.5% of the set value or ±0.002 x I ±1.5% of set value or ±0.002 x I PHHPTOC (at currents in the range of 0.1…10 x I...
  • Page 31 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 28. Three-phase non-directional overcurrent protection (PHxPTOC) main settings Parameter Function Value (Range) Step Start Value PHLPTOC 0.05...5.00 x I 0.01 0.10...40.00 x I 0.01 PHHPTOC PHIPTOC 1.00...40.00 x I 0.01 Time multiplier PHLPTOC...
  • Page 32 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 29. Directional earth-fault protection (DEFxPDEF) Characteristic Value Operation accuracy Depending on the frequency of the current measured: f ±2 Hz DEFLPDEF Current: ±1.5% of the set value or ±0.002 x I Voltage ±1.5% of the set value or ±0.002 x U Phase angle:...
  • Page 33 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 30. Directional earth-fault protection (DEFxPDEF) main settings Parameter Function Value (Range) Step Start Value DEFLPDEF 0.010...5.000 x I 0.005 0.10...40.00 x I 0.01 DEFHPDEF Directional mode DEFLPDEF and 1=Non-directional DEFHPDEF 2=Forward...
  • Page 34 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 31. Non-directional earth-fault protection (EFxPTOC) Characteristic Value Operation accuracy Depending on the frequency of the current measured: f ±2 Hz EFLPTOC ±1.5% of the set value or ±0.002 x I EFHPTOC ±1.5% of set value or ±0.002 x I (at currents in the range of 0.1…10 x I...
  • Page 35 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 32. Non-directional earth-fault protection (EFxPTOC) main settings Parameter Function Value (Range) Step Start value EFLPTOC 0.010...5.000 x I 0.005 EFHPTOC 0.10...40.00 x I 0.01 1.00...40.00 x I 0.01 EFIPTOC Time multiplier...
  • Page 36 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 33. Three phase undervoltage protection (PHPTUV) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz ±1.5% of the set value or ±0.002 x U 1)2) Minimum Typical...
  • Page 37 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 35. Positive sequence undervoltage protection (PSPTUV) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±2 Hz ±1.5% of the set value or ±0.002 x U 1)2) Minimum Typical...
  • Page 38 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 37. Frequency protection (FRPFRQ) Characteristic Value Operation accuracy f>/f< ±10 mHz df/dt ±100 mHz/s (in range |df/ dt| < 5 Hz/s) ± 2.0% of the set value (in range 5 Hz/s <...
  • Page 39 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 38. Frequency protection (FRPFRQ) main settings Parameter Values Unit Step Default Description (Range) Operation mode 1=Freq< 1=Freq< Frequency 2=Freq> protection 3=df/dt operation mode 4=Freq< + df/dt selection 5=Freq>...
  • Page 40 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 39. Negative sequence overvoltage protection (NSPTOV) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±2 Hz ±1.5% of the set value or ±0.002 × U 1)2) Minimum Typical...
  • Page 41 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 41. Negative phase-sequence overcurrent protection for motors (MNSPTOC) Characteristic Value Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz ±1.5% of the set value or ±0.002 x I 1)2) Minimum Typical...
  • Page 42 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 43. Loss of load supervision (LOFLPTUC) Characteristic Value Operation accuracy Depending on the frequency of the current measured: f ±2 Hz ±1.5% of the set value or ±0.002 x I Start time Typical 300 ms Reset time...
  • Page 43 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 46. Motor load jam protection (JAMPTOC) main settings Parameter Function Value (Range) Step Operation JAMPTOC Start value JAMPTOC 0.10...10.00 x I 0.01 Operate delay time JAMPTOC 100...120000 ms Table 47.
  • Page 44 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 49. Phase reversal protection (PREVPTOC) Characteristic Value Operation accuracy Depending on the frequency of the current measured: f ±2 Hz ±1.5% of the set value or ±0.002 x I 1)2) Minimum Typical...
  • Page 45 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 52. Thermal overload protection for motors (MPTTR) main settings Parameter Function Value (Range) Step Env temperature MPTTR FLC Only mode Use RTD Set Amb Temp Env temperature set MPTTR -20.0...70.0 °C Alarm thermal value...
  • Page 46 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 54. Circuit breaker failure protection (CCBRBRF) main settings Parameter Function Value (Range) Step Current value CCBRBRF 0.05...1.00 x I 0.05 (Operating phase current) Current value Res CCBRBRF 0.05...1.00 x I 0.05 (Operating residual...
  • Page 47 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 56. Arc protection (ARCSARC) main settings Parameter Function Value (Range) Step Phase start value ARCSARC 0.50...40.00 x I 0.01 (Operating phase current) Ground start value ARCSARC 0.05...8.00 x I 0.01 (Operating residual current)
  • Page 48 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Measurement functions Table 60. Three-phase current measurement (CMMXU) Characteristic Value Operation accuracy Depending on the frequency of the current measured: f ±2 Hz ±0.5% or ±0.002 x I (at currents in the range of 0.01...4.00 x I Suppression of harmonics DFT: -50 dB at f = n x f...
  • Page 49 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 63. Residual voltage measurement (RESVMMXU) Characteristic Value Operation accuracy Depending on the frequency of the current measured: f/f = ±2 Hz ±0.5% or ±0.002 x U Suppression of harmonics DFT: -50 dB at f = n x f , where n = 2, 3, 4, 5, …...
  • Page 50 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 66. RTD/mA measurement (XRGGIO130) Description Value RTD inputs Supported RTD 100 Ω platinum TCR 0.00385 (DIN 43760) sensors 250 Ω platinum TCR 0.00385 100 Ω nickel TCR 0.00618 (DIN 43760) 120 Ω...
  • Page 51 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Supervision functions Table 68. Current circuit supervision (CCRDIF) Characteristic Value < 30 ms Operate time 1) Including the delay of the output contact. Table 69. Current circuit supervision (CCRDIF) main settings Parameter Values (Range) Unit...
  • Page 52: Local Hmi

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 configuration, the IED displays the related 20. Local HMI measuring values, apart from the default single line diagram. The SLD view can also be accessed using the web-browser based The IED is available with two optional user interface.
  • Page 53: Mounting Methods

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 73. Large display Rows in the view Characters per row Character size Small, mono-spaced (6x12 pixels) Large, variable width (13x14 pixels) 8 or more 1) Depending on the selected language type RTXP 18, which can be mounted side by 21.
  • Page 54: Ied Case And Ied Plug-In Unit

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 placed above the HMI on the upper part of 22. IED case and IED the plug-in-unit. An order number label is plug-in unit placed on the side of the plug-in unit as well as inside the case.
  • Page 55 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 H B M B C C A H B C C 1 B B N 1 X D DESCRIPTION A = Motor protection, optional RTD/mA inputs B = Motor protection with current, voltage and frequency based protection and measurement functions, optional RTD/mA inputs C = Motor protection with current and voltage based protection...
  • Page 56 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 The communication module hardware determines the available communication protocols. H B M B C C A H C 1 B B N 1 X D DESCRIPTION Communication modules (Serial/Ethernet) Serial RS-485, incl.
  • Page 57 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 H B M B C C A H B C 1 B B N 1 X D DESCRIPTION Communication protocols IEC 61850 (for Ethernet communication modules and IEDs without a communication module ) Modbus (for Ethernet/serial or Ethernet + serial commu-...
  • Page 58: Accessories And Ordering Data

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Example code: H B M B C C A H B C C 1 B B N 1 X D Your ordering code: Digit (#) 10 11 12 13 14 15 16 17 18 ...
  • Page 59: Tools

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 locally or remotely using a web browser (IE 25. Tools 7.0 or later). For security reasons, the web- browser based user interface is disabled by default. The interface can be enabled with The IED is delivered as a pre-configured unit.
  • Page 60 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 77. Supported functions Function WebHMI PCM600 PCM600 PCM600 Engineering Engineering ● ● ● ● IED parameter setting Saving of IED parameter settings in ● ● ● ● the IED ●...
  • Page 61 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 77. Supported functions, continued Function WebHMI PCM600 PCM600 PCM600 Engineering Engineering Application ● ● configuration IEC 61850 communication configuration, GOOSE (communication ● configuration) Phasor diagram ● viewing ●...
  • Page 62: Terminal Diagrams

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 26. Terminal diagrams GUID-B2057B3C-DDFD-4A85-98AF-9E14D947439D V1 EN Figure 13. Terminal diagram of standard configuration A...
  • Page 63 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 GUID-FB8CC4CD-F5ED-4FE5-837D-B39CB06ED67C V1 EN Figure 14. Terminal diagram of standard configuration B...
  • Page 64 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 GUID-1589F909-AB4D-44A7-9445-057B7385AFD7 V2 EN Figure 15. Terminal diagram of standard configuration C...
  • Page 65: References

    27. References the web page contains the latest product documentation, such as technical reference manual, installation manual, operators www.abb.com/substationautomation manual, etc. The selection tool on the web portal offers you information about the page helps you find the documents by the distribution automation product and service document category and language.
  • Page 66: Functions, Codes And Symbols

    Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 28. Functions, codes and symbols Table 78. REM615 Functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent protection, low stage, PHLPTOC1 3I> (1) 51P-1 (1) instance 1 Three-phase non-directional...
  • Page 67 Motor Protection and Control 1MRS756890 D REM615 Product version: 3.0 Issued: 2010-06-29 Table 78. REM615 Functions, codes and symbols, continued Function IEC 61850 IEC 60617 IEC-ANSI Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2) Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
  • Page 68: Document Revision History

    1) Multi-purpose protection is used for, for example, RTD/mA based protection. 29. Document revision history Document revision/ Product version History date A/2009-07-03 First release B/2009-10-01 Content updated C/2010-06-11 Content updated to correspond to the product version D/2010-06-29 Terminology corrected Download the latest documents from the ABB web site http://www.abb.com/ substationautomation.
  • Page 72 Distribution Automation Maneja Vadodara 390013, India Phone +91 265 2604032 +91 265 2638922 Transmission and Distribution Automation Equipment (Xiamen) Co. Ltd. ABB Industrial Park, Torch Hi-tech Development Zone 361006 Xiamen, Fujian, China Phone +86 592 5702288 +86 592 5718598 www.abb.com/substationautomation...

This manual is also suitable for:

Relion 615 seriesRem615