Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
The pre- GUID-0021B61F-B1F1-4B39-81C5-E1FB78EA87ED v3 REC650 is used for the control, protection and monitoring of configured IED can be changed and adapted to suit specific different types of bays in power networks. The IED is applications with the application configuration tool.
Page 4
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 REC650 A02 – Double busbar in single breaker arrangement 12AI (7I + 5U) VN MMXU Control Control Control SC/VC S CILO S CSWI S XSWI VN MMXU SES RSYN...
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 are not exposed to the user or do not need 2. Available functions GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1 to be configured are not described in this manual. The following tables list all the functions available in the IED.
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v16 IEC 61850 or ANSI Function description Bay control function name REC650 (A02) Control SESRSYN Synchrocheck, energizing check and synchronizing APC10 Control functionality for a single bay, max 10 objects (1CB), including interlocking...
Page 7
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Bay control function name REC650 (A02) ANDQT, Configurable logic blocks Q/T (see Table 3) INDCOMBSPQT, INDEXTSPQT, INVALIDQT, INVERTERQT, ORQT, PULSETIMERQT, RSMEMORYQT, SRMEMORYQT, TIMERSETQT,...
Page 8
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Table 1. Number of function instances in APC10 Function name Function description Total number of instances SCILO Interlocking BB_ES A1A2_BS A1A2_DC ABC_BC BH_CONN BH_LINE_A BH_LINE_B DB_BUS_A DB_BUS_B DB_LINE ABC_LINE...
Page 9
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Table 3. Total number of instances for configurable logic blocks Q/T Configurable logic blocks Q/T Total number of instances ANDQT INDCOMBSPQT INDEXTSPQT INVALIDQT INVERTERQT ORQT PULSETIMERQT RSMEMORYQT SRMEMORYQT TIMERSETQT...
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Bay control function name REC650 (A02) Monitoring CVMMXN Power system measurement CMMXU Current measurement VMMXU Voltage measurement phase-phase CMSQI Current sequence measurement VMSQI...
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Bay control function name REC650 (A02) TEILGAPC Running hour meter Metering PCFCNT Pulse-counter logic ETPMMTR Function for energy calculation and demand handling...
Page 12
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v16 IEC 61850 or ANSI Function description Bay control function name REC650 (A02) Station communication LONSPA, SPA SPA communication protocol LON communciation protocol HORZCOMM Network variables via LON...
Page 13
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Bay control function name REC650 (A02) FSTACCS Field service tool access IEC 61850-9-2 Process bus communication, 4 merging units 1-P31 ACTIVLOG Activity logging...
Page 14
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v13 Table 4. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list TIMESYNCHGEN Time synchronization module BININPUT, SYNCHCAN,...
Page 15
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Table 5. Local HMI functions IEC 61850 or function ANSI Description name LHMICTRL Local HMI signals LANGUAGE Local human machine language SCREEN Local HMI Local human machine screen behavior FNKEYTY1–FNKEYTY5...
Page 16
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 In normal security, the command is processed and the Each of the 9 circuit switch controllers SXSWI provides the resulting position is not supervised. However with enhanced actual position status and pass the commands to the primary...
Page 17
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 • Line for double and transfer busbars, ABC_LINE GOOSE function block to receive a switching device • Bus coupler for double and transfer busbars, ABC_BC GOOSEXLNRCV • Transformer bay for double busbars, AB_TRAFO...
Page 18
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 means, such as binary inputs and SPGAPC function blocks. The fuse failure supervision function basically has three The commands can be pulsed or steady with a settable pulse different detection methods, negative sequence and zero time.
Page 19
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 according to the specific application needs for settable pulse • SRMEMORY function block is a flip-flop that can set or or steady output. reset an output from two inputs respectively. Each block has two outputs where one is inverted.
Page 20
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 • PULSETIMERQT Pulse timer function block can be used, Boolean to integer conversion, 16 bit B16I for example, for pulse extensions or limiting of operation SEMOD175725-4 v5 Boolean to integer conversion, 16 bit (B16I) is used to of outputs.
Page 21
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Disturbance report (DRPRDRE), always included in the IED, The Indication list function shows all selected binary input acquires sampled data of all selected analog input and binary signals connected to the Disturbance recorder function that signals connected to the function block with a maximum of have changed status during a disturbance.
Page 22
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 The disturbance recorder information for up to 100 input signals to the function. In addition, the function disturbances are saved in the IED and the local HMI is used generates alarms based on the received information.
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 8. Metering AMU0600442 v15 Pulse-counter logic PCFCNT M13394-3 v7 Pulse-counter logic (PCFCNT) function counts externally generated binary pulses, for instance pulses coming from an external energy meter, for calculation of energy consumption values.
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 synchronization method that can be used to maintain a Routes common time within a station. This time can be synchronized GUID-95F9C7BA-92F8-489F-AD0A-047410B5E66F v1 A route is a specified path for data to travel between the to the global time using, for instance, a GPS receiver.
Page 25
SPA communication protocol SEMOD120134-5 v1 parameter is defined for each output signal. A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation Status for user-defined signals for IEC 60870-5-103 automation systems but the main use is for Substation I103USRDEF Monitoring Systems SMS.
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 14. Hardware description Function commands generic for IEC 60870-5-103 I103GENCMD Hardware modules IP14529-1 v1 I103GENCMD is used for transmitting generic commands Numeric processing module NUM M12643-3 v4 over IEC 60870-5-103. The function has two output signals,...
Page 27
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 however a control of the output. The 4-wire connection has separated signals for RX and TX multidrop communication with a dedicated Master and the rest are slaves. No special control signal is needed in this case.
Page 28
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 • Wall mounting kit See ordering for details about available mounting alternatives.
Connection diagram, 650 series 2.2 IEC 1MRK006501-AG The latest versions of the connection diagrams can be Connection diagram, 650 series 2.2 ANSI 1MRK006502-AG downloaded from http://www.abb.com/protection-control. Connection diagrams for Configured products Connection diagram, REC650 2.2, A02X00 1MRK006507-CA...
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 16. Technical data General M10993-1 v3 IP11376-1 v2 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range...
Page 31
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Energizing quantities, rated values and limits Analog inputs M16988-1 v11 IP15842-1 v1 Table 6. TRM - Energizing quantities, rated values and limits for protection transformer Description Value Frequency Rated frequency f...
Page 32
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Table 8. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20% 220/250 V RL ±20%...
Page 33
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 M12573-1 v10 The stated operate time for functions include the operating time for the binary inputs and outputs. Table 10. IOM - Binary input/output module Quantity Rated value Nominal range...
Page 34
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 M12318-1 v9 The stated operate time for functions include the operating time for the binary inputs and outputs. Table 11. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Page 35
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 M12584-1 v9 The stated operate time for functions include the operating time for the binary inputs and outputs. Table 12. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Page 36
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 M12441-1 v9 The stated operate time for functions include the operating time for the binary inputs and outputs. Table 13. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Page 37
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Table 15. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/%...
Page 38
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Table 18. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III...
Page 39
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Table 20. Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1 Cold storage test Test Ab for 16 h at -40°C...
Page 40
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Multipurpose protection M13095-2 v10...
Page 41
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Table 23. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2-phase3, phase3-phase1,...
Page 42
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Table 23. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Independent time delay, overvoltage at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater 0.8 x U...
Page 43
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Secondary system supervision M12358-1 v10 Table 24. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I > I Reset ratio, Operate current >90%...
Page 44
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Control M12359-1 v15 Table 26. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase...
Page 45
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Scheme communication...
Page 46
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Logic M12380-1 v13 Table 27. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s...
Page 47
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3 Table 34. Number of AND instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v3 Table 35. Number of GATE instances Logic block...
Page 48
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 GUID-C6C98FE0-F559-45EE-B853-464516775417 v3 Table 42. Number of TIMERSET instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms TIMERSET (0.000–90000.000) s ±0.5% ±10 ms GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v2 Table 43.
Page 49
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 GUID-61263951-53A8-4113-82B5-3DB3BF0D9449 v1 Table 50. Number of PULSETIMERQT instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms (0.000–90000.000) s ±0.5% ±10 ms...
Page 50
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2 Table 58. Number of ITBGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms ITBGAPC GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4 Table 59. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC...
Page 51
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Monitoring M12386-1 v16 Table 63. Power system measurement CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U≤ 50 V ±0.2% of U at U>...
Page 52
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6 Table 66. Voltage measurement phase-earth VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V...
Page 53
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 M12760-1 v11 Table 70. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out...
Page 54
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v8 Table 72. Insulation supervision for liquid medium function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value Oil lockout level 1.00-100.00 ±10.0% of set value Temperature alarm level -40.00-200.00...
Page 55
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 M13765-1 v5 Table 76. Indications Function Value Buffer capacity Maximum number of indications presented for single disturbance Maximum number of recorded disturbances M12702-1 v4 Table 77. Event recorder Function...
Page 56
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Metering M13404-2 v5 Table 82. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value SEMOD153707-2 v5 Table 83.
Page 57
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Station communication M15031-1 v9 Table 84. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0...
Page 58
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 M12589-1 v4 Table 89. SLM – LON port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *)
Page 59
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Hardware M11778-1 v7 SEMOD53385-1 v1 Table 93. Case Material Steel sheet Front plate Stainless steel with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) M12327-1 v5 Table 94.
Page 60
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3 Table 100. NUM: Communication ports 4 Ethernet ports 1 Basic, 3 Optional Ethernet connection type SFP Optical LC or Galvanic RJ45...
Page 61
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Basic IED functions M11963-1 v5 Table 101. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v9 Table 102.
To obtain the complete ordering code, please combine code from the tables, as given in the example below. Example code: REC650*2.2-A02X00- P23-B1A12-AA-CA-B-A3-CD1AX-KXXXXXLXGX. Using the code of each position #1-11 specified as REC650*1-2 2-3-4 4-5 6-7 7-8-9 9-10 10 10-11 11 11...
Page 63
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Power supply modules Ordering no Notes and rules Compression terminals 1MRK002960-GA Ringlug terminals 1MRK002960-HA Power supply module, 24-60 VDC 1MRK002239-AB Power supply module, 90-250 VDC 1MRK002239-BB Selection for position #7...
Page 64
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Binary input/output modules Ordering no Notes and rules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1 BIM required in position P3 and 1 BOM always included in position P4.
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 18. Ordering for Accessories Test switches type RTXP 24 is ordered separately. Please refer to Section Related documents for references to Accessories corresponding documents. IP15151-1 v1 Test switch SEMOD111888-5 v12...
Page 66
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 User documentation Rule: Specify the number of printed manuals requested Application manual Quantity: 1MRK 511 423-UEN Technical manual Quantity: 1MRK 511 424-UEN Commissioning manual Quantity: 1MRK 511 425-UEN Communication protocol manual, IEC 61850 Edition 1...
Page 67
1MRK 511 426-BEN B Bay control REC650 2.2 Product version: 2.2 Related documents GUID-94E8A5CA-BE1B-45AF-81E7-5A41D34EE112 v6 Documents related to REC650 Document numbers Application manual 1MRK 511 423-UEN Commissioning manual 1MRK 511 425-UEN Product guide 1MRK 511 426-BEN Technical manual 1MRK 511 424-UEN...