9-2. Performing Test Run with Optional Wired Remote Control Unit 9-3. Basic Function of the Service Valves 9-4. Pump Down S4359128 Outdoor units C1852, CL1852 SANYO FISHER COMPANY A DIVISION OF SANYO NORTH AMERICA CORPORATION 21605 Plummer Street Chatsworth, CA91311...
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. When Installing ……………………………………………………………………...
1. General This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning. 1-1.
1-7. Tubing Length Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. Select and decide the installation location so that the length of the refrigerant tubing will be within the limits given in Table 1-2. Table 1-2 Tubing Data Narrow tube...
2. Selecting the Installation Site Indoor Unit AVOID: areas where leakage of flammable gas may be expected. places where large amount of oil mist exist. direct sunlight. locations near heat sources which may affect performance of the unit. locations where external air may enter the room directly.
(Fig. 2-5) This unit is designed so that the fan of the outdoor unit runs at low speed when the air conditioner is operated at low outdoor air temperatures. When the outdoor unit is exposed to strong wind, the system pressure drops because of the freeze protector.
Table 3-1 Length Type XS1852 (PNR-XS2432) 32-9/32 (820) 28-3/4 (730) (3) Determine the pitch of the suspension bolts using the supplied full-scale installation diagram. The diagram and table (Fig. 3-3 and Table 3-2) show the relationship between the positions of the suspension fitting, the unit, and the panel.
3-3. Placing the Unit Inside the Ceiling (1) When placing the unit inside the ceiling, deter- mine the pitch of the suspension bolts using the supplied full-scale installation diagram. (Fig. 3-4) The size of the opening for the indoor unit can be confirmed by attaching the full-scale installation diagram beneath the unit.
3-4. Installing the Drain Piping (1) Prepare standard hard PVC pipe (O.D. 1-3/64 in.) for the drain and use the supplied drain hose and hose band to prevent water leaks. The PVC pipe must be purchased separately. The transparent part allows you to check drain- age.
3-5. Checking the Drainage After wiring and piping are completed, use the follow- ing procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth ready to catch and wipe up spilled water. Do not supply power to the unit until the tubing and wiring to the outdoor unit are completed.
Ceiling Panel Never touch or attempt to move the air direction louver CAUTION by hand or you may damage the unit. Instead, use the remote control unit if you want to change the direction or air flow. 3-6. Before Installing the Ceiling Panel (1) Remove the air-intake grille and air filter from the ceiling panel.
3-7. Installing the Ceiling Panel (1) Lift the ceiling panel and position it to align the panel hook with the panel catch of the indoor unit. NOTE The ceiling panel must be mounted in the correct direction. Note that the 2 catches of the panel differ in size.
3-9. Duct for Fresh Air Air-intake chamber (including Duct connection box and flange) are attached to the indoor unit when used to take fresh outdoor air. High-performance filter or Super long-life filter can be also installed in the air-intake chamber. (1) SETUP PRIOR TO INSTALLATION When installing the high performance filter or super long-life filter, the parts and parts numbers of filters to be assembled with the air-intake chamber are listed below.
Page 14
(b) INSTALLING THE AIR-INTAKE CHAMBER Set the air-intake chamber to the indoor unit taking care not to set to the incorrect direction. (Fig. 3-17) Fasten the air-intake camber with the accessory screws. (M5 L125, 4pcs) (Fig. 3-17) (c) INSTALLING THE DUCT CONNECTION BOX Fasten the duct connection flange to the duct connection box with the accessory screws (M4 L12, 4 pcs.).
In direct sunlight Behind a curtain or other place where it is covered More than 26 ft. away from the air conditioner In the path of the air conditioner’s airstream Where it may become extremely hot or cold Where it may be subject to electrical or magnetic interference 4-1.
Wired Remote Control Unit (Option) (1) To access the printed circuit board, remove the cover plate of the electrical component box. (2) Attach the remote control connectors securely to the mating connector pins on the printed circuit board. (3) Turn the R.C.U. switch from “WIRELESS” to “WIRED”.
5. Address Switches If you are installing one indoor unit or one group of indoor units in the same room, it is necessary for you to assign each unit its own address so that each can be operated by its own remote control unit. You assign the addresses by matching the switch position of each indoor unit with the switch position of its remote control unit.
Electric Code: ANSI/NFPA70) before beginning. You must ensure that installation complies with all relevant rules and regulations. (8) To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows: The inter-unit control wiring and the remote control wiring (option) should be wired apart from the inter- unit power wiring.
Grounding line Indoor unit Outdoor unit 1304_C_I INDOOR INDOOR UNIT Disconnect switch (Field supply) CAUTION Problem 2 Air conditioner will not operate. Disconnect switch Grounding line Indoor unit Outdoor unit 1302_C_I Disconnect switch Grounding line Indoor unit Outdoor unit...
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected. When connecting each power wire to the correspond- ing terminal, follow the instructions on “How to connect wiring to the terminal”...
7. How to Process Tubing The narrow tubing side is connected by flare nut, and the wide tubing side is connected by brazing. 7-1. Use of the Flaring Method Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units.
7-4. Precautions during Brazing Replace air inside the tube with nitrogen gas to prevent copper oxide film from forming during the brazing process. Do not allow the tubing to get too hot during the brazing process. The nitrogen gas inside the tubing may overheat, causing refrigerant system valves to become damaged.
Important Because capillary tubing is installed in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. Therefore, to prevent heat loss and wet floors due to dripping of condensation water, both tubes must be well insulated with proper insulation material.
8. Air Purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely. pressure in the system rises operating current rises cooling (or heating) efficiency drops moisture in the air may freeze and block capillary tubing water may lead to corrosion of parts in the refrigerant system Air Purging with a Vacuum Pump (for Test Run)
Page 25
(12) Test run the air conditioner. (See next page.) (13) While the air conditioner is running, apply liquid soap to check for any gas leaks around the service valves or caps.
ON / OFF operation button on the remote control unit. (3) The air conditioner will start running 3 minutes after the ON / OFF operation button is pressed. (4) Let the unit run for about 30 minutes and check that it operates normally.
The basic function of the service valves are given in Table 7 below. Narrow Tube Service Action Valve (2-Way) Shipping Operating and test running the air conditioner Measuring pressure and gas charging Air purging with a vacuum pump The service port on the wide tube service valve uses a Schrader core valve to access the refrigerant system.