hit counter script
ABB Relion 670 series Operation Manual
Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

®
Relion
670 series
670 series
Version 2.2 IEC
Operation manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 670 series

  • Page 1 ® Relion 670 series 670 series Version 2.2 IEC Operation manual...
  • Page 3 Document ID: 1MRK 500 127-UEN Issued: November 2018 Revision: D Product version: 2.2 © Copyright 2017 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license.
  • Page 5 This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
  • Page 6 (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The...
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction......................5 This manual............................5 Intended audience..........................5 Product documentation........................6 1.3.1 Product documentation set......................6 1.3.2 Document revision history......................7 1.3.3 Related documents........................7 Document symbols and conventions.....................9 1.4.1 Symbols............................9 1.4.2 Document conventions......................10 Section 2 Safety information....................11 Symbols on the product........................
  • Page 8 Table of contents 5.1.6 Identifying the device......................... 35 5.1.7 Adjusting the display contrast....................35 5.1.8 Changing the local HMI language.....................36 5.1.9 Navigating in the menu......................36 5.1.9.1 Menu structure......................... 36 5.1.9.2 Scrolling the display.........................36 5.1.9.3 Changing the default view......................37 5.1.10 Using function buttons......................37 5.1.11 Using the single-line diagram....................
  • Page 9 Table of contents 7.1.5 Through fault monitoring report....................57 7.1.5.1 Through fault monitoring tool....................57 7.1.5.2 Through fault monitoring using local HMI................62 Controlling............................63 7.2.1 Controlling circuit breakers and disconnectors..............63 Resetting the IED..........................64 7.3.1 Clearing and acknowledging via the local HMI..............64 Changing the IED functionality.....................
  • Page 11: Introduction

    1MRK 500 127-UEN D Section 1 Introduction Section 1 Introduction This manual GUID-AB423A30-13C2-46AF-B7FE-A73BB425EB5F v19 The operation manual contains instructions on how to operate the IED once it has been commissioned. The manual provides instructions for the monitoring, controlling and setting of the IED.
  • Page 12: Product Documentation

    Section 1 1MRK 500 127-UEN D Introduction Product documentation 1.3.1 Product documentation set GUID-3AA69EA6-F1D8-47C6-A8E6-562F29C67172 v16 Engineering manual Installation manual Commissioning manual Operation manual Application manual Technical manual Communication protocol manual Cyber security deployment guideline IEC07000220-4-en.vsd IEC07000220 V4 EN-US Figure 1: The intended use of manuals throughout the product lifecycle The engineering manual contains instructions on how to engineer the IEDs using the various tools available within the PCM600 software.
  • Page 13: Document Revision History

    1MRK 500 127-UEN D Section 1 Introduction The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also provide assistance for calculating settings. The technical manual contains operation principle descriptions, and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data, sorted per function.
  • Page 14 Section 1 1MRK 500 127-UEN D Introduction Documents related to RED670 Document numbers Application manual 1MRK 505 376-UEN Commissioning manual 1MRK 505 378-UEN Product guide 1MRK 505 379-BEN Technical manual 1MRK 505 377-UEN Type test certificate 1MRK 505 379-TEN Documents related to REG670 Document numbers Application manual 1MRK 502 071-UEN...
  • Page 15: Document Symbols And Conventions

    1MRK 500 127-UEN D Section 1 Introduction 670 series manuals Document numbers Operation manual 1MRK 500 127-UEN Engineering manual 1MRK 511 398-UEN Installation manual 1MRK 514 026-UEN Communication protocol manual, DNP3 1MRK 511 391-UUS Communication protocol manual, IEC 60870-5-103 1MRK 511 394-UEN Communication protocol manual, IEC 61850 Edition 1 1MRK 511 392-UEN Communication protocol manual, IEC 61850 Edition 2...
  • Page 16: Document Conventions

    Section 1 1MRK 500 127-UEN D Introduction The information icon alerts the reader of important facts and conditions. The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death.
  • Page 17: Safety Information

    1MRK 500 127-UEN D Section 2 Safety information Section 2 Safety information Symbols on the product GUID-E48F2EC3-6AB8-4ECF-A77E-F16CE45CA5FD v4 All warnings must be observed. Read the entire manual before doing installation or any maintenance work on the product. Class 1 Laser product. Take adequate measures to protect your eyes and do not view directly with optical instruments.
  • Page 18: Caution Signs

    Section 2 1MRK 500 127-UEN D Safety information M2370-2 v1 Never connect or disconnect a wire and/or a connector to or from a IED during normal operation. Hazardous voltages and currents are present that may be lethal. Operation may be disrupted and IED and measuring circuitry may be damaged.
  • Page 19 1MRK 500 127-UEN D Section 2 Safety information M2695-2 v2 Always transport PCBs (modules) using certified conductive bags. M2696-2 v1 Do not connect live wires to the IED. Internal circuitry may be damaged M2697-2 v2 Always use a conductive wrist strap connected to protective earth when replacing modules.
  • Page 21: Environmental Aspects

    1MRK 500 127-UEN D Section 3 Environmental aspects Section 3 Environmental aspects Sustainable development GUID-573C2931-CBB2-4E7D-A067-D8246CC7A52F v7 Sustainability has been taken into account from the beginning of the product design including the pro-environmental manufacturing process, long life time, operation reliability and disposing of the IED.
  • Page 23: Overview

    1MRK 500 127-UEN D Section 4 Overview Section 4 Overview GUID-0AFD09C7-371E-4895-8125-38DD18A7A0F2 v7 Local HMI AMU0600442 v15 IEC13000239-3-en.vsd IEC13000239 V3 EN-US Figure 2: Local human-machine interface The LHMI of the IED contains the following elements • Keypad • Display (LCD) • LED indicators •...
  • Page 24: Display

    Section 4 1MRK 500 127-UEN D Overview 4.1.1 Display GUID-55739D4F-1DA5-4112-B5C7-217AAF360EA5 v13 The LHMI includes a graphical monochrome liquid crystal display (LCD) with a resolution of 320 x 240 pixels. The character size can vary. The amount of characters and rows fitting the view depends on the character size and the view that is shown.
  • Page 25 1MRK 500 127-UEN D Section 4 Overview IEC15000138-1-en.vsdx IEC15000138 V1 EN-US Figure 4: Truncated path The number after : (colon sign) at the end of the function instance, for example, 1 in SMAI1:1, indicates the number of that function instance. The display is updated either cyclically or based on changes in the source data such as parameters or events.
  • Page 26: Leds

    Section 4 1MRK 500 127-UEN D Overview The indication LED panel shows on request the alarm text labels for the indication LEDs. Three indication LED pages are available. IEC13000240-1-en.vsd GUID-5157100F-E8C0-4FAB-B979-FD4A971475E3 V1 EN-US Figure 6: Indication LED panel The function button and indication LED panels are not visible at the same time. Each panel is shown by pressing one of the function buttons or the Multipage button.
  • Page 27: Keypad

    1MRK 500 127-UEN D Section 4 Overview IEC16000076-1-en.vsd IEC16000076 V1 EN-US Figure 7: OPENCLOSE_LED connected to SXCBR 4.1.3 Keypad AMU0600428 v19 The LHMI keypad contains push-buttons which are used to navigate in different views or menus. The push-buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode.
  • Page 28 Section 4 1MRK 500 127-UEN D Overview IEC15000157-2-en.vsd IEC15000157 V2 EN-US Figure 8: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port 1...5 Function button Close Open Escape Left Down Right Enter Remote/Local Uplink LED Not in use Multipage Menu Clear...
  • Page 29 1MRK 500 127-UEN D Section 4 Overview Communication port Programmable indication LEDs IED status LEDs Object control If the control position of the IED is set to local with the R/L button, the controlled objects can be opened and closed using the object control buttons. Object to be controlled is selected from the single line diagram.
  • Page 30: Local Hmi Functionality

    Section 4 1MRK 500 127-UEN D Overview Commands Table 4: Command push-buttons Name Description • Moving directly to Main menu, if currently Menu in any other menu or view. • Moving to the default view, if currently in Main menu. Changing the control position (remote or local) of the device.
  • Page 31: Parameter Management

    1MRK 500 127-UEN D Section 4 Overview Table 7: Start LED (yellow) LED state Description Normal operation. A protection function has started and an indication message is displayed. The start indication is latching and must be reset via communication, LHMI or binary input on the LEDGEN component.
  • Page 32: Front Communication

    Section 4 1MRK 500 127-UEN D Overview • Numerical values • String values • Enumerated values Numerical values are presented either in integer or in decimal format with minimum and maximum values. Character strings can be edited character by character. Enumerated values have a predefined set of selectable values.
  • Page 33: Authorization

    1MRK 500 127-UEN D Section 4 Overview IEC13000244-1-en.vsd GUID-40BD0177-1CB8-48D6-B149-D25BD109C78F V1 EN-US Figure 10: Example of a single-line diagram Authorization GUID-981A881D-9229-45E8-9EE5-D6DF2CA457E5 v5 User roles with different user rights are predefined in the IED. It is recommended to use user defined users instead of the predefined built-in users. The IED users can be created, deleted and edited only with PCM600.
  • Page 34 Section 4 1MRK 500 127-UEN D Overview User roles Role explanation User rights SECAUD Security auditor Can view audit logs RBACMNT RBAC Can change role assignment management ADMINISTRATOR Administrator Sum of all rights for SECADM, SECAUD and RBACMNT rights This User role is vendor specific and not defined in IEC 62351–8 Changes in user management settings do not cause an IED reboot.
  • Page 35: Communication

    1MRK 500 127-UEN D Section 4 Overview For user management, see Cyber security deployment guideline. Only characters A - Z, a - z and 0 - 9 shall be used in user names. User names are not case sensitive. For passwords see the Password policies in PCM600. GUID-75BBAD63-2CA0-4169-97C8-2EC31C945FF4 v1 See the Cyber security guideline for information on cyber security.
  • Page 36: Pcm600 Tool

    Section 4 1MRK 500 127-UEN D Overview PCM600 tool AMU0600443 v13 Protection and Control IED Manager PCM600 offers all the necessary functionality to work throughout all stages of the IED life cycle. • Planning • Engineering • Commissioning • Operation and disturbance handling •...
  • Page 37: Using The Hmi

    1MRK 500 127-UEN D Section 5 Using the HMI Section 5 Using the HMI Using the local HMI GUID-235278D0-97C9-4F0F-A521-C7DFA8600C4E v7 At delivery, logging on is not required and the user has full access until users and passwords are created with PCM600 and written into the IED or Centralized Account Management is enabled.
  • Page 38: Logging On

    Section 5 1MRK 500 127-UEN D Using the HMI IEC15000064.vsdx IEC15000064 V1 EN-US 5.1.2 Logging on GUID-E0F937A9-78EC-4528-AB34-FD6EC79A7815 v5 Press to activate the login procedure. The login is also activated when attempting a password-protected operation. Press to activate the User field. If CAM is activated an on-screen keyboard is shown.
  • Page 39 1MRK 500 127-UEN D Section 5 Using the HMI IEC12000157-3-en.vsd IEC12000157 V3 EN-US Figure 14: Entering the password Passwords are case sensitive. Only characters A - Z, a - z and 0 - 9 shall be used in user names. User names are not case sensitive.
  • Page 40: Logging Off

    Section 5 1MRK 500 127-UEN D Using the HMI 5.1.3 Logging off GUID-0FDDB51B-D1C2-4442-AAE5-865BC39AE253 v1 The user is automatically logged off after the display timeout. The IED returns to a state where only reading is enabled. Manual logoff is also possible. Press To confirm logoff, select Yes and press IEC12000159-3-en.vsd...
  • Page 41: Identifying The Device

    1MRK 500 127-UEN D Section 5 Using the HMI To control the IED, log in with the appropriate user rights. 5.1.6 Identifying the device AMU0600422 v9 The IED information includes detailed information about the device, such as revision and serial number.
  • Page 42: Changing The Local Hmi Language

    Section 5 1MRK 500 127-UEN D Using the HMI 5.1.8 Changing the local HMI language GUID-3DF3CD65-3EC2-41AF-B538-5CDA0C34E804 v9 Select Main menu/Language/LANGUAGE:1 and press Change the language using Press to confirm the selection. Commit the changes. 5.1.9 Navigating in the menu AMU0600412 v7 Navigate the menus and change the display views on the screen with the keypad.
  • Page 43: Changing The Default View

    1MRK 500 127-UEN D Section 5 Using the HMI IEC13000292-1-en.vsd GUID-8E3AA7B8-283F-4C0F-85F8-3DBA8FD366EA V1 EN-US Figure 21: Scroll bar on the right • To scroll the view upwards, press • To scroll the view downwards, press • To jump from the last row to the first row, press again.
  • Page 44: Using The Single-Line Diagram

    Section 5 1MRK 500 127-UEN D Using the HMI IEC13000281-1-en.vsd GUID-C98D972D-D1D8-4734-B419-161DBC0DC97B V1 EN-US Figure 22: Function button panel Press the wanted function button. • Press the wanted function button to jump to a certain menu item. The menu opens immediately upon pressing the button. •...
  • Page 45: Browsing Setting Values

    1MRK 500 127-UEN D Section 5 Using the HMI IEC13000244-1-en.vsd GUID-40BD0177-1CB8-48D6-B149-D25BD109C78F V1 EN-US Figure 23: Example of a single-line diagram Select an object with Selection of an object is indicated with a square border that moves when used. Switch objects can have additional icons that present the switch object states. •...
  • Page 46: Editing Values

    Section 5 1MRK 500 127-UEN D Using the HMI IEC13000054-2-en.vsd IEC13000054 V2 EN-US Figure 25: Selecting a setting group To browse the settings, scroll the list with and to select a setting press To move back to the list, press IEC13000265-1-en.vsd GUID-EFC7C47F-39D4-4C89-9672-55F338D63F4F V1 EN-US Figure 26: Selecting settings...
  • Page 47 1MRK 500 127-UEN D Section 5 Using the HMI IEC13000285-1-en.vsd GUID-8A573707-899E-4F4C-B20A-931D1556F480 V1 EN-US Figure 27: Last digit is active and it can be increased or decreased Press to increase or to decrease the value of an active digit. One press increases or decreases the value by a certain step. For integer values, the change is 1, 10, 100 or 1000 (...) depending on the active digit.
  • Page 48: Editing String Values

    Section 5 1MRK 500 127-UEN D Using the HMI IEC13000284-1-en.vsd GUID-4F2950E6-5F1F-4B7A-A191-43539B800FAE V1 EN-US Figure 28: Restoring the previous value 5.1.13.2 Editing string values AMU0600416 v9 Unicode characters that are not found on the on-screen keyboard can be used if the string is edited in PCM600. This string can be shown and edited on the HMI but if a character that is not found on the on-screen keyboard is deleted it cannot be retrieved using the HMI.
  • Page 49: Editing Enumerated Values

    1MRK 500 127-UEN D Section 5 Using the HMI IEC15000063.vsdx IEC15000063 V1 EN-US Edit the string using the on-screen keyboard. Select OK on the on-screen keyboard or press while the string editing field is focused to accept the entered string is accepted and the editing dialog is closed. 5.1.13.3 Editing enumerated values AMU0600417 v6...
  • Page 50: Clearing And Acknowledging

    Section 5 1MRK 500 127-UEN D Using the HMI Pressing Cancel in the Save changes dialog closes only the Save changes dialog box, but the IED remains in editing mode. All the changes applied to any setting are not lost and the user can continue to change settings. To leave the change setting mode, select No or Yes in the Save changes dialog.
  • Page 51 1MRK 500 127-UEN D Section 5 Using the HMI IEC13000065-2-en.vsd IEC13000065 V2 EN-US Figure 31: Help menu 670 series Operation manual...
  • Page 53: Ied Operation

    1MRK 500 127-UEN D Section 6 IED operation Section 6 IED operation Normal operation GUID-25794CEB-1F3A-452E-92B4-DDAD6F058CAF v6 In a normal IED use situation, the basic operation includes monitoring and checking procedures. • Monitoring measured values • Checking object states • Checking function setting parameters •...
  • Page 54: Disturbance Recording Triggering

    Section 6 1MRK 500 127-UEN D IED operation 6.2.1 Disturbance recording triggering GUID-5569488B-F930-4762-99CE-2863BEFB1947 v8 Disturbance recordings are normally triggered by IED applications when they detect fault events. Disturbance recordings can also be triggered manually or periodically. The manual trigger generates an instant disturbance report. Use this function to get a snapshot of the monitored signals.
  • Page 55: Ied Parameterization

    1MRK 500 127-UEN D Section 6 IED operation Non-operative functions, functions that are blocked due to bad or lost data from MU and functions set to a non-operative state by IEC 61850 are listed on the LHMI under Main menu/ Test/Function overview.
  • Page 57: Operating Procedures

    1MRK 500 127-UEN D Section 7 Operating procedures Section 7 Operating procedures Monitoring 7.1.1 Indications GUID-E3CC6AB4-D6C4-4504-A0F2-CA76EA3D7FCD v10 The operation of the IED can be monitored via three different indications on the LHMI. • Three indicator LEDs with fixed functionality: Ready, Start and Trip •...
  • Page 58: Monitoring Alarm Data

    Section 7 1MRK 500 127-UEN D Operating procedures IEC13000237-1-en.vsd GUID-42E5B0A0-789D-4B6F-9615-5B14AD8C1653 V1 EN-US Figure 32: Auto-indication message 7.1.1.2 Monitoring alarm data GUID-CC3B2CC2-FCE1-4256-A83E-D27AF735C9C2 v4 Active alarms are indicated by the alarm LEDs and the LED in the Multipage button. The alarms are configured with PCM600. The alarm type and information depend on the application configuration.
  • Page 59: Monitoring An Internal Ied Fault

    1MRK 500 127-UEN D Section 7 Operating procedures 7.1.1.3 Monitoring an internal IED fault GUID-67B6F8FD-3E2B-4EA6-8822-539F7FA3678B v4 The flashing green LED indicates an internal IED fault. The fault messages are found in the LHMI menu. Select Main menu/Diagnostics/Internal events or IED status to monitor the latest fault indication.
  • Page 60: Recorded Data

    Section 7 1MRK 500 127-UEN D Operating procedures 7.1.3 Recorded data GUID-1E9CFEC1-6245-4612-B637-821951B95D60 v7 The IED is provided with intelligent and flexible functionality that collects different kinds of data. The recorded data gives substantial information for post fault analysis. • Disturbance records •...
  • Page 61: Controlling And Reading Disturbance Recorder Data

    1MRK 500 127-UEN D Section 7 Operating procedures IEC13000262-1-en.vsd GUID-ACB5A57F-394B-475B-96C0-7C515A530D1F V1 EN-US Figure 36: Monitoring disturbance recorder via the LHMI To view a specific disturbance record, press A list of detail categories is displayed. IEC13000263-1-en.vsd GUID-D6F5E45F-12FE-40E7-9C3F-8CA82DB8498C V1 EN-US Figure 37: Disturbance record data categories To select a category and view the items under it, press and then 7.1.3.3...
  • Page 62: Monitoring Events

    Section 7 1MRK 500 127-UEN D Operating procedures 7.1.3.4 Monitoring events GUID-257DAC08-C4E7-4BB2-9654-630C3AAF29FC v4 The event view contains a list of events produced by the application configuration. The events are grouped by day, and each event takes one line. Select the order of events with the setting Main menu/Configuration/HMI/Screen/SCREEN:1/EvListSrtOrder.
  • Page 63: Through Fault Monitoring Report

    1MRK 500 127-UEN D Section 7 Operating procedures 7.1.5 Through fault monitoring report GUID-7B1BBAA3-7E5C-4F4E-BD90-B5D8A47036CE v1 Through fault reports can be viewed via the user interface using either the PCM tool or the local HMI. Additionally, the IED generates through fault reports those can be exported using multiple ways.
  • Page 64 Section 7 1MRK 500 127-UEN D Operating procedures IEC18000080-1-en.vsdx IEC18000080 V1 EN-US Figure 40: Through fault monitoring tool Through fault reports table GUID-E64AF177-D3FA-434A-86D2-589C0607D6D7 v1 The through fault reports table is an overview of fault reports. It displays the available fault reports from the IED.
  • Page 65 1MRK 500 127-UEN D Section 7 Operating procedures Selected through fault report data table GUID-BDABA774-DE1A-4F47-A2B6-986641B903CC v1 The report data table shows a detailed view of the selected through fault report. Based on the PTRSTHR function configuration, the windings columns are displayed. If the function is configured with two windings, Winding 1 and Winding 2 columns are displayed in the report data table.
  • Page 66 Section 7 1MRK 500 127-UEN D Operating procedures IEC18000085-1-en.vsdx IEC18000085 V1 EN-US Figure 43: Read through fault confirmation window In order to open the TFM tool successfully in PCM600, the configuration between the PCM600 tool and the IED should match. If the configuration is not same between the PCM600 tool and the IED, then read configuration from IED via Read from IED option in PCM600 need to be performed.
  • Page 67 1MRK 500 127-UEN D Section 7 Operating procedures IEC18000088-1-en.vsdx IEC18000088 V1 EN-US Figure 46: Confirm clear through fault reports Click on the Yes button to confirm the deletion. The through fault reports are deleted from the IED, and a confirmation dialog box appears.
  • Page 68: Through Fault Monitoring Using Local Hmi

    Section 7 1MRK 500 127-UEN D Operating procedures The through fault reports are exported into PCMDataBases folder as shown in Figure IEC18000091-1-en.vsdx IEC18000091 V1 EN-US Figure 49: PCMDataBases folder 7.1.5.2 Through fault monitoring using local HMI GUID-389023C4-33B6-4CBC-AB9D-9B07127F84C0 v1 The list of saved through fault reports those are grouped based on the instance can be found on the local HMI under Main menu/Measurements/Through fault reports.
  • Page 69: Controlling

    1MRK 500 127-UEN D Section 7 Operating procedures An instance specific clear option is provided to delete all the through fault reports from local HMI. Through fault monitoring report handling GUID-049E8C44-B981-4731-9882-0402AC57C17D v1 The through fault monitoring creates fault report for each through fault event. The through fault information is stored in a zipped .xml file in the IED under flash/frep folder.
  • Page 70: Resetting The Ied

    Section 7 1MRK 500 127-UEN D Operating procedures Selection of object is indicated with a square border that moves when used. Switch objects can have additional icons that present the switch object states. Switch object is in substituted state. Switch object is interlocked. Press to select open or to select close the object.
  • Page 71: Changing The Ied Functionality

    1MRK 500 127-UEN D Section 7 Operating procedures IEC13000236-1-en.vsd GUID-0CFAED62-312B-449F-BB58-D49496EA1CC8 V2 EN-US Figure 52: Clear view The content of the Clear menu depends on the configuration configured with PCM600. Select the item to be cleared with Press , select OK to confirm the selection or Cancel to cancel the selection. To clear other items, repeat the steps.
  • Page 72: Browsing And Editing Setting Group Values

    Section 7 1MRK 500 127-UEN D Operating procedures IEC13000235-1-en.vsd GUID-9BC3D595-CF08-42AF-B74E-0D3970A552DB V1 EN-US Figure 53: Active setting group Select the setting group with Press to confirm the selection or to cancel. Commit the settings. Remember to document the changes you make. 7.4.1.2 Browsing and editing setting group values GUID-5624E7E4-1D14-469A-BF86-8BD560B72F9D v5...
  • Page 73 1MRK 500 127-UEN D Section 7 Operating procedures IEC13000265-1-en.vsd GUID-EFC7C47F-39D4-4C89-9672-55F338D63F4F V1 EN-US Figure 56: Selecting the function category To browse the function blocks, scroll the list with Function blocks available depend on the application configuration. To move back to the list, press To select a function block, press IEC13000055-2-en.vsd...
  • Page 74: Activating Leds

    Section 7 1MRK 500 127-UEN D Operating procedures IEC13000049-2-en.vsd IEC13000049 V2 EN-US Figure 58: Changing the setting value Press to change the value. Confirm the change with 7.4.2 Activating LEDs GUID-C63971C7-EDC8-40BA-B53B-7377AA33FCC5 v6 To activate the LEDs, they must be configured with PCM600. Select Main menu/Configuration/HMI/LEDs and press IEC13000056-2-en.vsd IEC13000056 V2 EN-US...
  • Page 75 1MRK 500 127-UEN D Section 7 Operating procedures For more information, see PCM600 documentation. 670 series Operation manual...
  • Page 77: Rex060 Injection Unit Lhmi

    REX060 start up sequence GUID-63A15CD3-17B0-41DD-9611-8272DDA53137 v1 When the injection unit REX060 is energized, the ABB logotype is shown followed by current REX060 revision status. When the start up sequence is completed, the main menu (normal display content) is shown. The duration of the start up sequence is a few seconds.
  • Page 78: Rex060 Front Panel Controls

    Section 8 1MRK 500 127-UEN D REX060 injection unit LHMI 8.1.3 REX060 Front panel controls GUID-31FB2725-4394-4B7A-89F1-5C4FE61A30EB v2 IEC11000053-1-en.vsd IEC11000053 V1 EN-US Figure 60: REX060 front panel 670 series Operation manual...
  • Page 79: Display

    1MRK 500 127-UEN D Section 8 REX060 injection unit LHMI Table 15: HMI keys on the front of the injection unit REX060 Function The Injection switch enables injection at rotor and stator 2 s after switching on. A LED indicates that the injection switch is set to enable injection.
  • Page 80: How To Set Frequency And Voltage And Current Gain Factors

    Section 8 1MRK 500 127-UEN D REX060 injection unit LHMI Column System [Hz] : STATOR [Hz] : UmaxEF [V] : ROTOR [Hz] : Gain IEC10000334-1-en.vsd IEC10000334 V1 EN-US Figure 61: Display content in normal operation Column 1 (status column) symbols Table 16: Status symbols and their description Status symbol...
  • Page 81: Setting System Frequency

    1MRK 500 127-UEN D Section 8 REX060 injection unit LHMI The settings are stored in non-volatile memory, which means that they remain stored in case IED is powered off. 8.1.5.1 Setting system frequency GUID-D5CB4B02-F5EC-4680-8368-E9BDBAA28BD3 v1 Frequency can be set to either 50 or 60 Hz. Use the Up and Down button to select frequency.
  • Page 82: Resetting Overvoltage

    Section 8 1MRK 500 127-UEN D REX060 injection unit LHMI Table 18: Stator gain UmaxEF [V] Note Default value up to 120 8.1.5.5 Resetting overvoltage GUID-656B534F-3F83-4B35-8020-F9875FF82DED v1 Stator and rotor injection output is protected against voltages exceeding maximum operating range (10% of rated VT/DT) by a relay blocking the injection circuit. This blocking is controlled by measuring the stator and/or rotor voltage, and remains blocked until manually reset.
  • Page 83: Troubleshooting

    Inspect the IED visually. • Inspect the IED visually to find any physical error causes. • If you can find some obvious physical damage, contact ABB for repair or replacement actions. Check whether the error is external or internal. •...
  • Page 84: Checking The Communication Link Operation

    Section 9 1MRK 500 127-UEN D Troubleshooting 9.1.4.1 Checking the communication link operation GUID-A1815C16-1AB7-4DEE-8E9B-0BF91DDEE72C v9 There are several different communication links on the product. First check that all communication ports that are used for communication are turned on. Check the front communication port RJ-45. 1.1.
  • Page 85 1MRK 500 127-UEN D Section 9 Troubleshooting be blocked. This condition will be indicated with a sub-menu under Hints, where details about this condition are shown. The Hint menu is a way to assist the user in troubleshooting. The Hint menu is currently only available in English. All the entries are in English, regardless of which language is selected.
  • Page 86: Indication Messages

    Corresponding hardware(s) is set to fail. Please restart IED and consider Reconfigure HW modules to get updated hardware list. Non ABB vendor SFP detected Non ABB vendor SFP detected. Corresponding hardware(s) is set to fail. Please use ABB approved SFP’s.
  • Page 87: Warnings

    1MRK 500 127-UEN D Section 9 Troubleshooting Fault indication Additional information Internal Fail One or more of the application threads are not in an expected Runtime App Error state. Internal Fail IEC 61850 has not succeeded in some actions such as reading IEC 61850 Error the configuration file or start-up.
  • Page 88: Correction Procedures

    Section 9 1MRK 500 127-UEN D Troubleshooting Table 22: Additional indications Warning indication Additional information Time Synch Error Source of the time synchronization is lost or time system has made a time reset. Settings Changed Settings have been changed. Setting Groups Changed Setting group has been changed.
  • Page 89: Inspecting The Wiring

    1MRK 500 127-UEN D Section 9 Troubleshooting 9.3.2.1 Inspecting the wiring GUID-665B75A6-A074-4A03-ADF1-3D0FAD198E61 v8 The physical inspection of wiring connections often reveals the wrong connection for phase currents or voltages. However, even though the phase current or voltage connections to IED terminals might be correct, wrong polarity of one or more measurement transformers can cause problems.
  • Page 90 Section 9 1MRK 500 127-UEN D Troubleshooting GUID-BBAEAF55-8D01-4711-A71D-BBC76B60BA3D V1 EN-US Figure 62: Testing output contacts using the voltage drop method Contact current 2 Contact voltage drop 3 Load 4 Supply voltage • To check the status of the output circuits driving the output relay via the LHMI, select Main menu/Test/Binary output values and then navigate to the board with the actual binary output to be checked.
  • Page 91: Section 10 Glossary

    1MRK 500 127-UEN D Section 10 Glossary Section 10 Glossary M14893-1 v18 Alternating current Actual channel Application configuration tool within PCM600 A/D converter Analog-to-digital converter ADBS Amplitude deadband supervision Analog digital conversion module, with time synchronization Analog input ANSI American National Standards Institute Autoreclosing ASCT Auxiliary summation current transformer...
  • Page 92 Section 10 1MRK 500 127-UEN D Glossary CO cycle Close-open cycle Codirectional Way of transmitting G.703 over a balanced line. Involves two twisted pairs making it possible to transmit information in both directions Command COMTRADE Standard Common Format for Transient Data Exchange format for Disturbance recorder according to IEEE/ANSI C37.111, 1999 / IEC 60255-24 Contra-directional...
  • Page 93 1MRK 500 127-UEN D Section 10 Glossary Electromagnetic interference EnFP End fault protection Enhanced performance architecture Electrostatic discharge F-SMA Type of optical fiber connector Fault number Flow control bit; Frame count bit FOX 20 Modular 20 channel telecommunication system for speech, data and protection signals FOX 512/515 Access multiplexer...
  • Page 94 Section 10 1MRK 500 127-UEN D Glossary IEC 61850–8–1 Communication protocol standard IEEE Institute of Electrical and Electronics Engineers IEEE 802.12 A network technology standard that provides 100 Mbits/s on twisted- pair or optical fiber cable IEEE P1386.1 PCI Mezzanine Card (PMC) standard for local bus modules. References the CMC (IEEE P1386, also known as Common Mezzanine Card) standard for the mechanics and the PCI specifications from the PCI SIG (Special Interest Group) for the electrical EMF (Electromotive force).
  • Page 95 1MRK 500 127-UEN D Section 10 Glossary Multifunction vehicle bus. Standardized serial bus originally developed for use in trains. National Control Centre Number of grid faults Numerical module OCO cycle Open-close-open cycle Overcurrent protection Optical Ethernet module OLTC On-load tap changer OTEV Disturbance data recording initiated by other event than start/pick-up Overvoltage...
  • Page 96 Section 10 1MRK 500 127-UEN D Glossary Switch or push button to close Short circuit location Station control system SCADA Supervision, control and data acquisition System configuration tool according to standard IEC 61850 Service data unit SELV circuit Safety Extra-Low Voltage circuit type according to IEC60255-27 Small form-factor pluggable (abbreviation) Optical Ethernet port (explanation) Serial communication module.
  • Page 97 1MRK 500 127-UEN D Section 10 Glossary Transformer Module. This module transforms currents and voltages taken from the process into levels suitable for further signal processing. Type identification User management tool Underreach A term used to describe how the relay behaves during a fault condition. For example, a distance relay is underreaching when the impedance presented to it is greater than the apparent impedance to the fault applied to the balance point, that is, the set reach.
  • Page 100 ABB AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 Scan this QR code to visit our website www.abb.com/protection-control © Copyright 2017 ABB. All rights reserved.

This manual is also suitable for:

Relion sam600-ioRex060

Table of Contents