Page 1
SUN2000-(60KTL, 65KTL)-M0 User Manual (Mexico Edition) Issue Date 2020-10-12 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage safety standards.
Do not touch the energized equipment, as the enclosure is hot. 1.2 Personnel Requirements ● Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and be able to correctly perform all operations.
The DC power is then converted into three-phase AC power through an inverter circuit. Surge protection is supported on both the DC and AC sides. Figure 2-5 shows the conceptual diagram for the SUN2000-60KTL-M0. Figure 2-6 shows the conceptual diagram for the SUN2000-65KTL-M0.
The inverter will be corroded in salt areas. Before installing the inverter outdoors in salt areas, consult Huawei. A salt area refers to the region within 500 meters from the coast or prone to sea breeze. The regions prone to sea breeze vary with weather conditions (such as typhoons and monsoons) or terrains (such as dams and hills).
Page 51
SUN2000-(60KTL, 65KTL)-M0 User Manual (Mexico Edition) 5 Electrical Connections Figure 5-11 Connecting the AC output power cable for the SUN2000-60KTL-M0 (A) Three-core cable (excluding the ground (B) Four-core cable (including the ground cable cable and neutral wire) but excluding the neutral wire)
NO TE When the Grid code for the SUN2000-60KTL-M0 is set to Mexico-MV480, and the SUN2000-60KTL-M0 is used for power generation in 440 V AC grid connection, you need to adjust the level-1 and level-2 undervoltage protection threshold to 384 V.
Page 115
Output mode to Three-phase, three-wire. When it is used in the scenarios with neutral wires, set Output mode to Three-phase, four-wire. Note c: When the Grid code for the SUN2000-60KTL-M0 is set to Mexico- MV480, and the SUN2000-60KTL-M0 is used for power generation in 440 V AC grid connection, you need to adjust the level-1 and level-2 undervoltage protection threshold to 384 V.
User Manual (Mexico Edition) A Grid Codes Grid Codes NO TE The grid codes are subject to change. The listed codes are for reference only. Table A-1 Grid codes (for the SUN2000-60KTL-M0) Grid Code Description VDE-AR-N-4105 Germany low-voltage power grid...