ABB Relion 670 Series Product Manual

ABB Relion 670 Series Product Manual

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:

Advertisement

Quick Links

®
Relion
670 SERIES
Phasor measurement unit RES670
Version 2.2
Product guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 670 Series

  • Page 1 ® Relion 670 SERIES Phasor measurement unit RES670 Version 2.2 Product guide...
  • Page 2: Table Of Contents

    The information in this document is subject to change without notice and should not be construed as a commitment by Hitachi Power Grids. Hitachi Power Grids assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding. ABB is a registered trademark of ABB Asea Brown Boveri Ltd.
  • Page 3: Document Revision History

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Issued: September 2020 Revision: L 1. Document revision history GUID-34B323E4-1319-4D42-80CE-29B0F2D36E2C v4 Table 1. Document revision history Document Date Product revision History revision 2017-07 2.2.0 First release for product version 2.2 2017-10 2.2.1 Ethernet ports with RJ45 connector added.
  • Page 4: Application

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 • PMU Phasor Measurement Unit, including all accessories for time synchronization 2. Application • TCP/IP and/or UDP/IP communication network infra- GUID-CF75762E-73C1-40AF-8D6F-6EC3D8395982 v4 RES670 is a Phasor Measurement Unit (PMU) that structure provides power system AC voltages and currents as •...
  • Page 5 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 binary inputs and outputs on the IED I/O modules (BOM, binary reporting channels can be extended to maximum BIM, IOM & SOM) can be forced to arbitrary values. 24 channels per PMU instance (on each data stream) on request.
  • Page 6 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 RES670 A20 – Phasor Measurement Unit, 3 bays, single busbar, 12AI (9I+3U) WA1_VT df/dt SA PFRC f> SA PTOF f< SA PTUF 2(3U<) UV2 PTUV 2(3U>) OV2 PTOV V MMXU Usqi DFR/SER DR V MSQI...
  • Page 7 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 can be done when ordering the RES670 B20 configuration also includes general back-up protection configuration. functions which are mainly intended for alarm purposes. Available protection functions in standard B20 In addition, each data stream includes 16 analog and 16 configuration are Over Voltage, Under Voltage, Over binary reporting channels over IEEE C37.118/1344 in the Frequency, Under Frequency and Rate of Change of...
  • Page 8 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 RES670 B20 – Phasor Measurement Unit, 6 bays, double busbar, 24AI (9I+3U, 9I+3U) WA1_VT WA2_VT df/dt df/dt SA PFRC SA PFRC f> f> SA PTOF SA PTOF f< f< SA PTUF SA PTUF 2(3U<) 2(3U<)
  • Page 9: Available Functions

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 3. Available functions GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1 The following tables list all the functions available in the IED. Those functions that are not exposed to the user or do not need to be configured are not described in this manual.
  • Page 10 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v16 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) Impedance protection OOSPPAM Out-of-step protection 2-B36 2-B36 Current protection OC4PTOC Directional phase overcurrent protection, four steps 3-C26 6-C27 51_67...
  • Page 11 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v20 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) Control QCBAY Bay control LOCREM Handling of LR-switch positions LOCREMCTRL LHMI control of PSTO SXCBR Circuit breaker SLGAPC...
  • Page 12 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) SMPPTRC Tripping logic SMAGAPC General start matrix block STARTCOMB Start combinator TMAGAPC Trip matrix logic ALMCALH Logic for group alarm WRNCALH Logic for group warning INDCALH...
  • Page 13 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) TEIGAPC Elapsed time integrator with limit transgression and overflow supervision INTCOMP Comparator for integer inputs REALCOMP Comparator for real inputs Hitachi Power Grids ©...
  • Page 14 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) Monitoring CVMMXN Power system measurement CMMXU Current measurement VMMXU Voltage measurement phase-phase CMSQI Current sequence measurement VMSQI Voltage sequence measurement VNMMXU Voltage measurement phase-earth...
  • Page 15 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) I103USRDEF Status for user defined signals for IEC 60870-5-103 L4UFCNT Event counter with limit supervision TEILGAPC Running hour meter CHMMHAI ITHD Current harmonic monitoring, 3 phase...
  • Page 16 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 3. Total number of instances for configurable logic blocks Q/T Configurable logic blocks Q/T Total number of instances ANDQT INDCOMBSPQT INDEXTSPQT INVALIDQT INVERTERQT ORQT PULSETIMERQT RSMEMORYQT SRMEMORYQT TIMERSETQT XORQT Table 4.
  • Page 17 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v18 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON PROTOCOL Operation selection between SPA and IEC60870-5-103 for SLM RS485PROT...
  • Page 18 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) LPHD Physical device information PCMACCS IED configuration protocol SECALARM Component for mapping security events on protocols such as DNP3 and IEC103 FSTACCSNA Field service tool access via SPA protocol over Ethernet...
  • Page 19 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) BST2M_305 Binary signal transfer, 2Mbit transmit BST2M_312 BST2M_322 BST2M_306 BST2M_313 BST2M_323 LDCMTRN Transmission of analog data from LDCM LDCMTRN_2M_305 Transmission of analog data from LDCM, 2Mbit LDCMTRN_2M_306...
  • Page 20 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v14 Table 5. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list SELFSUPEVLST TIMESYNCHGEN Time synchronization module SYNCHCAN, Time synchronization SYNCHCMPPS, SYNCHPPS, SYNCHCMPPS,...
  • Page 21: Impedance Protection

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 5. Basic IED functions, continued IEC 61850 or function Description name ALTMS Time master supervision ALTIM Time management CAMCONFIG Central account management configuration CAMSTATUS Central account management status TOOLINF Tools information COMSTATUS Protocol diagnostic...
  • Page 22: Wide Area Measurement System

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 finds the center of oscillation in its zone 1 should data types for phasor data, analog data and frequency operate first. data. Two current channels I3P1 and I3P2 are available in Synchrophasor data can be reported to up to 8 clients OOSPPAM function to allow the direct connection of two over TCP and/or 6 UDP group clients for multicast or...
  • Page 23: Voltage Protection

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 A second harmonic blocking can be set individually for No specific sensitive current input is needed. Sensitive each step. directional residual overcurrent and power protection (SDEPSDE) can be set as low 0.25% of IBase. Directional operation can be combined together with Thermal overload protection, one time constant the corresponding communication logic in permissive or...
  • Page 24: Frequency Protection

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Two step overvoltage protection OV2PTOV Rate-of-change of frequency protection SAPFRC M13798-3 v17 M14965-3 v14 Overvoltages may occur in the power system during The rate-of-change of frequency protection function abnormal conditions such as sudden power loss, tap (SAPFRC) gives an early indication of a main disturbance changer regulating failures, and open line ends on long in the system.
  • Page 25: General Calculation

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 of the earth fault from the directional earth fault A criterion based on delta current and delta voltage protection function. measurements can be added to the fuse failure supervision function in order to detect a three phase fuse failure, which in practice is more associated with 10.
  • Page 26: Logic

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 QCBAY also provides blocking functions that can be Automation bits, command function for DNP3.0 distributed to different apparatuses within the bay. AUTOBITS SEMOD158591-5 v9 Local remote LOCREM/Local remote control Automation bits function for DNP3 (AUTOBITS) is used LOCREMCTRL within PCM600 to get into the configuration of the M17086-3 v11...
  • Page 27 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 before the power interruption. RESET input has Group alarm logic function ALMCALH priority. GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v4 The group alarm logic function (ALMCALH) is used to route several alarm signals to a common indication, LED •...
  • Page 28 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 • INVERTERQT function block that inverts the input Elapsed time integrator with limit transgression and signal and propagates the time stamp and the quality overflow supervision TEIGAPC of the input signal. GUID-2D64874A-F266-4251-8EED-E813F40513D7 v3 The Elapsed time integrator function (TEIGAPC) is a function that accumulates the elapsed time when a...
  • Page 29: Monitoring

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 A disturbance is defined as an activation of an input to the AnRADR or BnRBDR function blocks, which are set to 14. Monitoring trigger the disturbance recorder. All connected signals from start of pre-fault time to the end of post-fault time Measurements CVMMXN, CMMXU, VNMMXU, will be included in the recording.
  • Page 30 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 The event recording information is an integrated part of Generic communication function for Single Point the disturbance record (Comtrade file). indication SPGAPC SEMOD55713-5 v8 Trip value recorder DRPRDRE Generic communication function for Single Point M12128-3 v7 indication (SPGAPC) is used to send one single logical Information about the pre-fault and fault values for...
  • Page 31: Metering

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 breaker condition. The breaker requires maintenance The current harmonic function monitors the harmonic when the number of operations reaches a predefined distortion and demand distortion values constantly. value. For a proper functioning of the circuit breaker, it Whenever these value crosses their set limit levels, a is essential to monitor the circuit breaker operation, warning signal will be initiated.
  • Page 32: Human Machine Interface

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 signals for limit violation of energy values and maximum • Graphical display capable of showing a user defined power demand, can be found. single line diagram and provide an interface for controlling switchgear.
  • Page 33: Station Communication

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 redundant communication is activated for the access point. Device 1 Device 1 Default gateway SFP_301 SFP_302 SFP_303 SFP_301 SFP_302 SFP_303 Gateway IEC16000092-1-en.vsdx IEC16000092 V1 EN-US Figure 5. Access points, non redundant (left) and redundant Source Destination communication (right)
  • Page 34 GUID-9C5DC78E-041B-422B-9668-320E62B847A2 v1 SEMOD120134-5 v1 The quality expander component is used to display the A single glass or plastic port is provided for the ABB SPA detailed quality of an IEC/UCA 61850-9-2LE analog protocol. This allows extensions of simple substation channel. The component expands the channel quality...
  • Page 35: Remote Communication

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 The BLOCK input will block only the signals in Supervison status for IEC 60870-5-103 I103SUPERV monitoring direction (the position information), not the I103SUPERV is a function block with defined functions commands via IEC 60870-5-103.
  • Page 36: Hardware Description

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Optical Ethernet module M16073-3 v9 The optical Ethernet module (OEM) provides two 21. Hardware description additional optical Ethernet ports. The port connectors are of optical (type LC) or galvanic (type RJ45) Ethernet Hardware modules ports.
  • Page 37 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Layout and dimensions IP14539-1 v1 Dimensions IP14826-1 v1 M15243-4 v7 IEC08000165‐3‐en.vsdx IEC08000165 V3 EN-US Figure 8. Case with rear cover and 19” rack mounting kit IEC08000163‐3‐en.vsdx IEC08000163 V3 EN-US Figure 7. Case with rear cover Hitachi Power Grids ©...
  • Page 38 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 M15243-12 v11 IEC06000182-2-en.vsd IEC06000182 V2 EN-US Figure 9. A 1/2 x 19” size IED side-by-side with RHGS6. Table 7. Case dimensions Case size (mm)/ (inches) 6U, 1/2 x 19” 265.9/ 223.7/ 247.5/ 255.0/...
  • Page 39: Connection Diagrams

    1446-18 IEC 61850 Ed2 level A1 10175313-INC 20-2185rev1 certificate issued by DNV GL IEC 61850 Ed1 level B1 1KHL050130 certificate issued by ABB Power Grids Switzerland Ltd, System Verification and Validation Center, SVC Baden IEC 60870-5-103 certificate 10021419-OPE/INC 16-2490 issued by DNV GL DNP 3.0 certificate issued by...
  • Page 40: Technical Data

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 24. Technical data General M10993-1 v4 IP11376-1 v3 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to...
  • Page 41 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Energizing quantities, rated values and limits Analog inputs M16988-1 v11 IP15842-1 v1 Table 8. TRM - Energizing quantities, rated values and limits for protection transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ±...
  • Page 42 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 9. TRM - Energizing quantities, rated values and limits for measuring transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ± 10% Current inputs Rated current I Operating range (0-1.8) ×...
  • Page 43 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Binary inputs and outputs M12576-1 v13 IP15844-1 v1 Table 12. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20%...
  • Page 44 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 14. IOM - Binary input/output module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20% 220/250 V RL ±20% Power consumption 24/30 V, 50 mA...
  • Page 45 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 M12318-1 v11 Table 15. IOM - Binary input/output module contact data (reference standard: IEC 61810-1) Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Binary outputs Max system voltage 250 V AC/DC 250 V DC...
  • Page 46 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 M12584-1 v11 Table 16. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-1) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay) Binary outputs IOM: 10 IOM: 2...
  • Page 47 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 SEMOD175395-2 v11 Table 17. SOM - Static Output Module data (reference standard: IEC 61810-1): Heavy duty static binary outputs Function of quantity Static binary output trip Max system voltage 250 V DC Number of outputs Impedance open state High impedance...
  • Page 48 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 18. SOM - Static Output module data (reference standard: IEC 61810-1): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250 V AC/DC Min load voltage 24 V DC Number of outputs Test voltage across open contact, 1 min...
  • Page 49 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 M12441-1 v11 Table 19. BOM - Binary output module contact data (reference standard: IEC 61810-1) Function or quantity Trip and Signal relays Binary outputs Max system voltage 250 V AC/DC Min load voltage 24V DC Test voltage across open contact, 1 min...
  • Page 50 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 21. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/% Operative range Full wave rectified...
  • Page 51 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Type tests according to standards M16706-1 v15 IP15778-1 v1 Table 23. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Level 3 Ring wave immunity test, 100 kHz...
  • Page 52 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 25. Environmental conditions Description Value Operating temperature range -25°C to +55°C (continuous) Short-time service temperature range -40°C to +70°C (<16h) Note: Degradation in MTBF and HMI performance outside the temperature range of -25°C to +55°C Relative humidity <93%, non-condensing...
  • Page 53 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Impedance protection GUID-E65CE996-C0CE-4620-8E01-A96896E62802 v1 Table 29. Power swing detection, blocking and unblocking ZMBURPSB Function Range or value Accuracy Reactive reach (0.10-3000.00) W/phase ±2.0% static accuracy Conditions: Voltage range: (0.1-1.1) x U Current range: (0.5-30) x I Angle: at 0 degrees and 85 degrees Resistive reach...
  • Page 54 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Wide area measurement system GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v5 The IED is compliant with the synchrophasor measurement requirements of IEEE C37.118.1-2011, including the amendment (IEEE C37.118.1a-2014) for both P and M performance classes. The IED is also compliant with synchrophasor data transfer requirements of IEEE C37.118.2-2011.
  • Page 55 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Current protection M12342-1 v22 Table 31. Directional phase overcurrent protection, four steps OC4PTOC Function Range or value Accuracy lBase Operate current, step 1-4 (5-2500)% of ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 56 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 M15223-1 v18 Table 32. Directional residual overcurrent protection, four steps EF4PTOC Function Range or value Accuracy Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 57 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6 Table 33. Four step directional negative phase sequence overcurrent protection NS4PTOC Function Range or value Accuracy lBase Operate current, step 1 - 4 (1-2500)% of ±1.0% of I at I £...
  • Page 58 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 SEMOD173350-2 v16 Table 34. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of IBase Operate level for 3I ·cosj directional ±1.0% of I at I £ I residual overcurrent ±1.0% of I at I >...
  • Page 59 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 M12352-1 v15 Table 35. Thermal overload protection, one time constant LCPTTR/LFPTTR Function Range or value Accuracy Reference current (2-400)% of IBase ±1.0% of I Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F Operate time: IEC 60255-149, ±5.0% or ±200 ms whichever is greater...
  • Page 60 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 SEMOD175159-2 v9 Table 37. Directional overpower protection GOPPDOP Function Range or value Accuracy Power level (0.0–500.0)% of SBase ±1.0% of S at S ≤ S for Step 1 and Step 2 ±1.0% of S at S >...
  • Page 61 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Voltage protection M13290-1 v15 Table 38. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U UBase Absolute hysteresis (0.0–50.0)% of ±0.5% of U UBase...
  • Page 62 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 M13304-1 v15 Table 39. Two step overvoltage protection OV2PTOV Function Range or value Accuracy UBase Operate voltage, step 1 and 2 (1.0-200.0)% of ±0.5% of U at U ≤ U ±0.5% of U at U >...
  • Page 63 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Frequency protection M13360-1 v16 Table 40. Underfrequency protection SAPTUF Function Range or Value Accuracy Operate value, start function, at (35.00 - 75.00) Hz ±2.0 mHz symmetrical three phase voltage, StartFrequency Reset hysteresis 10.0 mHz fixed ±2.0 mHz...
  • Page 64 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 M14964-1 v13 Table 41. Underfrequency protection SAPTOF Function Range or Value Accuracy Operate value, start function, (35.00 - 90.00) Hz ±2.0 mHz at symmetrical three phase voltage, StartFrequency 10.0 mHz fixed ±2.0 mHz Reset hysteresis Start time measurement with...
  • Page 65 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-E8D0EE7C-D7B8-46C3-9C0D-363FFC75DE93 v5 Table 43. Frequency accumulation protection FTAQFVR Function Range or value Accuracy Operate value, frequency high limit level at (35.00 – 90.00) Hz ±2.0 mHz symmetrical three phase voltage Operatevalue, frequency low limit level at (30.00 –...
  • Page 66 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Multipurpose protection M13095-2 v11 Table 44. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1- phase2, phase2-phase3, phase3- phase1, MaxPh-Ph, MinPh-Ph, UnbalancePh-Ph...
  • Page 67 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 44. General current and voltage protection CVGAPC, continued Function Range or value Accuracy Start undervoltage, step 1 - 2 (2.0 - 150.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U >...
  • Page 68 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 44. General current and voltage protection CVGAPC, continued Function Range or value Accuracy Impulse margin time 15 ms typically Undervoltage: Critical impulse time 10 ms typically at 1.2 x U to 0.8 x Impulse margin time 15 ms typically...
  • Page 69 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Secondary system supervision M12358-1 v10 Table 45. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I > I Reset ratio, Operate current >90% Block current...
  • Page 70 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-ED3FE722-1F29-4340-94E9-6C907C4474F2 v3 Table 48. Current based delta supervision DELISPVC Function Range or value Accuracy Minimum current (5.0 - 50.0)% of IBase ±1.0% of Ir at I ≤ Ir±1.0% of I at I > Ir DelI>...
  • Page 71 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Logic M12380-1 v15 Table 49. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Program Trip action, 3 phase, 1ph/2ph, 1ph/2ph/3ph Minimum trip pulse (0.000-60.000) s ±0.2% or ±15 ms whichever is greater length , tTripMin tWaitForPHS...
  • Page 72 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v2 Table 55. Number of INDCALH instances Function Quantity with cycle time 3 ms 8 ms 100 ms INDCALH GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3 Table 56. Number of AND instances Logic block Quantity with cycle time 3 ms 8 ms...
  • Page 73 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-BE6FD540-E96E-4F15-B2A2-12FFAE6C51DB v2 Table 62. Number of RSMEMORY instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms RSMEMORY GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v2 Table 63. Number of SRMEMORY instances Logic block Quantity with cycle time 3 ms 8 ms...
  • Page 74 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-77FEBE9B-0882-4E85-8B1A-7671807BFC02 v2 Table 69. Number of INVALIDQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms INVALIDQT GUID-F25B94C6-9CC9-48A0-A7A3-47627D2B56E2 v1 Table 70. Number of INVERTERQT instances Logic block Quantity with cycle time 3 ms 8 ms...
  • Page 75 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-1C381E02-6B9E-44DC-828F-8B3EA7EDAA54 v1 Table 76. Number of XORQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms XORQT GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v8 Table 77. Number of instances in the extension logic package Logic block Quantity with cycle time 3 ms...
  • Page 76 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2 Table 81. Number of ITBGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms ITBGAPC GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4 Table 82. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC Function Cycle time (ms) Range or value...
  • Page 77 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Monitoring M12386-1 v16 Table 86. Power system measurement CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U ≤ 50 V ±0.2% of U at U >...
  • Page 78 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6 Table 89. Voltage measurement phase-earth VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V Phase angle (5 to 175) V ±0.5 degrees at U ≤...
  • Page 79 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 M12760-1 v12 Table 93. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 200, first in - first out Time tagging resolution 1 ms See table...
  • Page 80 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v9 Table 95. Insulation supervision for liquid medium function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater Oil lockout level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater Temperature alarm level...
  • Page 81 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 M12702-1 v5 Table 99. Event recorder Function Value Buffer capacity Maximum number of events in disturbance report Maximum number of disturbance reports Resolution 1 ms Accuracy Depending on time synchronizing M13747-1 v6 Table 100.
  • Page 82 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3 Relion® 670 series can store up to 10240 security events. Table 102. Event counter with limit supervision L4UFCNT Function Range or value Accuracy Counter value 0-65535 Hitachi Power Grids ©...
  • Page 83 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 102. Event counter with limit supervision L4UFCNT , continued Function Range or value Accuracy Max. count up speed 30 pulses/s (50% duty cycle) GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1 Table 103. Running hour-meter TEILGAPC Function Range or value Accuracy...
  • Page 84 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-2068BBA0-9026-48D0-9DEB-301BCB3C600C v2 Table 105. Voltage harmonic monitoring VHMMHAI (50/60 Hz) Function Range or value Accuracy Fundamental Harmonic Frequency (0.95 - 1.05) X f 2nd order to 5th order (0.1 - 0.5) X U ±...
  • Page 85 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Metering M13404-2 v5 Table 106. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of (1–3600) s counter value SEMOD153707-2 v5 Table 107.
  • Page 86 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Station communication M15031-1 v9 Table 108. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0 Communication speed for the IEDs...
  • Page 87 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 112. SFP - Galvanic RJ45 Quantity Rated value Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for communication using any protocol Standard IEEE 802.3u 100BASE-TX Type of cable...
  • Page 88 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Hardware M11778-1 v7 SEMOD53385-1 v1 Table 114. Case Material Steel sheet Front plate Stainless steel with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) M12327-1 v5 Table 115.
  • Page 89 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3 Because of limitations of space, when ring lug terminal is ordered for Binary I/O connections, one blank slot is necessary between two adjacent I/O modules. Please refer to the ordering particulars for details.
  • Page 90 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Basic IED functions M11963-1 v5 Table 122. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v9 Table 123. Time synchronization, time tagging Function Value Time tagging accuracy of the synchrophasor data...
  • Page 91 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 SEMOD141136-2 v10 Table 127. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 92 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Inverse characteristic M12388-1 v23 Table 128. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , 1.5 x I ≤ I ≤ 20 x I ±2.0% or ±40 ms whichever is greater æ...
  • Page 93 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 129. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is greater æ...
  • Page 94 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 130. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is greater ×...
  • Page 95 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 132. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0% 1.5 x I ≤...
  • Page 96 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 SEMOD116978-2 v10 Table 134. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 97 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 135. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 98 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 136. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps ±5.0% or ±45 ms whichever is greater of 0.01 æ...
  • Page 99: Ordering For Customized Ied

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 25. Ordering for customized IED GUID-B35852AB-ADB2-42E0-BA3A-55203EBB5C70 v11 Table 137. General guidelines Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
  • Page 100 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 140. Product definition ordering codes Product RES670* Product version Configuration alternative RES670 Phasor measurement unit ACT configuration No ACT configuration downloaded Ordering number RES670 Phasor measurement unit 1MRK002824-AG Table 141. Differential protection Position Table 142.
  • Page 101 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 149. Frequency protection Position Table 150. Frequency functions Function Function Ordering no Position Available Selected Notes and rules identification Underfrequency protection SAPTUF 1MRK005914-AC 0–6 Overfrequency protection SAPTOF 1MRK005914-BB 0–6 Rate-of-change of frequency protection SAPFRC 1MRK005914-CB...
  • Page 102 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 160. Logic functions Function Function Ordering no Position Available Selected Notes and rules identification Configurable logic blocks Q/T 1MRK005922-MX 0–1 Extension logic package 1MRK005922-DB 0–1 Table 161. Monitoring Position Table 162.
  • Page 103 Additional local HMI user dialogue language No additional HMI language HMI language, English US 1MRK002920-UB Selected Additional 2nd languages are continuously being added. Please get in touch with local ABB sales contact. Table 166. Casing selection Casing Ordering no Selection Notes and rules 1/2 x 19"...
  • Page 104 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 170. Analog system selection Analog system Ordering no Selection Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug). Slot position (front view/rear view) No Transformer input module included TRM 12I 1A, 50/60Hz, compression terminals...
  • Page 105 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 172. Maximum quantity of I/O modules, with ringlug terminals Note: Only every second slot can be used. Case sizes BOM/ Maximum in case 1/1 x 19” rack casing, 7 **) possible locations: P3, P5, P7, P9, P11, P13, P15 one (1) TRM 1/1 x 19”...
  • Page 106 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 173. Binary input/output module selection Binary input/ Ordering no Selection Notes and rules output modules Slot position (front view/rear view) 1/2 case with 1 █ █ █ 3/4 case with 1 █...
  • Page 107 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 173. Binary input/output module selection, continued Binary input/ Ordering no Selection Notes and rules output modules IOM 8 inputs, RL 1MRK000173-BE 110-125 VDC, 50mA, 10+2 output relays IOM 8 inputs, RL 1MRK000173-CE 220-250 VDC, 50mA, 10+2...
  • Page 108 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Table 174. Station communication and time synchronization selection Station communication and time Ordering no Selection Notes and rules synchronization Slot position (front view/rear view) Available slots in 1/2, 3/4 and 1/1 case █...
  • Page 109: Ordering For Pre-Configured Ied

    Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 26. Ordering for pre-configured IED GUID-D8264D89-2A4A-4AF6-A68F-B3CA1C5CDC5C v10 Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured IED.
  • Page 110 No additional HMI language HMI language, English US 1MRK002920-UB Selection for position #4 Additional 2nd languages are continuously being added. Please get in touch with local ABB sales contact. Hitachi Power Grids © Copyright 2017 Hitachi Power Grids. All rights reserved...
  • Page 111 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Casing Ordering no Notes and rules 1/2 x 19" rack casing, 1 TRM 1MRK000151-VA 3/4 x 19" rack casing, 1 TRM 1MRK000151-VB 3/4 x 19” rack casing, 2 TRM 1MRK000151-VE 1/1 x 19"...
  • Page 112 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Binary input/ Ordering no Notes and rules output modules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1BIM and 1 BOM required in positions P3 and P4 Slot position (front view/rear view)
  • Page 113 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Binary input/ Ordering no Notes and rules output modules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1BIM and 1 BOM required in positions P3 and P4 IOM 8 inputs, RL 1MRK000173-CE 220-250 VDC,...
  • Page 114 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Station communication and time Ordering no Notes and rules synchronization Slot position (front view/rear view) Available slots in 1/2, 3/4 and 1/1 case █ █ █ █ █ █ █ █...
  • Page 115: Ordering For Accessories

    IEDs is described in 1MRK 512 001-BEN and 1MRK 1 TRM/2 TRM with external neutral on currents circuits 001024-CA. Please refer to the website: (ordering number RK926 315–DC). www.abb.com/protection-control for detailed information. Test switches type RTXP 24 is ordered separately. Please...
  • Page 116 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 Configuration and monitoring tools M15042-3 v5 IP15162-1 v2 Front connection cable between LHMI and PC Quantity: 1MRK 001 665-CA SEMOD131414-4 v4 LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA...
  • Page 117 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 User documentation Specify the number of printed manuals requested Application manual Quantity: 1MRK 511 407-UEN ANSI Quantity: 1MRK 511 407-UUS Technical manual Quantity: 1MRK 511 408-UEN ANSI Quantity: 1MRK 511 408-UUS Commissioning manual Quantity: 1MRK 511 409-UEN...
  • Page 118 Phasor measurement unit RES670 1MRK 511 410-BEN L Version 2.2 ANSI Quantity: 1MRK 511 398-UUS Cyber security deployment guideline Quantity: 1MRK 511 399-UEN Application guide, Communication set-up Quantity: 1MRK 505 382-UEN Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name:...
  • Page 120 ABB Power Grids Sweden AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 10 738 00 00 Scan this QR code to visit our website https://www.abb.com/protection-control © Copyright 2017 Hitachi Power Grids. All rights reserved.