Summary of Contents for Oden Control P50

  • Page 1 Oden Control User’s gUide User´s guide installation and maintenance manUal Installation and maintenance manual oden p50, p220, p500 www.odencontrol.se...
  • Page 2: Table Of Contents

    CONTENT Content..............................1 General information..........................2 Technical description..........................4 Mechanical installation ..........................7 Electric connection ........................... 9 The calibration system..........................11 OVP – Oden Valve Program ........................13 Maintenance............................15 Trouble shooting............................. 16 Tips ................................. 18 Appendix: Technical specifications Drawings Electrical connection Version 2008-09-15...
  • Page 3: General Information

    Min. closing time 90˚ (s) 18-155*) Precision (˚) ± 0.5 ± 0.5 ± 0.1 ± 0.1 ± 0.1 *) Dependant on gear size. Please contact Oden Control AB for more information. 2.2.2 Linear actuators Linear actuators P30L P30EXL P50L P220L...
  • Page 4 Terms concerning safety It is of outmost importance that all users are follow instructions on how to install, maintain and use this series of electric actuators. The safety terms DANGER, WARNING, CAUTION and NOTE are used in these instructions to point out particular dangers and/or providing additional information on aspects which are not readily apparent. −...
  • Page 5: Technical Description

    TECHNICAL DESCRIPTION General The Oden P50/P220/P500 module system consists of: − Basic Unit − Turning or linear module − Valve adapter − Connection board Product Basic Unit Module Remarks P50R P50BU Turning actuator P50L P50BU Linear actuator P220R P220BU 220R...
  • Page 6 Turning module The turning module consists of a gear wheel, working as an inner part of a gear coupling, and two indicator pins firmly fitted and locked by Loctite. The indicator pins function as rough visual valve position indicators as well as internal mechanical stops.
  • Page 7 Connection boards Connection board A1 with analogue control is standard and included in delivery. There are other types of connection boards available for the P50, P220 and P500 units. Contact Oden Control for more information. Standard connection board The connection board is placed on the inside of the terminal lid, on the side of the actuator. The board has a terminal block with 6 inlets marked with text for 24 V DC and control signals.
  • Page 8: Mechanical Installation

    Installation of turning actuators The following installation instruction refers to the standard turning module described in section 3. When using the tapered clamping sleeve leave out the section about machining the turning module. Contact Oden Control for more information. Fitting of the turning module 1.
  • Page 9 Check that the spindle length above the valve flange adapter is Type A max A min within A max and A min, see table on the right. (mm) (mm) 5. Move the valve to closed position. P50R NOTE: Some valve shafts change the axial position in the P200R closed valve position.
  • Page 10: Electric Connection

    − One shielded cable with six conductors (wires) or − One cable for the power with two conductors and one shielded signal cable with four conductors. The maximum power peak current: − P50: − P220: − P500:...
  • Page 11 Use a cable which gives a voltage drop of max 2V. A bigger drop will reduce performance and may affect the function of the electronics. When calculating the drop - do not forget that the calculating length is twice the length of the cable.
  • Page 12: The Calibration System

    THE CALIBRATION SYSTEM To calibrate the actuator/valve-system means to find the closed valve position which corresponds to the closed position of the control signal, normally 4 mA. The Oden calibration system PC/PC means Power Calibration / Position Calibration. Which type of the two calibration methods you will use depends on the application. The position value will be automatically saved to a permanent memory during a power failure, see 6.3 Summary of calibration methods.
  • Page 13 If any of these ranges have been extended by making a change in the password protected Supervisor menu in OVP no saving occurs. Then you have to maintain the calibration point by continuously power the actuator for example by an UPS (Uninterrupted Power Supply) Please contact Oden Control AB for more information.
  • Page 14: Ovp - Oden Valve Program

    OVP – ODEN VALVE PROGRAM The Oden Valve Program, OVP, can be used to change the default settings of torque, speed, working range etc. However, it is not required for operating the actuator. If the default values are adequate for your application, it is not necessary to use the software.
  • Page 15 WARNING When performing a power calibration, the Automatic Power Calibration function is activated. To avoid automatic power calibration, the check box must be changed to “No” − New Automatic Power Calibration after > 8 hours power loss Two choices: Yes (default) or No. −...
  • Page 16: Maintenance

    MAINTENANCE Control and function test should be carried out only in every three years. In case of heavy loads of the actuator (and the valve) the intervals should be shorter. The Oden actuator gears and the bearings are lifetime greased and need no service.
  • Page 17: Trouble Shooting

    The interface between the actuator and the valve can cause problems depending on the lack of standards for valve flange and spindle. Oden Control can offer adapters for almost all types of valves. It is important to check that the right adapter is used. Check that the right valve closing direction, torque, speed and working range have been chosen.
  • Page 18 Blocked valve If the return signal is 2 mA (default) and the actuator does not react on a control signal the valve is probably blocked. Some common reasons for blockage; The necessary torque/force for the valve is not provided by the actuator. Check the setting in OVP. NB For a certain speed, use the maximum torque/force acceptable according to the valve specification.
  • Page 19: Tips

    OVP, no saving occurs. To maintain the calibration point for an extended working range, you will need to continuously power the actuator, for example by an UPS (Uninterrupted Power Supply). Please contact Oden Control AB for more information. −...
  • Page 20 SS 4212-06, black anodizing Steel components SS 2346, SS 2333 *) Speed depending on chosen torque. 2) UPS needed. 3) Parameters depending on chosen size of gear. Oden Control AB (publ) Phone: +46 (0)8-767 76 57 E-mail: sales@odencontrol.se Herserudsvägen 5...
  • Page 21 SS 4212-06, blue anodizing Aluminium components SS 4212-06, black anodizing Steel components SS 2346, SS 2333 1) Speed depending on chosen force. 2) UPS needed. Oden Control AB (publ) Phone: +46 (0)8-767 76 57 E-mail: sales@odencontrol.se Herserudsvägen 5 Fax: +46 (0)8-767 04 17 Web: www.odencontrol.se...
  • Page 22 1 60 1 20 Speed (degree/ sec) Oden P 500 Torque (Nm) Force (kN) 12 0 10 0 Speed (degree/sec) Oden Control AB (publ) Phone: +46 (0)8-767 76 57 E-mail: sales@odencontrol.se Nilstorpsvägen 53 Fax: +46 (0)8-767 04 17 Web: www.odencontrol.se...
  • Page 29 Oden Control AB Control that it is 24 V DC +/- 15 % at the Connection diagram Connection board. Nilstorpsvägen 53 181 47 Lidingö, Sweden Doc.Nr P50, P220 and P500 Phone +46-8-767 76 57 Fax +46-8-767 47 18 P50.90 E-mail oden@odencontrol.se www.odencontrol.se...
  • Page 30 Oden P50-P220-P500 Block Diagram 2-phase Current +24VDC 2-phase Switchmode driver Sensing Power stepper Supply motor Ground 4-20 mA Driver Analog-Digital Control 4-20mA converter Logic Input 4-20 mA Digital-Analog converter 4-20mA Output Backup capacitor Feedback Main Control Feedback control & Asynchronous...