Install the air unit at a place that can withstand its weight. is shorted and operated forcibly, or parts other than those specified - Inadequate strength may cause the unit to fall down, resulting in by Mitsubishi Electric are used, fire or explosion may result. injuries. •...
Page 3
Precautions for devices that use Warning: • Note the following when building a heater in the air R410A refrigerant conditioning system. - Leave enough space between units for proper ventilation so that Caution: the indoor unit temperature does not exceed 40˚C when •...
PART NAMES AND FUNCTIONS Indoor (Main) Unit Air outlet Air inlet Remote controller [PAR-21MAA] Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button. G Operation buttons TEMP. ON/OFF MENU ON/OFF FILTER BACK MONITOR/SET CHECK...
Page 6
[Display] CENTRALLY CONTROLLED 1Hr. ON OFF CLOCK CHECK FILTER CHECK MODE TEST RUN STAND BY ERROR CODE FUNCTION NOT AVAILABLE DEFROST TEMP. ON/OFF A Current time/Timer B Centralized control C Timer OFF D Timer indicator E Operation mode: COOL, DRY, AUTO, FAN, HEAT...
TROUBLE SHOOTING 7-1. How to check the parts Parts name Check points Room temparature Disconnect the connector, then measure the resistance using a tester. thermistor (Sorrounding temperature 10˚C~30˚C[50˚F~86˚F]) (TH21) Liquid pipe thermistor (TH22) Normal Abnormal Gas pipe thermistor (Refer to the thermistor) (TH23) 4.3kΩ...
Page 15
<Thermistor Characteristic graph> < Thermistor for lower temperature > Room temparature thermistor(TH21) Thermistor for Liquid pipe thermistor(TH22) lower temperature Gas pipe temparature thermistor(TH23) Drain sensor(DS) =15kΩ ± 3% Thermistor R Fixed number of B=3480kΩ ± 2% Rt=15exp { 3480( 273+t 0˚C 32˚F 15kΩ...
Page 16
<Output pulse signal and the valve operation> Output Output : 1 ¡ 2 ¡ 3 ¡ 4 ¡ 1 (Phase) Closing a valve Opening a valve : 4 ¡ 3 ¡ 2 ¡ 1 ¡ 4 ø1 The output pulse shifts in above order. ø2 ✻...
Page 17
Operation by switch Switch Pole Remarks Function Thermistor<Intake temperature Indoor unit Built-in remote controller Address board detection>position Filter crogging detection Provided Not provided <At delivery> Filter life 2,500hr 100hr 1 2 3 4 5 6 7 8 9 10 Air intake Effective Not effective Remote indication switching...
DISASSEMBLY PROCEDURE 8-1 CONTROL BOX Be careful removing heavy parts. OPERATING PROCEDURE PHOTOS 1.Removing the control box cover (1)Remove the fixing screws(two) of the cover(A) and remove the cover. Fig.1 8-2 THERMISTOR (Liquid piping temperature detection) OPERATING PROCEDURE PHOTOS 1.Removing the cover (1)Remove the fixing screws(two) of the cover(C) and remove the cover.
Page 20
8-3 THERMISTOR (Intake air temperature detection) Be careful removing heavy parts. OPERATING PROCEDURE PHOTOS 1.Removing the thermistor and thermistor holder (1)Pull out the thermistor holder(F) and thermistor (G) which are fixed the control box. Fig.1 (F),(G) 8-4 DRAINPAN OPERATING PROCEDURE PHOTOS 1.Removing the cover (1)Remove the fixing screws of the cover(H) and...
Page 21
8-5 THERMISTOR (Gus piping temperature detection) OPERATING PROCEDURE PHOTOS 1.Removing the cover (1)Remove the fixing screw of the cover(J) and remove the cover. 2.Removing the thermistor (1)Remove the thermistor(K), from the thermistor holder(L), which are installed on the copper tube. Fig.1 Fig.2 (K),(L)
Page 22
8-6 FAN and FAN MOTOR OPERATING PROCEDURE PHOTOS 1.Removing the filter (1)Press the tabs of the filter and remove the filter in the direction of the arrow 1. 2.Removing the bottom plate (1)Remove the fixing screws (two) of the bottom plate(N) and remove the plate.
Page 23
8-7 HEAT EXCHANGER OPERATING PROCEDURE PHOTOS 1.Removing the drainpan with procedure 8-4 2.Removing the cover(J) with procedure 8-5 3.Removing the Heat exchanger (1)Remove the fixing screws of the heat exchang- er(S) and remove the heat exchanger. Fig.1 Fig.2...
Page 24
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Issued in Aug. 2005 HWE05160 New publication, effective Aug. 2005 Printed in Japan Specifications subject to change without notice...