Relion
615 series
Motor Protection and Control
REM615
IEC 60870-5-103 Point List Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 615 Series

  • Page 1 ® Relion 615 series Motor Protection and Control REM615 IEC 60870-5-103 Point List Manual...
  • Page 3 Document ID: 1MRS756882 Issued: 2012-05-11 Revision: C Product version: 4.0 © Copyright 2012 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction...............5 This manual..................5 Intended audience................5 Product documentation...............5 Product documentation set............5 Document revision history.............6 Related documentation..............6 Symbols and conventions..............7 Symbols..................7 Document conventions..............7 Functions, codes and symbols............8 Section 2 IEC 60870-5-103 data mappings........11 Overview...................11 Supported functions................11 Point list for REM615 Ver.4.0 ME01-03..........13 Indications and controls...............13...
  • Page 8 Table of contents LD0.MAPGAPC5 Multipurpose analog protection function (5)................19 LD0.MAPGAPC6 Multipurpose analog protection function (6)................19 LD0.XRGGIO130 Alarm and warning........19 LD0.PHPTUV3 Phase undervoltage protection - stage 3.....................20 LD0.PHPTUV1 Phase undervoltage protection - stage 1.....................20 LD0.PSPTUV1 Positive-sequence undervoltage protection - stage 1..............20 LD0.NSPTOV2 Negative-sequence overvoltage protection - stage 2..............20 LD0.NSPTOV1 Negative-sequence overvoltage...
  • Page 9 Table of contents LD0.DEFLPDEF1 Directional earth-fault protection - low stage 1..................26 LD0.CMMXU1 Phase currents (1) limit supervision....26 LD0.RESCMMXU1 Residual current (1) limit supervision................26 LD0.VMMXU1 Phase voltage (1) limit supervision....27 LD0.RESVMMXU1 Residual voltage (1) limit supervision................27 CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection................27 LD0.SSCBR1 Circuit breaker (1) condition monitoring..28 CTRL.DCXSWI1 Disconnector (1) - controllable object..28...
  • Page 10 Table of contents Auto-reclosure indications in monitor direction.......38 Measurands in monitor direction..........39 Generic functions in monitor direction........39 Selection of standard information numbers in control direction..................39 System functions in control direction........39 Generic functions in monitor direction........39 Basic application functions............40 Miscellaneous................40 Section 4 Glossary.................41 REM615 Point List Manual...
  • Page 11: Section 1 Introduction

    Section 1 1MRS756882 C Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
  • Page 12: Document Revision History

    B/2010-06-11 Content updated to correspond to the product version C/2012-05-11 Content updated to correspond to the product version Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID IEC 60870-5-103 Communication Protocol Manual...
  • Page 13: Symbols And Conventions

    Section 1 1MRS756882 C Introduction Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
  • Page 14: Functions, Codes And Symbols

    Section 1 1MRS756882 C Introduction 1.4.3 Functions, codes and symbols Table 1: REM615 functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent PHLPTOC1 3I> (1) 51P-1 (1) protection, low stage Three-phase non-directional overcurrent PHIPTOC1 3I>>> (1) 50P/51P (1) protection, instantaneous stage Non-directional earth-fault protection, low stage...
  • Page 15 Section 1 1MRS756882 C Introduction Function IEC 61850 IEC 60617 IEC-ANSI Disconnector position indication DCSXSWI1 I <-> O DC (1) I <-> O DC (1) DCSXSWI2 I <-> O DC (2) I <-> O DC (2) DCSXSWI3 I <-> O DC (3) I <->...
  • Page 17: Section 2 Iec 60870-5-103 Data Mappings

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings Section 2 IEC 60870-5-103 data mappings Overview These tables show the default point definitions. The user is able to freely remap all these data. In that case PCM600 can provide an updated point list export of the new outlook.
  • Page 18 Section 2 1MRS756882 C IEC 60870-5-103 data mappings IEC 61850 ME01 ME02 ME03 MAPGAPC1 MAPGAPC2 MAPGAPC3 MAPGAPC4 MAPGAPC5 MAPGAPC6 CBXCBR1 ● ● ● DCXSWI1 ● ● ● DCXSWI2 ● ● ● ESXSWI1 ● ● ● DCSXSWI1 ● ● ● DCSXSWI2 ●...
  • Page 19: Point List For Rem615 Ver.4.0 Me01-03

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings Point list for REM615 Ver.4.0 ME01-03 2.3.1 Indications and controls Table 3: Explanations of the indications and controls table columns Column name Description IEC 61850 Original IED data object identification. Described in the IEC 61850 format as name Logical Device.Logical Node and thereafter .Data Object.Data Attribute.
  • Page 20: General Data(Fun=10) - 615-Specific

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU LD0.LEDPTRC1 .Op.general Global operate 10=Operate .Str.general Global start 10=Start 2.3.1.2 General Data(FUN=10) - 615-specific Table 5: General Data(FUN=10) - 615-specific IEC 61850 name SA name Description DPI value...
  • Page 21: Ld0.Mvgapc1 Multipurpose Binary Inputs (1)

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.3 LD0.MVGAPC1 Multipurpose binary inputs (1) Table 6: LD0.MVGAPC1 Multipurpose binary inputs (1) IEC 61850 name SA name Description DPI value ASDU LD0.MVGAPC1 .Q1.stVal Input 1 signal 10=On .Q2.stVal Input 2 signal 10=On .Q3.stVal Input 3 signal...
  • Page 22: Ld0.Srgapc2 Multipurpose Binary Outputs - Flip-Flop Resets (2)

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.6 LD0.SRGAPC2 Multipurpose binary outputs - flip-flop resets (2) Table 9: LD0.SRGAPC2 Multipurpose binary outputs - flip-flop resets (2) IEC 61850 name SA name Description DPI value ASDU LD0.SRGAPC2 .Rs1.ctlVal Reset flip-flop 1 10=Reset .Rs2.ctlVal Reset flip-flop 2...
  • Page 23: Ld0.Spcggio2 Multipurpose Binary Outputs (2)

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.8 LD0.SPCGGIO2 Multipurpose binary outputs (2) The binary outputs may be configured either as pulse- or persistent-type outputs. Pulse-type outputs are triggered with the write value "ON". Persistent-type outputs can be written with both "ON" and "OFF" values. The persistent type is the same as the toggled mode on LHMI and WHMI.
  • Page 24: Ld0.Frpfrq1 Frequency Protection (1)

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.11 LD0.FRPFRQ1 Frequency protection (1) Table 14: LD0.FRPFRQ1 Frequency protection (1) IEC 61850 name SA name Description DPI value ASDU LD0.FRPTRC1 .Str.general START Stage start 10=Start LD0.FRPTOF1 Overfrequency .Op.general OPR_OFRQ -Operate 10=Operate LD0.FRPTUF1 Underfrequency .Op.general...
  • Page 25: Ld0.Mapgapc3 Multipurpose Analog Protection Function (3)

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.15 LD0.MAPGAPC3 Multipurpose analog protection function (3) Table 18: LD0.MAPGAPC3 Multipurpose analog protection function (3) IEC 61850 name SA name Description DPI value ASDU LD0.MAPGAPC3 .Str.general START Stage Start 10=Start .Op.general OPERATE Stage Operate 10=Operate 2.3.1.16...
  • Page 26: Ld0.Phptuv3 Phase Undervoltage Protection - Stage 3

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.20 LD0.PHPTUV3 Phase undervoltage protection - stage 3 Table 23: LD0.PHPTUV3 Phase undervoltage protection - stage 3 IEC 61850 name SA name Description DPI value ASDU LD0.PHPTUV3 Stage 3 .Str.phsA -phsA start 10=Start .Str.phsB -phsB start...
  • Page 27: Ld0.Nsptov1 Negative-Sequence Overvoltage Protection - Stage 1

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.24 LD0.NSPTOV1 Negative-sequence overvoltage protection - stage 1 Table 27: LD0.NSPTOV1 Negative-sequence overvoltage protection - stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.NSPTOV1 Stage 1 .Str.general START -general start 10=Start .Op.general OPERATE...
  • Page 28: Ld0.Xggio100 Physical Binary I/O Signals (Status Only)

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.27 LD0.XGGIO100 Physical binary I/O signals (status only) Table 30: LD0.XGGIO100 Physical binary I/O signals (status only) IEC 61850 name SA name Description DPI value ASDU LD0.XGGIO100 .SPCSO1.stVal X100-Output 1 10/01=On/Off .SPCSO2.stVal X100-Output 2 10/01=On/Off .SPCSO3.stVal...
  • Page 29: Ld0.Mnsptoc2 Negative-Sequence Overcurrent Protection For Motors (2)

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.31 LD0.MNSPTOC2 Negative-sequence overcurrent protection for motors (2) Table 34: LD0.MNSPTOC2 Negative-sequence overcurrent protection for motors (2) IEC 61850 name SA name Description DPI value ASDU LD0.MNSPTOC2 .Str.general START Stage2 start 10=Start .Op.general OPERATE Stage2 operate...
  • Page 30: Ld0.Mpttr1 Motor Thermal Overload Protection

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.36 LD0.MPTTR1 Motor thermal overload protection Table 39: LD0.MPTTR1 Motor thermal overload protection IEC 61850 name SA name Description DPI value ASDU LD0.MPTTR1 .StrInh.general BLK_RESTART Block restart 10=Restart .AlmThm.general ALARM Thermal alarm 10=Alarm .Op.general OPERATE...
  • Page 31: Ld0.Arcsarc3 Fault Arc Protection - Stage 3

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.41 LD0.ARCSARC3 Fault arc protection - stage 3 Table 44: LD0.ARCSARC3 Fault arc protection - stage 3 IEC 61850 name SA name Description DPI value ASDU LD0.ARCSARC31 .FADet.stVal ARC_FLT_DE T Arc detected 10=Detect LD0.ARCPTRC31 .Op.general...
  • Page 32: Ld0.Phlptoc1 Phase Overcurrent Protection - Low Stage 1

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.45 LD0.PHLPTOC1 Phase overcurrent protection - low stage 1 Table 48: LD0.PHLPTOC1 Phase overcurrent protection - low stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.PHLPTOC1 Low stage (1) .Str.phsA -phsA start 10=Start...
  • Page 33: Ld0.Vmmxu1 Phase Voltage (1) Limit Supervision

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.49 LD0.VMMXU1 Phase voltage (1) limit supervision Table 52: LD0.VMMXU1 Phase voltage (1) limit supervision IEC 61850 name SA name Description DPI value ASDU LD0.VMMXU1 .HiAlm.stVal HIGH_ALARM High alarm 10=Alarm .HiWrn.stVal HIGH_WARN High warning 10=Warning .LoWrn.stVal...
  • Page 34: Ld0.Sscbr1 Circuit Breaker (1) Condition Monitoring

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.52 LD0.SSCBR1 Circuit breaker (1) condition monitoring Table 55: LD0.SSCBR1 Circuit breaker (1) condition monitoring IEC 61850 name SA name Description DPI value ASDU LD0.SSCBR1 .RsAccAPwr.ctlVal RST_IPOW Accumul. energy reset 10=Reset .RsCBWear.ctlVal RST_CB_WEAR CB life/op.counters reset 10=Reset...
  • Page 35: Ctrl.dcxswi2 Disconnector (2) - Controllable Object

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.54 CTRL.DCXSWI2 Disconnector (2) - controllable object Table 57: CTRL.DCXSWI2 Disconnector (2) - controllable object IEC 61850 name SA name Description DPI value ASDU CTRL.DCCILO2 .EnaOpn.stVal ENA_OPEN Open enabled 10=Enabled .EnaCls.stVal ENA_CLOSE Close enabled 10=Enabled .ItlByPss.stVal...
  • Page 36: Ctrl.dcsxswi2 Disconnector (2) - Non-Controllable Object

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings 2.3.1.57 CTRL.DCSXSWI2 Disconnector (2) - non-controllable object Table 60: CTRL.DCSXSWI2 Disconnector (2) - non-controllable object IEC 61850 name SA name Description DPI value ASDU CTRL.DCSXSWI2 .Pos.stVal POSITION Disconnector 2 pos 10/01=Close/Open 2.3.1.58 CTRL.DCSXSWI3 Disconnector (3) - non-controllable object Table 61: CTRL.DCSXSWI3 Disconnector (3) - non-controllable object...
  • Page 37: Class 2 Data Measurands

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .SPCSO8.stVal LED 8 state 10=On .SPCSO9.stVal LED 9 state 10=On .SPCSO10.stVal LED 10 state 10=On .SPCSO11.stVal LED 11 state 10=On 2.3.2 Class 2 data measurands Class 2 data measurands use ASDU type 9, function type 10 and information number 236 for frame 6 and 237 for frame 7.
  • Page 38: Class 2 Private Measurand Data (6 And 7) For Rem615

    Section 2 1MRS756882 C IEC 60870-5-103 data mappings Table 65: Explanations of the class 2 data measurands table columns Column name Description IEC 61850 Original IED data object identification. Described in the IEC 61850 format as name Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the same as the application function block name.
  • Page 39 Section 2 1MRS756882 C IEC 60870-5-103 data mappings IEC 61850 name Description Scale ix (M-a) .phsB.cVal.mag -phsB magnitude .phsC.cVal.mag -phsC magnitude LD0.VMMXU1.PPV Phase-to-phase voltage .phsAB.cVal.mag -phsAB magnitude .phsBC.cVal.mag -phsBC magnitude .phsCA.cVal.mag -phsCA magnitude LD0.VSMSQI1 Sequence of voltages (1) LD0.VSMSQI1 Sequence of voltages .SeqA.c1.cVal.mag -positive magnitude .SeqA.c2.cVal.mag...
  • Page 41: Section 3 Interoperability Profile For 615 Series Iec 60870-5-103

    Section 3 1MRS756882 C Interoperability profile for 615 series IEC 60870-5-103 Section 3 Interoperability profile for 615 series IEC 60870-5-103 Physical layer 3.1.1 Electrical interface ⊠ EIA RS-485 ⃞ Number of loads ......for one protection equipment NOTE - EIA RS-485 standard defines unit loads so that 32 of them can be operated on one line. For detailed information refer to clause 3 of EIA RS-485 standard.
  • Page 42: Application Layer

    Section 3 1MRS756882 C Interoperability profile for 615 series IEC 60870-5-103 Application layer 3.3.1 Transmission mode for application data Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion standard. 3.3.2 COMMON ADDRESS of ASDU ⊠...
  • Page 43: Supervision Indications In Monitor Direction

    Section 3 1MRS756882 C Interoperability profile for 615 series IEC 60870-5-103 ⃞ <27> Auxiliary input 1 ⃞ <28> Auxiliary input 2 ⃞ <29> Auxiliary input 3 ⃞ <30> Auxiliary input 4 Note <27>...<30>: Depending on Binary I/O options and application usage there may be additional auxiliary inputs available in the IED.
  • Page 44: Auto-Reclosure Indications In Monitor Direction

    Section 3 1MRS756882 C Interoperability profile for 615 series IEC 60870-5-103 ⃞ <66> Start /pick-up L ⃞ <67> Start /pick-up N ⊠ <68> General trip ⃞ <69> Trip L ⃞ <70> Trip L ⃞ <71> Trip L ⃞ <72> Trip I>> (back-up operation) ⃞...
  • Page 45: Measurands In Monitor Direction

    Section 3 1MRS756882 C Interoperability profile for 615 series IEC 60870-5-103 3.3.3.7 Measurands in monitor direction Semantics ⊠ <144> Measurand I ⊠ <145> Measurands I, V ⊠ <146> Measurands I, V, P, Q ⊠ <147> Measurands I ⊠ <148> Measurands I , P, Q, f L1,2,3 L1,2,3...
  • Page 46: Basic Application Functions

    Section 3 1MRS756882 C Interoperability profile for 615 series IEC 60870-5-103 3.3.5 Basic application functions ⃞ Test mode ⃞ Blocking of monitor direction ⊠ Disturbance data ⃞ Generic services ⊠ Private data 3.3.6 Miscellaneous Measurands are transmitted as Class2 data using ASDU 3 or ASDU 9. The default MVAL scalings in 615 series devices is 2.4.
  • Page 47: Section 4 Glossary

    Section 4 1MRS756882 C Glossary Section 4 Glossary 615 series Series of numerical IEDs for low-end protection and supervision applications of utility substations, and industrial switchgear and equipment Electromagnetic compatibility Human-machine interface International Electrotechnical Commission IEC 60870-5-103 1. Communication standard for protective equipment 2.
  • Page 52 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...