STExCP8-PB
1) Warnings
• USE COVER BOLTS CLASS A4-70
• DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
• POTENTIAL ELECTROSTATIC HAZARD
• ALL ENTRIES M20 X 1.5
• DO NOT OPEN WHEN ENERGIZED
• IF TEMPERATURE EXCEEDS 70°C AT
ENTRY OR 80°C AT BRANCHING POINT
USE SUITABLE RATED CABLE AND CABLE
GLANDS
2) Rating & Marking Information
2.1 ATEX / IECEx / UKEX Certification
All units have a rating label, which carries the following
important information:-
STExCP8-PB-S (Single Switch)
Model No.:
STExCP8-PB-D (Dual Switch)
STExCP8-PB-S-L or -C (Single Switch
with LED
STExCP8-PM-S (Single Switch)
STExCP8-PM-D (Dual Switch)
STExCP8-PM-S-L or -C (Single Switch
with LED
STExCP8-PT-S (Single Switch)
STExCP8-PT-D (Dual Switch)
STExCP8-PT-S-L or -C (Single Switch
with LED
Input Voltage:
DC Units
AC Units
series , end-of-line or LED devices only)
STExCP8-PB-S ; -PM-S ; -PT-S Codes:
Ex db IIC T6 Gb Ta. -55°C to +70°C
STExCP8-PT-S-L or -C ; STExCP8-PM-S-L or -C ;
STExCP8-PB-S-L or -C Codes:
Ex db IIC T5 Gb Ta. -55 to +70°C
Ex db IIC T6 Gb Ta. -55 to +65°C
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D204-00-201-IS
STExCP8-PB-S, STExCP8-PB-D, STExCP8-PM-S, STExCP8-PM-D,
For use in Flammable Gas Atmospheres and Marine Environments
48Vdc Max
250Vac max (units without
Issue 8
10-09-2023
INSTRUCTION MANUAL
(ATEX / IECEx / UKEX / DNV)
STExCP8-PT-S & STExCP8-PT-D CALL POINTS
STExCP8- PB-D ; -PM-D ; -PT-D Codes:
STExCP8-PT-D-L or -C ; STExCP8-PM-D-L or -C ;
STExCP8-PB-D-L or -C Codes:
Certificate No.
ATEX Marking
Equipment Group and
Category:
CE Marking
Notified Body No.
UKCA Marking
Notified Body No.
The units can be installed in locations with the following
conditions:
Area Classification Gas:
Zone 1
Zone 2
Gas Groupings:
Group IIA
Group IIB
Group IIC
Sheet 1 of 6
STExCP8-PM
STExCP8-PT
Ex db IIC T5 Gb Ta. -55°C to +70°C
Ex db IIC T6 Gb Ta. -55°C to +60°C
Ex db IIC T4 Gb Ta. -55 to +70°C
Ex db IIC T5 Gb Ta. -55 to +65°C
Ex db IIC T6 Gb Ta. -55 to +50°C
DEMKO 15 ATEX 1589X
IECEx ULD 15.0018X
UL21UKEX2133X
II 2G
2813
0518
Explosive gas air mixture likely to occur in
normal operation.
Explosive gas atmosphere not likely to
occur in normal operation but may be
present for short periods.
Propane
Ethylene
Hydrogen and Acetylene
www.e2s.com
Tel: +44 (0)208 743 8880