hit counter script
Download Print this page
ABB CIP Safety FSCS-21 Quick Installation Manual
ABB CIP Safety FSCS-21 Quick Installation Manual

ABB CIP Safety FSCS-21 Quick Installation Manual

Functions module

Advertisement

Quick Links

OPTIONS FOR ABB DRIVES
FSCS-21 CIP Safety™ functions module
Quick installation guide
Related manual
FSCS-21 CIP Safety™ functions module user's manual (3AXD50001065478 [English])
Safety instructions
WARNING
damage to the equipment can occur.
Description of the FSCS-21 module
The FSCS-21 module adds support for the EtherNet/IP™ communication protocol and the CIP Safety™
extensions. With the module, you can connect the drive to a programmable logic controller (PLC). The
module supports the Safe torque off (STO) and Safe stop 1 with time monitoring (SS1-t) safety functions
with CIP Safety over EtherNet/IP.
Intentional misuse
Use the module according to the instructions given in the applicable manuals. ABB is not responsible for
any damage caused by the misuse of the module. The module is not designed to protect a machine
against intentional misuse or sabotage.
Limitations for use
Use the module only in an environment that meets the requirements given in the drive hardware manual.
Do not use the module in an environment that has conductive dust in the air. If you use the module in an
environment that does not meet the requirements, equipment malfunction or loss of a safety function
can occur.
Drive compatibility
The FSCS-21 module supports only the drives and firmware versions specified below. It has not been
tested with other drives or firmware versions.
ACS880 drives with primary control program version 2.90 or later
ACS580 drives with standard control program version 2.07 or later
ACS380 drives with machinery control program version 2.07 or later
Layout of the module
1
EtherNet/IP™
CIP Safety™
2
3
5
4
Obey the safety instructions of the drive. If you ignore them, injury or death, or
No. Description
1
Lock
2
Grounding screw
3
RJ-45 connector [X1] to Ethernet
7
4
RJ-45 connector [X2] for chaining another module
5
STO connector (under connectors [X1] and [X2])
6
Diagnostic LEDs
6
7
MAC address

Advertisement

loading

Summary of Contents for ABB CIP Safety FSCS-21

  • Page 1 Intentional misuse  Use the module according to the instructions given in the applicable manuals. ABB is not responsible for any damage caused by the misuse of the module. The module is not designed to protect a machine against intentional misuse or sabotage.
  • Page 2 FSCS-21 will keep the drive STO activated (safe state) until it is configured and a safety program is in place in the safety PLC. www.abb.com/drives © Copyright 2024 ABB. All rights reserved. Original instructions. Specifications subject to change without notice.