COMMUNICATION BMS ........................82 9.1 Communication in Modbus protocol ..................82 Communication in BACnet protocol..................84 10. COMMISSIONING ..........................85 10.1 AHU factory settings ....................... 85 10.2 AHU factory control ........................ 85 10.3 Recommendations........................86 11. MAINTENANCE - REPLACEMENT OF PARTS - ALARMS ............87 11.1 Safety instructions ........................
1.2 Safety instructions General • Meaning of the danger labels present on the access doors: Live equipment Rotating machine Potentially flammable dust filters • Put on appropriate PPE (Personal Protective Equipment) before any intervention. • Before installing the air handling unit, ensure that the support and location are sufficiently • Strong enough to support the weight of the unit and accessories. • Do not open doors or panels without shutting down the unit. Case of emergency or danger •...
PRODUCT RANGE PRESENTATION 2.1 Range Extraction of stale air and supply of fresh air in public/private premises with heat recovery by a rotating heat exchanger. Installation on feet indoor or outdoor with accessories. 10 sizes 700 (700 m /h), 1300 (1 600 m /h), 1900 (2 100 m /h), 2500 (3 000 m /h), 3500 (3 600 m /h), 4500 (4 500 m /h), 6000/6000HP (6 000 m...
2.2 Main components 2.2.1 General description Version without heater (D) or with electric heater (DI) Version HDR Version HDL Electric heater DI after the fan on size 15000 Version VDR Version VDL 16 15 10 11 Description Symbol Description Symbol ...
Page 7
Version hot water coil (DC) or reversible cold water/hot water coil (DFR) Version HDR Version HDL Size 15000 Version VDR Version VDL Description Symbol Description Symbol Outdoor air duct connection Supply air duct connection Pressure guard on outdoor air filter Extract air duct connection Outdoor air temperature sensor Filter G4 (Coarse 70%) outdoor air Pressure guard extract air filter...
Page 8
Version direct expansion coil (DX) Version HDR Version HDL 7 17 Reference Description Symbol Outdoor air duct connection Pressure guard on outdoor air filter Outdoor air temperature sensor Filter G4 (Coarse 70%) outdoor air F7 (ePM1 55%) filter on outdoor Air Rotary heat exchanger Direct expansion coil Supply air fan Supply air temperature sensor Supply air duct connection ...
Page 9
Hot and cold water coil (DC/DF) Version HDR Version HDL 17 18 Size 15000 11 12 13 1 2 3 4 5 9 10 18 17 Description Symbol Outdoor air duct connection Pressure guard on outdoor air filter Outdoor air temperature sensor Filter G4 (Coarse 70%) outdoor air F7 (ePM1 55%) filter on outdoor Air Rotary heat exchanger Hot water coil...
Page 10
2.2.2 Rotary heat exchanger - Principle / Construction The construction of the rotating heat exchanger used into the RHE consists of alternating layers of flat and corrugated aluminum foil, which form a spiral from the center. This results in a defined structure of small triangular flutes. Supply and exhaust air each pass through half of the wheel in counter flow directions. The rotor exchanger is a rotating transfer media. It temporarily takes up the heat from the warm air stream and releases it in the colder air stream. Purge sector: A bleed sector allows flushing stale air present in the “honeycombs” before the wheel passes in front of the fresh airflow.
2.3 Functional synoptics (examples) RHE D / DI Sizes 700 to 10000 Exhaust air Extract air Rejet air vicié Reprise air vicié SCO2 Outdoor air Supply air Aspiration air neuf Sou age air neuf HR-R Bat2 Triac1 Size 15000 Exhaust air Extract air Rejet air vicié...
Page 12
RHE DC/DF Exhaust air Reprise air vicié Rejet air vicié Extract air Outdoor air Supply air Sou age air neuf Aspiration air neuf Bat1 Bat3 HR-R Pr10 RHE DX Exhaust air Rejet air vicié Reprise air vicié Extract air Outdoor air Supply air Aspiration air neuf Sou age air neuf...
INSTALLATION 3.1 Machine identification / Symbols Identification label fixed on the casing Version HD (supply side upward) Version VD (on upper righthand corner) Meaning of the symbols present on the unit and in the manual AHU labelling Symbol Instructions manual Outdoor air Extract air ...
Page 15
RHE HDR 700 / 1300 / 1900 / 2500 / 3500 / 4500 Right hand side access door on the supply air flow direction Condensat sur ER et EX Condensat drain on DFR and DX RHE HDL 700 / 1300 / 1900 / 2500 / 3500 / 4500 Left hand side access door on the supply air flow direction Condensat drain on DFR and DX Condensat sur ER et EX Dimensions (mm) Size...
Page 16
RHE HDR 6000 / 8000 / 10000 - Deliver in 2 parts. Right hand side access door on the supply air flow direction 1/2" DX Model - Size 6000 DC/DF Model DX Model - Sizes 8000 - 10000 with direct expansion coil with direct expansion coil with hot and cold water coils Sizes (mm) 6000 HD 1972 1034...
Page 17
RHE HDL 6000 / 8000 / 10000 Left hand side access door on the supply air flow direction 1/2" DC/DF Model DX Model size 6000 DX Model sizes 8000 - 10000 with hot and cold water coils with direct expansion coil with direct expansion coil Sizes (mm) 6000 HD 1972 1034 1315 1553...
Page 18
RHE HDR - Size 15000 model DC/DF In line air connection / right hand side maintenance acces (delivered in 2 parts) 1/2" Model DFR4R Model DC and DFR water coil water coil Size 15000 3325 1552 1774 2215 2460 2100 2288 1409 1798 1840 Size 15000 2107 1 1/2" Weight (kg) DC / DFR2R DFR4R DC/DF Size...
Page 19
RHE HDL - Size 15000 model DC/DF In line air connection / Left hand side maintenance acces (delivered in 2 parts) Detail Y 1/2" Model DFR4R Model DC and DFR water coi water coil Size 15000 3325 1552 1774 2215 2460 2100 2288 1409 1798 1840 Size 15000 2107 1 1/2" Weight (kg) DC / DFR2R DFR4R DC/DF...
Page 20
RHE HDR OI 700 / 1300 / 1900 / 2500 / 3500 / 4500 / 6000 / 8000 / 10000 Right hand side access door on the supply air flow direction RHE HDL OI 700 / 1300 / 1900 / 2500 / 3500 / 4500 / 6000 / 8000 / 10000 Left hand side access door on the supply air flow direction RHE HDR OI / HDL OI 15000 Dimensions (mm)
Page 21
Weight (kg) Sizes A1+ A2 A1+ A2 A1+ A2 6000 HD OI 8000 HD OI 10000 HD OI 1005 15000 HD OI 1775 1865 1815 Weight (kg) Sizes DC/DF A1+ A2 A1+ A2 A1+ A2 6000 HD OI 8000 HD OI 10000 HD OI 1007 1041...
MIB for RHE 15000 Dimensions (mm) Description MIB 15000 1549 2215 2460 1563 Dimensions (mm) Description MIB 15000 1409 2000 1798 Dimensions (mm) Description MIB 15000 1388 1840 3.3 Handling and lifting The units are delivered screwed to pallets, except size 15000 delivered on its frame. The RHE dual flow air handling units can be handled by a pallet transporter, a forklift, or a crane. The han- dling machines will be adapted to the load and the lifting conditions. In all cases, the lifting will be done at the device’s base. The centre of gravity is located at the centre of the unit. The device must be carefully manipulated only in the horizontal position. Ø 50 mm. holes are provided for in the frame to allow passing a pipe to hook the slings. To avoid deteriorating the unit’s envelope, long length slings and lifting beam spacers must be used. In case a forklift / pallet transporter is used, the forks should be long enough to avoid pushing in the lower panel. Position the forks low enough so as to not damage the doors. Lift gently.
Moving and lifting RHE 15000 Exchanger module Coil module Crane lifting module by module or after assembly on the ground. 3.4 Placement and attachment point Placement The RHE must be laid on a smooth horizontal surface capable of supporting the load. The RHE HD / VD units are designed for an installation inside the building. Only the HD OI versions delivered with a roof can be used outdoors. In all cases, provide the ducts, connection accessories, heater antifreeze protection and antivibration equipment. In heavy snowfall zones, an additional protection must be provided for. It is important to provide enough space (Z minimum) to allow opening the doors, commissioning and main- tenance (filters, fans, heat exchanger). Do not position the unit against a wall to avoid the transmission of structurally borne noise. Size Z (mm) 200 mm 700/1300 1450 1900...
Page 24
RHE 700 / 1300 / 1900/ 2500 Dimensions (mm) RHE Sizes 700/1300 HD 1308,5 1900 HD 1458,5 2500 HD 1558,5 700/1300 VD 1285 1900 VD 1490 2500 VD 1740 RHE 3500 / 4500 Détail Y Ø11 Dimensions (mm) Sizes 3500/4500 HD 1558,5 1010 702,2...
Page 25
RHE 6000 / 8000 / 10000 On size 6000 - 8000 - 10000, units are delivered with frame in galvanized steel 3mm thickness, 100mm height, with assembling system between 2 modules, fixing holes for antivibration pads or adjustable feets. With this frame system, the unit could be lift with a crane after assembling the unit on the floor. Dimensions (mm) Sizes 6000 HD 1968 1868 919,4 824,6 1100 8000 HD 2108 2008 999,4 884,6 1350 1220 1090 10000 HD 2408 2308 1149,4 1034,6 1520 1390 1260 RHE 15000 Dimensions (mm) Size 15000 3322...
On the units of size 6000 - 8000 and 10000, a door handrail is install on the controler part. It allows the locking of the door in the open position. RHE 15000 are equipped with doors or half-doors mounted on hinges, closed by locks, on the front and back of the unit. RHE 15000 Without coil or electric heater With water coil Half door Door Half door Door Porte Demi-porte Porte Demi-porte 3.6 Assembly of the units delivered in two parts The RHE sizes 6000, 8000, 10000 and 15000 are delivered in two parts to facilitate the travel up to the instal- lation site.
Page 28
The units size 15000 are delivered with bumpers to prevent damage to the unit during transport and its handling. Once the unit is positioned, the bumpers must be removed, especially those at the junction of modules • On the first part, fix on both side the junction elements without fully tighten the junction strengthening elements. Hole on the direction of the floor • Move closer as much as possible to both modules ; fix the junction elements on the second module loosely. Finalize the junction with the tensioner screw. ENGLISH 28/100 NT-51897201-RHE-ETD2-AN-230918...
Page 29
• Once the two modules are edge to edge, finalize the assembly inside the modules using 4 screws (6 from from the size 10000 and 15000) M12x120 supplied (key size 18). The locations are spread on the 4 internal angles (+ 2 points in the middle from size 10000/15000) on each side of the box equip with the controler. Before tightening, put a little grease on the screw. Check that the 2 modules are correct nested. Tighten all the screws including those of the joint reinforcements. • Connect the fast electrical connector as shown : 1 - Plug fan electrical power. 2 - Heat exchanger electrical power.
3.7 Assembly of the mixing and recycling box The unit can be equipped with mixing box (MIB 0-10V) or recycling box (MIB ON/OFF), connection accor- ding the below procedure : Size 700 to 4500 • Move closer the 2 modules by taking care to • Screw 2 modules together with 10 auto-drills align the round cuts on the feet support. screws delivered with the box Size 6000 to 10000 • Move closer the 2 modules by taking care to • Screw 2 modules together with the 6 M8 align the cuts of the box with the inserts of screws delivered with the unit.
Roof assembly between a RHE 15000 HD OI and a MIB 0-10V / MIB ON/OFF On the HD OI models of sizes 15000, the roof is pre-assembled in the factory on each unit's modules and on the MIB HD OI mixing / recycling box. • Remove the end roof of the heat exchanger module from the unit. • Assemble the unit and mixing box assembly • Install and fix the junction roof between the unit and the box. HYDRAULIC AND FLUID CONNECTION 4.1 Water coils connection The unit’s hydraulic data are specific to your installation and are deter- mined by the computer selection : Water pressure drop / Waterflow. Refer to the selection to size the network, accessories, pump, etc. The pipe connection to the coil must not impose mechanical, vibrational or thermal (expansion) stresses on the coil. The coils are delivered end-threaded.
Page 32
504423-Etiquette-Marquage-batteries-eau-190114 2 modèles - Format 50 x 50 mm On size 15000, the water pipes are connected on the front, outside the unit. Pantone 108 Noir 100% Water sortie d'eau output Water output Water input Water entrée input d'eau Condensates drain (reversible water coil DFR version HD only) The installed coil is equipped with a droplet separator and a condensate dip tray made of stainless steel welded in the corners.
4.2 Valves connection Motorized 3-way valves are not delivered mounted. They are proposed as accessories. Respect the positioning of the mixing valve on the network and the water inlet and outlet directions. Electric connection on the RHE box: see subsection "Input – output tables (terminal block / signal / variable / function)", page 42 Unit with hot and cold water up to size 10000. Cold water Hot water Unit with hot water coil and / or cold water coil from size 15000. Connection on the main face of the unit. Provide sufficient space to allow the opening of the door for main- tenance ENGLISH 33/100 NT-51897201-RHE-ETD2-AN-230918...
Check that the fan motors are not accessible from the connection taps, provide a screened air intake or a sufficient length of duct. Respect a minimum distance of 8 m between the fresh air intake and the discharge. Place the fresh air intake far from any specific pollution. 5.2 Accessories connection Electrical connection on the RHE cabinet control: see "6.6 External components connection drawings (examples)", page 44. 5.2.1 Dampers When the unit is equipped with a water coil it is recommended to provide for an antifreeze protection dam- per on the fresh air network. A second damper should be mounted on the extraction network to isolate the unit. Airtight dampers for unit up to size 4500 – circular air duct connection Size Code Designation...
Page 36
5.2.2 Rain protection canopy Rain protection canopy for units up to size 10000 The outside units until the size 4500 can be equipped with standard accessories for circular ducts, type APC for the exhaust air and outdoor air inlet protection canopy. For the sizes 6000, 8000 and 10000 with rectangular air connection, exhaust air and outdoor air protection canopy are specific. Dimensions (mm) Type Designation APPR 6000 Exhaust air protection canopy RHE 6000 1065 APPR 8000 Exhaust air protection canopy RHE 8000 1265 APPR 10000 Exhaust air protection canopy RHE 10000 1465 APPA 6000 Outdoor air protection canopy RHE 6000 1065...
Page 37
Installation APPA-APPR up to size 15000 (Screws included) APPR APPA 2 HM8x20 2 HM8x20 APPA / APPR specific mounting for size 15000 Mounting of the support rails Installation of the peripheral seal Remove the front grids using 6 HM6x20 screws (same phase 2 of the other sizes) Installation of the 1st module Fix the 2nd module by following the Install the front grids thanks to the rail upper, fix it with...
5.2.3 Sensors Electric connection on the RHE box: see subsection "6.6 External components connection drawings (examples)", page 44. For an operation at constant pressure, it is necessary to install a pressure probe (Accessory) in the supply duct at a minimum distance of twice the connection’s diameter. 2xD mini Recommended pressure sensor : Application Code Designation Description Pressure transmitter in box 0 to 500 Pa/ Output Signal 0,5/ 4,5 Vdc RHE 700/1300 132146 SPRD-010B 500 Nominal voltage 12 up to 24 V dc All sizes except Pressure transmitter in box 0 to 800 Pa/ Output Signal 0,5/ 4,5 Vdc SPRD-010B 800 132105 700/1300 Nominal voltage 12 up to 24 V dc SPRD Accessoiry 132143 KTPR Kit of 2 pressure taps + screws + 2 m Translucid tube Air quality probe, measurement of CO2 - Operation in VAV (Variable Flow Rate) Electric connection on the RHE box: see subsection "6.6 External components connection drawings...
6.2 Electrical features Global unit Capacity of the power connection terminal strip : 10 mm², tightening torque: 2.5Nm. Units up to size 15000 are fitted with a proximity disconnect switch. Only size 15000 DI units, fitted with electric heaters, have a disconnect switch dedicated to supplying power to the electric heater. Heat exchanger rotor Complet unit to be multiplied by 2*...
Data of electric heaters with lower powers - Option Sizes Voltage (V) Nominal power (W) Current (A) Sizes Voltage (V) Nominal power (W) Current (A) 1 phase 1300 3 phase 230V 8000 400V 1 phase 1900 230V 3 phase 10000 400V 2500 3 phase 400V...
In the case of external mounting of the RHE HD OI, you can also leave it inside in the housing of the elec- trical box. Once the settings have been made, the remote control can be disconnected. Placement of the support and the remote control : Mounting bracket ETD2 remote control Câble (code 132389) Régulateur CORRIGO Télécommande ETD2 CORRIGO controller Ext. ETD2 remote control Disp. NOIR 1 (+24V) Black BLANC 2 (N) white 3 (A) Yellow JAUNE MARRON 4 (B) Brown...
Page 42
Power connection Actuators power supply Main electric power Auxilary power supply supply to the unit (Customer) (Customer) (coming from unit) Exhaust air fan motor 2T1 4T2 6T3 Distribution of internal power supplies done in factory Bat1 Bat1 Bat1 outside unit Supply air Electrical Heat...
Page 43
Analogic input (sensor) Terminals Signal Variable Name Description PT1000 AI 1 Supply Supply air sensor install on supply air duct connection PT1000 AI 2 Extract Extract air sensor install on extract air duct connection PT1000 AI 3 Frost protection Frost protection sensor install on water coil PT1000 AI 4 Outdoor...
Logic output (actuator and info report) : les contacts sont libres de potentiel Switch Signal Variable Description KM1 : 12-11-14 Control output for the fresh air register servo motor Available : - either for use of a 230 V register with a control by 230 V Supply air fan signal (on terminal) and a 230V power supply (L-N) - or by a dry contact for a general usage N-L-on 230V KM2 : Total alarm Total alarm status 12-11-14 Exchanger Start control of the heat exchanger Free cooling by night KM4 :...
Page 45
Case of a reversible water coil DFR (delivered mounted – cold or hot) + dampers (accessories) Out door air 3 way valve actuator Frost protection Change over damper on hot/cold water coil sensor thermostat actuator with security Supply air spring return T°...
Page 46
Case of a PWM controlled DI electric heater (delivered mounted) + dampers (accessories) Out door air Electrical heater damper battery control by Over heat protection actuator PWM signal control thermostats with security signal spring return type LF 230S Electrical power Supply air T°...
Page 47
Case of a register with 24V actuator (accessories) 21 11 24 14 Fdc A and B Actuator with spring return for fresh air damper type LF 24 S blowing step (antifreeze) Case of DX coil with DX group equiped with AHU kit Control unit DX-Kit CTA Defrost DX group...
Page 48
Case of operation in constant airflow (CAV) – controlled by optical sensor or box 0 / PV / GV (accessories) Warning : All the controls must be made with potential free contacts Variant : ON / OFF Fan control 0-PV-GV Presence detector Switch board into the unit Case of operation in variable airflow (VAV) – CO2 probe (accessory) The unit is preprogrammed for the usage of a CO2 measurement probe with a range 0 – 2000 ppm and a signal of 0 –...
Page 49
Case of operation in constant pressure (COP) – pressure probe at supply (accessory) The unit is preprogrammed for the usage of a pressure probe with a range of 0 – 800 Pa (0-500Pa on size 700/1300) and a signal of 0.5 – 4.5 Vdc. Another probe can be used by means of an advanced parameter setting. ON/OFF Pressure transmitter 0.5-4.5V Switch board into the unit ENGLISH 49/100 NT-51897201-RHE-ETD2-AN-230918...
Page 50
Electric wiring mixing box MIB 0-10V Internal wiring from the connection box to the damper actuators and the CO2 sensor are made into the ma- nufacture. Only the connection between the unit and the mixing box has to be done on the installation site. CAD O INTEGRAL 21 11 24 14 230 V Night cooling switch on N PH Supply air (open fresh fan switch air damper) 22 12 22 12 Connection box into the CMOI 24 V TM40/24 F1 F2...
Page 51
Electric wiring recycling box MIB ON/OFF Internal wiring from the connection box to the damper actuatore are made into the manufacture. Only the connection between the unit and the mixing box has to be done on the installation site. CAD O INTEGRAL 21 11 24 14 230 V Outdoor N PH Supply air air damper fan switch 22 12 22 12 Connexion box into the CREI 24 V F1 F2 24V CO2Com TM40/24 230 V On/O actuator...
CONTROL - FUNCTIONAL ANALYSIS 7.1 Main elements of control CORRIGO CONTROL D DI DC DFR DC/DF DX MAIN COMPONENTS Internal electrical box - composition : - Main power connection switch / safety circuit breaker - Controller and terminal strip integrated into the unit, easy access main side FUNCTIONS Air flow control - Constant or fixed air flow (CAV mode), up to 3 different flow setpoints - Variable flow according to an external 0-10V signal or from the remote control (VAV mode)
7.2 Airflow control Fan Airflow management can be carried out according to 3 control modes: CAV, VAV, COP. Whatever mode is selected, each fan suction pavilion (extraction and supply) is equipped with a pressure tap and connected to a pressure sensor. The flow rates resulting from the pressure measurements are calculated by the regulator, according to a coefficient K specific to each fan. • The DO1 digital output corresponds to the supply fan running command and can be used for acces- sory operation linked to the operating status of the fans (for example starting a DX unit if the supply fan is running). • Analog output AO4 corresponds to the 0-10V control signal sent to the supply fan. •...
Page 54
Independently, a BOOST (extra m /h) airflow can be programmed in the form of a fixed airflow for extrac- tion and supply. • Digital input DI5 = Start/stop. • Digital input DI6 = forcing GV - forcing of the max flow rate set for the max signal. • BOOST (extra m3/h) selection can be done from the remote control. To perform a BOOST forcing via a digital input, it is necessary to reparametrize a digital input (DI1 for example) and assign it the "Additional alarm 7" function. When closing this digital input, an “External BOOST forcing” message will appear on the main screen. • A fourth flow set point for "night free cooling” overventilation can be entered via the remote control, in the form of an offset of the high-speed flow GV (see free cooling for operation) 7.2.3 Operation at constant pressure COP on extraction or supply mode Recommended mode in multi-zone configuration associated with terminal airflow modulation systems.
7.3 Temperature control 7.3.1 General principle The temperature set point as well as the temperature regulation mode are entered via the touch screen. The supply or ambient temperature is maintained at the set value by acting on the controller outputs (hea- ting/exchange/cooling), a single PI loop is used. The exchanger is considered to be the first potential source of heat or cooling even before the batteries. For RHE fitted with a standard rotary heat exchanger (1 speed), the wheel is controlled in binary mode (on or off). For RHE equipped with a sorption exchanger, the rotation speed is variable, proportional to a 0 - 10V si- gnal. By varying the speed of rotation, it is therefore possible to modify the efficiency of the exchanger to reach a given temperature set point. Échangeur rotatif mono vitesse Échangeur rotatif à vitesse variable Single-speed rotary heat exchanger Rotary exchanger with variable speed Froid Froid Chaud Warm...
Page 56
7.3.2 Temperature control modes The temperature regulation can be carried out according to the following 4 modes: • Supply air control at constant temperature The supply air temperature is maintained at the set value by acting on the exchanger outputs, hot output and cold output. The setpoint is adjusted using the display and number keys. The user set point for the mode is entered in °C in the settings menu. • Supply air control at constant temperature with outdoor temperature compensation The supply air temperature setpoint is adjusted according to the outside temperature according to a compensation law made up of 8 factory preset setpoints. The supply temperature is maintained at the set value by acting on the exchanger, internal coil, exchan- ger, external coil outputs.
7.4 Special case: temperature control with DX direct expansion coil General: • A communication box, “AHU kit”, must be provided by the unit's supplier. He makes the communica- tion possible between the direct expansion group and the CORRIGO regulator. • The direct expansion coil regulation mode is selected on the touch control. • Temperature regulation by DX group. • The DX group controls the regulation temperature using its own sensors. •...
Page 58
If ALL the conditions are fulfilled, the cooling by overventilation starts. It remains on for 3 minutes to ensure that the temperature measurements are representative (by creating air movement in the ducts). After three minutes, the controller checks for shutdown conditions. Stop conditions: • The outside temperature is above 18°C or below 10°C (risk of condensation station). • The return temperature is below 18°C • The time programs (timer) for normal speed, normal override and control are “On”. • It is past 7:00 in the morning. If at least one of these conditions is fulfilled after the first three minutes of operation, then the overventila- tion is stopped. When the over-ventilation function is active, the fans run: • In CAV at the speed set for high speed(GV) + an offset in m /h (settings entered in the CAV settings menu).
To be able to benefit from the nocturnal overventilation, it is necessary to force the opening of the modula- tion registers, wiring principle below: 230V~ 230V~ TRAFO 0 24~ CAPI 0 24~ 0 24~ Registre LM24-A-SR Information Information register overventilation LM24-A-SR Surventilation 230V~ Capteur Optique Optical sensor N L L D1D2 CAPI 230V~ damper Registre 230V~ LM230A, RMME... LM230A, RMME... 7.6 Hot water coil frost protection The hot water or reversible coils integrated in our units have a temperature sensor "Antifreeze protection sensor"...
7.7 Control of the fresh air damper When a damper is provided on the fresh air and connected to the regulation, its operation is explained in the table below: Unit operating mode Digital output DO 1 Damper status Stop Open (=0) Damper closed Start sequence Closed (=1) Open at start of start sequence Standard Closed (=1) Damper open Free cooling Closed (=1) Damper open Night overventilation Closed (=1) Ditto start-up sequence if unit stopped...
7.9 MIB 0-10V – Mixing box The mixing box is mainly used in mixed ventilation and heating installations. It will make it possible to operate in recycling mode during periods of non-occupation and in all fresh air during maximum occupancy of the premises. Operating principle: The mixing box is fitted with a CO2 sensor (SCO2 A-010 400-1100ppm) which continuously measures the level of CO2 contained in the extracted air, it sends a proportional signal to the damper servomotors to open them more or less depending on the indoor air quality. Unit shut down (antifreeze protection, system shutdown, etc. Unité à l'arrêt ( protection antigel, arrêt système...) SCO2 When the unit is stopped, the extraction and fresh air dampers are closed, the mixing damper is open.
7.10 MIB ON/OFF - Recycling box The recycling box is used when it is desired to recycle the air extracted over a time slot when it is not oc- cupied, to allow for example a rise in temperature of the room. Operating principle: Timer programming of recycling hours is to be carried out in time slot 5. This time slot, which does not have priority, is to be programmed outside the other time slots (normal speed or reduced speed). Programming example: Time program Programmation Marche Start vitesse normale normal speed Arrêt Stop Programmation Time program Marche Start vitesse réduite reduce speed...
Page 63
A pressure regulator varies the position of a dam- Regulator Régulateur per to increase the vacuum in the return network. It will maintain a minimum difference of 10Pa at the level of the exchanger, which will force the es- cape of fresh air towards the stale air network and (Extract Air) (Extract air) not the other way around. (Exhaust Air) (Exhaust air) -250Pa -310Pa +30Pa (Supply Air) (Supply air) (Outdoor Air) (Outdoor air) +300Pa +400Pa Installation :...
7.12 Input for external fire signal The controler is configured to receive a fire contact. If the fire input is activated (DI7), the panel is stopped. When the control panel has been stopped by the fire input, it can only be restarted after an acknowledg- ment of the alarm. 7.13 Clock and time programming From the clock menu, it is possible to update the date, the time, as well as the activation of the automatic winter/summer time change. It is possible to set different time programs for each day of the week, plus a specific time program for ho- lidays and vacations. Time slots (time prg 5) can be programmed for air recycling if the unit is equipped with a recycling box. It is possible to define up to 24 holiday periods. A vacation period can last from 1 to 365 days. The time programs for holidays have priority over the others. Clock setting: Only the operating ranges are programmed (outside these ranges the unit is stopped). The installer can define 3 operating ranges: reduced speed ECO, high speed GV, boost.
USE OF REMOTE CONTROL ETD2 8.1 Presentation of the ETD2 touch display Welcome screen This window displays strictly essential information on the state of the machine. It is possible to switch to the other available windows by pressing the menu window icon . If a menu includes several pages, up and down scroll windows appear on the right of the screen, al- lowing you to move from one window to another. To scroll through the pages of the different menus, use the up/down arrow keys The back arrow allows you to return directly to the main menu with several windows. The remote control goes to sleep (screen off) after two minutes of inactivity, by pressing anywhere on the screen, it is automatically reactivated. The temperature icon allows the temperature to be increased or decreased by +/-3 C° compared to the main set point. If there are alarms, an orange bell appears in the upper band of the screen. Pressing the bell allows direct access to the alarm message. Authority level Reporting of active alarms Date and time...
Main menu In the menu window, you can access the following functions: Synoptic Temperatures Fan stop and running speeds Screen display settings Alarms Password with 3 authority levels: User, Installer or Factory Depending on the level of authority entered, padlocks present on the icons indicate the impossibility of accessing the content. Menu accessible with installer or factory password: Settings > with installer password Clock > with installer password Communication >...
8.3 Main settings Selection of speeds according to operating mode CAV, constant flow, VAV, variable flow, COP, constant pressure Press the main menu icon CAV MENU Allows: • to stop the unit > STOP • to manually select one of the 3 speeds parameters > ECO/GV/BOOST •...
Page 68
Screen settings Press the main menu icon This menu is used to configure the characteristics of the screen and gives access to: • Choice of language: among 4 languages French / English / German / Spanish It also indicates the versions of the software used in the display and in the controller, the VTC (the application) loaded and the serial number of the controller. Alarm settings Press the main menu icon Allows you to view active alarms, acknowledge them or block them if necessary.
To identify yourself, press the icon corresponding to the required level. Enter the password using the numeric window. Once connected, it is possible to change the password or to disconnect from the level to return to the User level. After a certain period of inactivity, the disconnection is done automatically. 8.4 Specific configuration of the ventilation modes CAV / VAV / COP Press the main menu icon > Installer level Access to this menu is used to modify the factory settings presented in § "10.1 AHU factory settings", page Choice of fan regulation mode: •...
Page 70
If Variable flow - VAV selected On this page it is possible to enter: • The range of use of the connected air quality sensor Vmin and Vmax • The desired values in m³/h for the mini signal Vmin ECO - for the normal Vmax GV and the values Extra m³/h BOOST, extraction and supply. Example of use: connection of a CO2 sensor with a range of 0-2000ppm (0-10V). For use in the 400-1400ppm range, you must select: •...
Page 71
Each RHE fan is equipped with a differential pressure sensor, connected to the regulation. • Sizes 700 to 1300 = 0-500 Pa pressure sensor and 0.5 - 4.5 Vdc signal. • Sizes 1900 to 10000 = 0-800 Pa pressure sensor and 0.5 -4.5 Vdc signal. • Size 15000 = 0-3000 Pa pressure sensor and 0.5 - 4.5Vdc signal. The pressure sensor measures the difference in static pressure before the suction horn and at the horn. The airflow can be calculated according to the following equation: • Qv = K x √ΔPa Qv flow in m /h. The K factor takes into account the specific characteristics of each fan. Size RHE K factor Pa-sensor...
Page 72
• Activate or deactivate the free cooling over-ventilation function and set the time range during which this function will be active. • Enter the setpoint offset in Pa (on the normal speed GV) which will be added to the pressure setpoint during overventilation. To allow the display of airflows and the control of a fan according to the airflow of the other fan (COP with 1 single sensor), it is necessary to characterize: • The factor K • The scale of the pressure sensors used to display the flow rates • Configuration of the pressure sensor used for duct measurement • Setting the type of signal emitted by the duct pressure sensor • Characteristics of the proportional bands and integral time of the pressure regulation loop (800 Pa 8 seconds) and flow rate for the slave fan (see CAV – VAV mode table). 8.4.3 Settings common to all fan operating modes Press the main menu icon > Installer level This screen is used to configure the reaction of the fans when the "fire" digital input is activated.
Page 73
This screen is used to set the temperature regulation mode that will be used by the air handling unit. This window allows you to configure the type of post- processing installed. By pressing the icons, it is possible to define the desired configuration: • No electric coil post-heating coil • Hot water coil • Reversible water coil • Reversible DX coil This window is used to configure the type of 2nd battery installed. This window allows you to declare a recycling box. The hours of operation must be set on timer program 5. ENGLISH 73/100 NT-51897201-RHE-ETD2-AN-230918...
8.5 Time schedule Press the main menu icon > Installer level This menu is used to define: • Date and time • Time programs for unit operation • Automatic Winter/Summer time change Date / time menu Allows the regulation to be set to the correct time and date. It is possible to automatically activate summer/winter time changes. If unit configured in CAV: If unit configured in VAV: Time program settings menu A Summary key allows viewing of all the configured time slots.
Page 75
It is possible to configure up to 4 time programs per day of the week + 1 Holiday day If the unit has been configured in CAV it is possible to select: • STOP / ECO / GV / BOOST If the unit has been configured in VAV it is possible to select: • STOP / AUTO / GV / BOOST If the unit has been configured in COP , it is possible to select: •...
8.6 Setting up the communication protocol Press the main menu icon > Installer level This menu contains the configuration parameters for the MODBUS RS485 and MODBUS IP – BACnet MSTP – BACnet IP protocols. Communication to RS485 supervision must be done on communication port N°. 1. Allows selection of the desired protocol using the arrows: • Modbus • BACnet MS/TP • Modbus IP • BACnet IP Modbus This screen enables or disables the Modbus on port 1 RS485 • Address : Represents the address you wish to assign to the unit (by default the units are at address 1) •...
TCP/IP This screen allows you to enter: • IP address • Subnet mask • Default gateway • DNS server Corresponding to the characteristics of the fixed IP that you assign to the unit and to activate the CLOUDIGO if the offer has been subscribed. Contact your network administrator for the values to use for these settings 8.7 Save and restore Press the main menu icon >...
To recall the last saved configuration: • Press the corresponding icon • A pop-up window appears asking you to validate your request. • A new window informs you when the operation is complete. 8.8 Expert level configuration Press the main menu icon > Expert level: factory password transmitted only by our after-sales service This menu is used to view the status of the inputs/ outputs, to force their values, to modify their assignments and their reactions.
Page 79
Analog outputs - vizualisation and modification Press the value to modify, a pop-up window appears. The arrows allow you to select between: • Value provided by the controller • Force a manual set point value • Cut output As long as the value is forced, the hand next to the value appears in red. Digital outputs - vizualisation and modification Press the value to modify, a pop-up window appears. The arrows allow you to select between: • Value provided by the controller • Force a manual set point value As long as the value is forced, the hand next to the value appears in red. ENGLISH 79/100 NT-51897201-RHE-ETD2-AN-230918...
Page 80
8.8.2 Inputs / outputs - Allocation of new functions Press the advanced settings menu icon The advanced settings menu is broken down into 2 submenus: • I/O functions (inputs / outputs) • Control functions I/O function (inputs / outputs) This menu is used to assign or reassign a function to the inputs/outputs. Analog inputs To modify the assigned function, press the value to be modified, a pop-up window will open.
Page 81
8.8.3 Control functions Press the advanced settings menu icon ENGLISH 81/100 NT-51897201-RHE-ETD2-AN-230918...
COMMUNICATION BMS 9.1 Communication in Modbus protocol MODBUS RTU on port 1 - RS 485 The CORRIGO controller has 2 RS485 communication ports (to be used with an STP cable), port 1 is by default dedicated to Modbus RTU communication CORRIGO (Modbus RTU) MODBUS IP on TCP/IP port The CORRIGO controller has a TCP/IP communication port (RJ45 socket) allowing TCP/IP connection to a TCP/IP network. This port is by default dedicated to Modbus IP communication. Simplified MODBUS table The simplified Modbus list below includes the data most commonly used in supervision.
Page 83
Type Register Read/ Accepted Function Description Write values Manual control of the unit Pace in CAV Holding Register 611 0=Off, 1=reduce speed, 2=Normal speed, 3=Auto according 0,1, 2, 3 or 4 mode timer, 4 =Extra speed (Boost) Manual control of the unit Holding 0,1, 2, 3, 4 0=Off, 1=Manual, 2=Auto according external signal, 3=Extra Pace in VAV Register or 5 speed (Boost), 4=auto according timer, 5= Grande vitesse...
Read/ Accepted Function Type Register Description Write values DISPLAY OF ALARMS Input Summary of Presences of alarm Status 0 or 1 alarms 0=Normal 1=alarm Register Input Alarm filter guard Filter alarm Status 0 or 1 0=Normal 1=alarm Register Input Supply air fan alarm Status 0 or 1 0=Normal 1=alarm Register...
BACnet IP on TCP/IP port TCP/IP The CORRIGO controller has a TCP/IP communication port (RJ45 socket) allowing connection to a TCP/IP network. This port must be configured to be able to communicate in BACnet IP (BACnet TCP/IP ou Modbus TCP/IP) It is possible to give a fixed IP address to the controller (procedure identical to Modbus IP). For the various information reported by the Bacnet, contact S&P Technical Assistance Service. 10.
10.3 Recommendations See § "1.2 Safety instructions", page 4. The commissioning and setting of the regulation must be carried out by a qualified person. In France this service can be provided by VIM and its qualified service providers. Contact sav@vim.fr. This service can only take place once the installation, the electrical connection operations, aeraulics and hydraulics carried out. For the commissioning and configuration of the CTA, bring the necessary data, flow rates, pres- sures, temperatures, desired operating mode and installation diagrams. • Before connecting the ducts, check that the 4 labels (below) stuck on the CTA correspond to the diagrams in "2.2.1 General description", page 6.
11. MAINTENANCE - REPLACEMENT OF PARTS - ALARMS 11.1 Safety instructions General: • Meaning of the danger labels present on the access doors: Live equipment Rotating machine Potentially flammable dust filters • Put on appropriate PPE (Personal Protective Equipment) before any intervention. • Before installing the air handling unit, ensure that the support and location are sufficiently strong enough to support the weight of the unit and accessories. •...
Organ At startup At least every 6 months Check dirt + clean if necessary. Check Water Coil Check the tightness for leaks / tighten connections Droplet separator To clean Condensate collection tray Check for tightness/ flow To clean Check the electrical / aeraulic Pressure switches Check function connections...
The clogging of the filters is controlled by differential pressure switches with information feedback on regulation. 2x0.75mm tube "rilsan" Factory settings: DP1 OUTDOOR AIR DP2 EXTRACT AIR Sizes Adjustment in Pa if Adjustment in Pa if Adjustment in Pa if Adjustment in Pa if G4+F7 G4+F9...
Page 90
Belt replacement: Unit sizes 700 to 8000 Units of sizes 700 to 8000 are equipped with a tubular type round belt. A replacement belt is always planned around the interchange. Replacement belt Main belt Access hatch Exchanger pulley Exchanger motor To use the replacement belt: • Remove the old belt • Pull on the exchanger to get it out of about twenty centimeters • Pass one of the hands through the access hatch and the other from below the exchanger to pull on the replacement belt and the put in the groove of the exchanger pulley • Push back the exchanger Units larger than size 8000 Sizes larger than size 8000 are supplied with an SPA-type replacement strap not fitted around the inter- change.
Throat side Outer side • Replace the belt inside the driving pulley • Adjust the tension of the belt using themotor carriage tension screw. 11.5 Fan maintenance / replacement After a long period of use, dust can settle on the fan, a dust removal is then necessary. To extract the fans: • Open the access doors. • Disconnect the power and control connection plugs on the side. • Disconnect the pressure tap. •...
11.6 Maintenance / Reset / Replacement of electric heater Electric heater maintenance Before the heating season, dust the resistors with compressed air or using a vacuum cleaner and a soft brush. • Open the access doors. • Visually check the condition of the components and tighten the connections. •...
On 6000 / 8000 / 10000 units, the resetting of the manual electric heater safety thermostat is done inside of the unit according to the following steps: Remove the filter on the extraction Remove the rubber washer Slide your finger to reset side On 15000 units, resetting of the manual electric heater safety thermostat is done inside the unit on the front side of the heater.
11.8 CORRIGO controler - Reset and replace battery Resetting the CORRIGO regulator from the ETD2 remote control In some cases, after multiple settings or following a malfunction, it is sometimes necessary to reset the pro- grammer. Perform this operation only after having been instructed to do so by the VIM after-sales service.
The screen used to choose the program to load into the controller appears: • Select the RHE program for units up to size 10000 and RHE GT for size 15000. • Wait for the application to load • The welcome screen appears • Set the disconnector to "OFF" and open the door. • Reconnect the connectors to the CORRIGO then close the unit.
Address Text of alarm Description Malfonction SAF Malfunction supply air fan Malfunction EAF Malfunction extract air fan Filter guard 1 Filter guard 1 - check the filter (clean or replace) Fire alarm Fire alarm enable Electric heating is overheated Electric heating is overheated Frost risk Water temperature on water coil low (<12°C fixed value) Low frost guard temp Water temperature on water coil too low (7) Sensor error outdoor temp Sensor error outdoor temp Rotation sentinel exchanger Rotation sentinel exchanger...
Code Type Name R153142002 Standard rotary exchanger with motor ENOI RHE 15000 D2050 Tri 400V R153533006 Sorption rotary exchanger with motor ESOI RHE 700/1300 D540 200 Mono 230V R153534206 Sorption rotary exchanger with motor ESOI RHE 1900 D650 200 Mono 230V R153531506 Sorption rotary exchanger with motor ESOI RHE 2500 D800 200 Tri 400V R153530006 Sorption rotary exchanger with motor...
Page 99
ENGLISH 99/100 NT-51897201-RHE-ETD2-AN-230918...
Page 100
S&P SISTEMAS DE VENTILACIÓN, S.L.U. C. Llevant, 4 Polígono Industrial Llevant 08150 Parets del Vallès Barcelona - España Tel. +34 93 571 93 00 Fax +34 93 571 93 01 www.solerpalau.com NT-51897201-RHE-ETD2-AN-230918...