Stepper valve driver

Advertisement

DIP switch
The driver has one 8-position DIP switch per stepper motor output.
Note: DIP switch must be changed during POWER OFF only, Any change during power on will not take e ect until driver
switches o .
Valve selection
Con gure Valve type by selecting DIP switch as shown in table below (green denotes ON).
Group
Valve
No Valve (Default)
A
ETS 12C, ETS 24C, ETS 25C, ETS 50C, ETS 100C, KVS 2C,
B
KVS 3C, KVS 5C
ETS 5M Unipolar
C
ETS 6, UKV, UKV-J
D
ETS12.5, ETS 25, ETS 50, KVS15
E
ETS 100
F
ETS 250, ETS 400, KVS 42
G
Manifold Valves (ETS 500P, ETS 800P)
H
JKV
I
CCMT 2, CCMT4, CCMT8
J
CCMT 16
K
CCMT 24
L
CCMT30
M
CCMT 42
N
CCM 10, CCM 20, CCM 30
O
CCM 40
P
CTR 20
Q
CCMT 3L, CCMT 5L, CCMT 8L, CCMT 10L
R
ETS 175L, ETS 250L, ETS 400L
S
ETS 175L, ETS 250L, ETS 400L
T
oil free and high temperature
ETS 500L
V
ETS 500L oil free and high temperature
X
ETS 8M Bipolar
Y
ETS 8M Unipolar
Z
Note:
When using Manifold Valves (ETS 500P ad ETS 800P).
Dip switch of driver 1 should be selected to ETS 250/ETS 400.
Dip switch of driver 2 should be selected to Manifold Valves (ETS 500P ad ETS 800P).
See example image of Dip Switch setting
5 | AN375548103097en-000206
DIP Switch
1
ETS 12C with 0-5 V AI input
ETS 12C selected
2
3
4
5
ETS 12C with 0-10 V AI input
0-5 V AI input
© Danfoss | Climate Solutions | 2024.03
6
7
8