hit counter script
Download Print this page
Honeywell GENT S4-34410 Data And Installation
Honeywell GENT S4-34410 Data And Installation

Honeywell GENT S4-34410 Data And Installation

Interface modules for vigilon
Hide thumbs Also See for GENT S4-34410:

Advertisement

Quick Links

Data and Installation
Interface Modules for Vigilon
Low voltage (LV) Input/Output
S4-34410*
S4 1-Input Interface
Module
(low voltage)
1- End-of-line
Capacitor unit
2- 10K Resistors
These instructions cover the above
LPCB approved interface modules
and accessories. These interface
modules are designed for use with
Vigilon and 34000 fire alarm control
panel. Each module includes a loop
042ba
isolator for device isolation. Each interface module
use one of 207 available device addresses on a loop
and responds to regular polls from the control panel
reporting the type of device and the status
(open/normal/short) of its supervised input circuit(s).
Features
¨
Analogue addressable communications
¨
Built-in type identification automatically identifies
these devices to the control panel
¨
Reliable communication technique with high noise
immunity
¨
Soft or SAFE addressing
¨
Common mounting options including surface
mount, panel mount and DIN rail mount
¨
Dual-colour LEDs
¨
Plug-in terminal connections for ease of wiring
¨
EN54-17:2005 and EN54-18:2005
Cables
The cables recommended for wiring the input / output
lines are the same as those used for loop wiring, see
instructions supplied with the fire control panel.
4188-873_issue 5_Pt.1_09/10_S4 LV Interfaces
www.acornfiresecurity.com
S4-34420*
S4-34450*
S4 1-Output &
S4 4-Input / Output
1-Input Interface
Interface Module
Module (low voltage)
(low voltage)
Output
2- 10K Resistors
1- End-of-line
Capacitor unit
8- 10K Resistors
* - LPCB approved
www.acornfiresecurity.com
S4-34490*
Plastic box
1- Allen key
2 - M4 Posi Pan Screws
7 - Hole plugs
S4-34492*
Metal box
Installation
The S4 interface modules can be mounted in
other equipment housings using the DIN rail
mount brackets (S4-34491). A module can also
be fitted into a plastic box (S4-34490) or metal
box (S4-34492). The boxes have cable
termination points on the enclosure for incoming
cables.
Module
Slide &
lock
DIN rail mount bracket
Allen
key
Door
Module
M4 Screws
Metal
backbox
Lid
7 usable cable entry points
by Honeywell
2 - M4 Screws
S4-34491
DIN rail mount
bracket
Connect to loop
cable screen
DIN rail
Hook and push
to lock
7 - top cable
62.5 62.5
entry points
Box
3 - box fixing points
(Includes 1-keyhole)
140
Module
M4 Screws
1

Advertisement

loading

Summary of Contents for Honeywell GENT S4-34410

  • Page 1 Data and Installation Interface Modules for Vigilon by Honeywell Low voltage (LV) Input/Output S4-34410* S4-34420* S4-34450* S4-34490* S4 1-Input Interface S4 1-Output & S4 4-Input / Output Plastic box Module 1-Input Interface Interface Module (low voltage) Module (low voltage)
  • Page 2 www.acornfiresecurity.com Data and Installation Interfaces (Low voltage) to minimise false alarms by suppressing a fire input Maximum cable usage per circuit for a period of time defined during commissioning. & The zone reset period can be extended to allow for different types of fire detectors.
  • Page 3 www.acornfiresecurity.com Interfaces (Low voltage) Data and Installation Wiring diagrams & The loop cable screen must be continued through each interface module. The loop, switch input, zone input and LED output cable screens where used must connect to an earth terminal. S4 1-Input module S4 4-Input/Output module connection details...
  • Page 4 S4-34450 0832-CPD-1411 Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes. Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK Website: www.gent.co.uk...
  • Page 5 Data and Installation by Honeywell Interface Module for Vigilon Medium Voltage (MV) Output S4-34411 Single Output Interface Module DIN rail mountable (Medium Voltage) S4-34415 Single Output Interface PCB with cover (Medium Voltage) in a metal box These instructions cover the...
  • Page 6 Do not dispose of with your normal household waste. Do not burn. Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes.
  • Page 7 Data and Installation S4 Mains Powered Interface by Honeywell (S4-34440-02 & S4-34440-12) Relative Humidity up to 95% (Non condensing) Temperature 5 - 45°C Ingress Protection IP31(estimated) Operating voltage 230V 50Hz +10% -6% Rated current 0.7A Input modes Input can be fault monitored,...
  • Page 8 www.acornfiresecurity.com Data and Installation S4 Mains powered interface unit EN54-17 : 2005 0.4A C max Features (section 4.8) S max ¨ data: Fail-safe operation 20mA L max A fail-safe operation is available on all sectored 0.1W SO max C max outputs, if loop communications are lost for a defined SO min duration then the sector outputs will be turned ON.
  • Page 9 www.acornfiresecurity.com S4 Mains powered interface unit Commissioning information Mains supply Installation The mains supply cable must be a standard fire resisting type and should meet PH30 classification, such as any The batteries are supplied in a separate pack. of the standard and enhanced loop cable. Requires a Spare Parts packages minimum conductor cross sectional area of 0.75mm Fuse 3.15A AS Ceramic...
  • Page 10 Do not burn. Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes.