Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 1. Application WAN / LAN Events printer Printer satellite Gateway Substation LAN C37.118 Station PDC RES670 RES670 IEC11000408_1_en.eps GUID-13F439FC-6AB6-4ED0-A629-EBC8F984B447 V1 EN Figure 1. PMUs in a substation RES 670 is a Phasor Measurement Unit that provides power...
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 2. Available functions Wide area measurement functions IEC 61850 ANSI Function description Phasor measurement unit RES670 PMUCONF Configuration parameters for IEEE1344 and C37.118 protocol PMUREPORT Protocol reporting via IEEE1344 and C37.118...
Page 6
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Control and monitoring functions IEC 61850 ANSI Function description Phasor measurement unit RES670 Control QCBAY Apparatus control LOCREM Handling of LRswitch positions LOCREMCTR LHMI control of PSTO SLGGIO Logic rotating switch for function selection and LHMI presentation...
Page 7
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 IEC 61850 ANSI Function description Phasor measurement unit RES670 BSStatReport Logical signal status report RANGE_XP Measured value expander block Metering PCGGIO Pulse-counter logic ETPMMTR Function for energy calculation and demand handling...
DOSOEMCD Denial of service, frame rate control for OEM port CD 3. Wide area measurement system • Data about the particular RES670 IED in the PMU synchrophasor streaming network. For example, IP address, Configuration parameters for IEEE1344 and C37.118 protocol id, communication port.
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 EF4PTOC (51N/67N) can be used as main protection for phase- Protocol reporting via IEEE 1344 and C37.118 PMUREPORT to-ground faults. The phasor measurement reporting block moves the phasor calculations into a C37.118 frame which contains data about...
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 There is also available one nondirectional 3I0 step and one 3V0 6. Frequency protection overvoltage tripping step. Underfrequency protection SAPTUF (81) Underfrequency occurs as a result of a lack of generation in the No specific sensitive current input is needed.SDEPSDE can be...
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 7. Multipurpose protection value of voltage without the presence of the negative-sequence current 3I General current and voltage protection CVGAPC The General current and voltage protection (CVGAPC) can be...
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 bring in commands from REMOTE (SCADA) to those parts of • PULSETIMER function block can be used, for example, for the logic configuration that do not need extensive command pulse extensions or limiting of operation of outputs, settable receiving functionality (for example, SCSWI).
Page 13
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Supervision of mA input signals Sequential of events DRPRDRE The main purpose of the function is to measure and process Continuous event-logging is useful for monitoring the system signals from different measuring transducers. Many devices...
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 The trip value recorder information is an integrated part of the generic communication I/O functions (MVGGIO) are provided disturbance record (Comtrade file). with measurement supervision functionality. All measured values can be supervised with four settable limits: low-low limit, Disturbance recorder DRPRDRE low limit, high limit and high-high limit.
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 • Status indication LEDs. according to GOOSE is part of the standard. Disturbance files • Alarm indication LEDs, which consist of 15 LEDs (6 red uploading is provided. and 9 yellow) with user printable label. All LEDs are DNP3.0 communication protocol...
Page 16
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 mA input module MIM GPS time synchronization module GTM The milli-ampere input module is used to interface transducer This module includes a GPS receiver used for time signals in the –20 to +20 mA range from for example OLTC synchronization.
Page 17
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Mounting alternatives See ordering for details about available mounting alternatives. • 19” rack mounting kit • Flush mounting kit with cut-out dimensions: – 1/2 case size (h) 10.01 inches (w) 8.27 inches –...
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 17. Connection diagrams Table 1. Designations for 1/1 x 19” casing with 2 TRM slots Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X131 IOM or MIM...
Page 20
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 1MRK002802-AB-11-670-1.2-PG-ANSI V1 EN Figure 6. Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, etc. and input contacts named XB to rear position X32, X42, etc.
Page 21
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 1MRK002802-AB-8-670-1.2-PG-ANSI V1 EN Figure 11. IED with basic functionality communication interfaces...
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 18. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified...
Page 23
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 4. TRM - Energizing quantities, rated values and limits for measuring transformer modules Quantity Rated value Nominal range Current = 1 or 5 A (0-1.8) × I at I = 1 A (0-1.6) ×...
Page 24
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Auxiliary DC voltage Table 7. PSM - Power supply module Quantity Rated value Nominal range Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL ± 20% EL = (90 - 250) V EL ±...
Page 25
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 9. BIM - Binary input module with enhanced pulse counting capabilities Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ± 20% 48/60 V RL ±...
Page 26
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 11. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250V AC/DC Number of outputs...
Page 27
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Influencing factors Table 13. Temperature and humidity influence Parameter Reference value Nominal range Influence Ambient temperature, operate value +20 °C -10 °C to +55 °C 0.02% /°C Relative humidity...
Page 28
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Type tests according to standards Table 16. Electromagnetic compatibility Test Type test values Reference standards 1 MHz Oscillatory burst disturbance 2.5 kV IEC 60255-22-1 100 kHz slow damped oscillatory wave immunity test 2.5 kV...
Page 29
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 18. Environmental tests Test Type test value Reference standard Cold test Test Ad for 16 h at -25°C IEC 60068-2-1 Storage test Test Ad for 16 h at -40°C...
Page 30
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Wide area measurement system Table 21. Protocol reporting via IEEE 1344 and C37.118 PMUREPORT Influencing quantity Range Accuracy Signal frequency ± 0.1 x f ≤ 1.0% TVE Signal magnitude: Voltage phasor (0.1–1.2) x V...
Page 31
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Current protection Table 22. Four step phase overcurrent protection OC4PTOC (51/67) Function Setting range Accuracy Trip current (5-2500)% of lBase ± 1.0% of I at I ≤ I ± 1.0% of I at I > I...
Page 32
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 23. Four step residual overcurrent protection EF4PTOC (51N/67N) Function Range or value Accuracy lBase Operate current (1-2500)% of ± 1.0% of I at I < I ± 1.0% of I at I > I Reset ratio >...
Page 33
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 24. Four step negative sequence overcurrent protection NS4PTOC (46I2) Function Range or value Accuracy lBase Operate value, negative (1-2500)% of ± 1.0% of I at I £ I sequence current, step 1-4 ±...
Page 34
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 25. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) Function Range or value Accuracy lBase Operate level for 3I ·cosj (0.25-200.00)% of ± 1.0% of I at I £ I directional residual ±...
Page 35
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 25. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) , continued Function Range or value Accuracy Reset time, non-directional 60 ms typically at 2 to 0 x I...
Page 36
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Voltage protection Table 27. Two step undervoltage protection UV2PTUV (27) Function Range or value Accuracy Operate voltage, low and high step (1–100)% of VBase ± 0.5% of V Absolute hysteresis (0–100)% of...
Page 37
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Frequency protection Table 29. Underfrequency protection SAPTUF (81) Function Range or value Accuracy Operate value, pickup function (35.00-75.00) Hz ± 2.0 mHz Operate time, pickup function 100 ms typically...
Page 38
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 31. Rate-of-change frequency protection SAPFRC (81) Function Range or value Accuracy Operate value, pickup function (-10.00-10.00) Hz/s ± 10.0 mHz/s Operate value, internal blocking level (0-100)% of VBase ±...
Page 39
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Multipurpose protection Table 32. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input Phase A, Phase B, Phase C, PosSeq, NegSeq, 3*ZeroSeq, MaxPh, MinPh,...
Page 40
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 32. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Reset time pickup undervoltage 25 ms typically at 0 to 2 x V High and low voltage limit, voltage dependent operation (1.0 - 200.0)% of VBase...
Page 41
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Secondary system supervision Table 33. Current circuit supervision CCSRDIF (87) Function Range or value Accuracy Operate current (5-200)% of I ± 10.0% of I at I £ I ± 10.0% of I at I > I...
Page 42
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Logic Table 35. Tripping logic SMPPTRC (94) Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms Timers (0.000-60.000) s...
Page 43
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Monitoring Table 37. Measurements CVMMXN Function Range or value Accuracy Voltage (10 to 300) V ± 0.3% of V at ≤ 50 V ± 0.2% of V at V > 50 V Current (0.1-4.0) ×...
Page 44
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 40. Phase-neutral voltage measurement VNMMXU Function Range or value Accuracy Voltage (10 to 300) V ± 0.3% of V at V ≤ 50 V ± 0.2% of V at V > 50 V...
Page 45
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 44. Event counter CNTGGIO Function Range or value Accuracy Counter value 0-100000 Max. count up speed 10 pulses/s (50% duty cycle) Table 45. Disturbance report DRPRDRE Function Range or value...
Page 46
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 48. Event recorder Function Value Buffer capacity Maximum number of events in disturbance report Maximum number of disturbance reports Resolution 1 ms Accuracy Depending on time synchronizing Table 49. Trip value recorder...
Page 47
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Metering Table 51. Pulse counter PCGGIO Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value Table 52. Energy metering ETPMMTR...
Page 48
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Station communication Table 53. IEC 61850-8-1 communication protocol Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 608–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0...
Page 49
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Hardware Table 56. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 57. Water and dust protection level according to IEC 60529...
Page 50
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Basic IED functions Table 61. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out Table 62. Time synchronization, time tagging...
Page 51
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 65. IRIG-B Quantity Rated value Number of channels IRIG-B Number of channels PPS Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
Page 52
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Inverse characteristic Table 66. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷...
Page 53
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 67. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è ø...
Page 54
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 68. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic td = (0.05-999) in steps of 0.01 IEC 60255-151, 5% + 40 ×...
Page 55
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Table 70. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 5% +40 ms æ ö VPickup V ç...
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 19. Ordering Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections.
Page 57
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Current protection Four step phase overcurrent protection (OC4PTOC, 51/67) Qty: 1MRK 002 906-BD Four step residual overcurrent protection (EF4PTOC, 51N/67N) Qty: 1MRK 002 906-DD Four step directional negative phase sequence overcurrent protection (NS4PTOC, 46I2)
Page 58
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 First local HMI user dialogue language Rule: One must be ordered HMI language, English IEC 1MRK 002 930-AA HMI language, English US 1MRK 002 930-BA Optional hardware Human machine hardware interface Rule: One must be ordered.
Page 59
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Analog system Note: The same type of connection terminals has to be ordered for both TRMs Transformer input module, compression terminals 12I, 1A, 50/60 Hz Qty: 1MRK 002 247-CG...
Page 60
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Transformer input module, ring lug terminals 6I+6V, 5A, 50/60 Hz Qty: 1MRK 002 247-AD Transformer input module, ring lug terminals 3I, 5A+3I, 1A+6V, 50/60 Hz 1MRK 002 247-AF Qty: Note: One Analog digital conversion module, with time synchronization is always delivered with each Transformer input module.
Page 61
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Binary input/output modules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Binary input module (BIM) 16 inputs RL 24-30 VDC, 50 mA...
Page 63
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 GPS antenna and mounting details GPS antenna, including mounting kits Quantity: 1MRK 001 640-AA Cable for antenna, (Appx. 65 ft) Quantity: 1MRK 001 665-AA Cable for antenna, (Appx. 131 ft)
Page 64
Phasor measurement unit RES670 ANSI 1MRK511254-BUS B Customized Product version: 1.2 Manuals Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical reference manual, Installation and commissioning manual, Application manual and Getting started guide), Connectivity packages and LED label template is always included for each IED.
Page 65
670 series SPA and signal list 1MRK 500 092-WUS IEC 61850 Data objects list for 670 series 1MRK 500 091-WUS Engineering manual 670 series 1MRK 511 240-UUS Communication set-up for Relion 670 series 1MRK 505 260-UEN More information can be found on www.abb.com/substationautomation.
Page 67
ABB Inc. 3450 Harvester Road Burlington, ON L7N 3W5, Canada Phone Toll Free: 1-800-HELP-365, menu option #8 ABB Mexico S.A. de C.V. Paseo de las Americas No. 31 Lomas Verdes 3a secc. 53125, Naucalpan, Estado De Mexico, MEXICO Phone (+1) 440-585-7804, menu...