Heat recovery unit ALTAIR Supply air (SUP) Extract air (ETA) Outdoor air (ODA) Exhaust air (EHA) G4 filter (outdoor air) G4 Filter (extract air) Exhaust air fan Supply air fan Counterflow heat exchanger Humidity sensor Condensation water connection Power supply cable Control Drain duct Remote control (inlcudes 10m cable)
Page 3
l. GENERAL l. GENERAL 1.1 - Warnings 1.1 - Warnings This product was manufactured according to rigorous technical safety rules in compliance with DC This product was manufactured according to rigorous technical safety rules in compliance with DC standards. The DC declaration and the manual can be downloaded from the Internet. standards.
Page 4
1.2 - Safety instructions • Wear appropriate IPE (Individual Protection Equipment) before any intervention. This appliance can be used by children aged from 8 years and above and persons with reduced • Before installing the unit, make sure that the support and placement are sufficient resistant to withstand the physical, sensory or mental capabilities or lack of experience and knowledge if they have been units weight.
Page 5
caused by negligence, lack of monitoring, or servicing; faults due to the incorrect installation of the devices or to bad storage conditions before mounting. bad storage conditions before mounting. In any case, S&P will not be responsible for transformed unit, repaired even partially. In any case, S&P will not be responsible for transformed unit, repaired even partially.
Page 6
2.2 - Dimensions and electric connection: included 10m cable type HV05-F-4G0,25 (max. length 50 m) REMOTE CONTROL SPCM-1 (optional) included 10m cable type HV05-F-4G0.25 blue (max. length 50 m) blue blue white green white white green green ~230V 50/60Hz ~ 230V, 50/60Hz...
Page 7
Wall: 2.3 - Installation 2.3 - Installation Wall: 2.3 - Installation Wall: Wall: To avoid the vibration transmission and noise to the duct, we recommend to use flexible connections. Supply/Extract Air: Installation of flexible silencers type LAF 95 (article code: 5209358600 / LAF 95 0,5M or 5209358500 / LAF 95 1M) To avoid the vibration transmission and noise to the Outdoor/Exhaust Air: connection with flexible duct...
Page 8
2.4 - Start up – Installer 2.4 - Start up – Installer The remote control allows to adjust: The remote control allows to adjust: - Airflows (3 speeds) - Airflows (3 speeds) - Period for filter maintenance - Period for filter maintenance - Balance of supply/extract airflow - Balance of supply/extract airflow To adjust the speed please turn the corresponding potentiometer with a small screw driver in the wished...
Page 9
Adjustment of the filter maintenance period It is possible to set the period to 6, 9, 12, or 15 months (12 month factory setting). The filter clogging depends on the pollution of the area where the unit is installed. We recommend checking the time in which the filter clogs and adjusting this period.
Page 10
Adjustment of the relative humidity % The Altair has as a standard a humidity sensor in the extract air installed. This sensor allows to adjust the velocity in dependence of the relative humidity in the extract air. The upper limit of the relative humidity can be adjusted with the potentiometer as shown below (factory setting position A = 84% rH).
Page 11
Electronic board description without function without function DIP SWITCH 6: 1 (Default command) - 0 (SPCM) without function Set point humidity sensor. No function in case of connection of the SPCM-1 Module. USB connector (for software updates) temperature sensor humidity sensor extract fan supply fan power supply motors (230V/50Hz)
Page 12
Remote control adjustments – user airflow adjustments automatic mode Speed adjustment Pressing the “speed adjustment” buttons you can change the airflow. The LED of the active botton will light green (left fan symbol= decrease speed, right fan symbol=increase speed) low speed medium speed hight speed Automatic mode...
Page 13
2.5 - Filter maintenance: We recommend a periodical maintenance of the filters (minimum 1x year). After the adjusted period de alarm will be activate. For changing the filter, please remove the plastic taps (1) put the filters (2) out and substitute them with new ones.
Page 14
2.7 - Alarm Index Through the LED located in the “A” button on the remote control it is possible to supervise the status of the unit. This LED will show the alarm in case of a failure or missfunction on the unit. Depending on the risk level of the generated alarm the unit will stop for safety reasons.
Page 15
Waste Management Plant at the end of its servicable life. 2.10 - ErP data Ecodesign Commission regulation (EU) N°1253/2014 of July 2014 Information requirements (Annex V) ALTAIR 120 V Trade mark S&P Identifier 5153811200 SEC average climate (kWh/(m².an))